IQ – In Control 3
IQM – Standard Facilities 4
IQM – Optional Facilities 5
IQM – Actuator Control Circuits 6
IQM – Optional Features 7
IQM – Remote Digital Control Circuits 8
IQML10 to IQML25 Actuator Dimensions 9
Rotork actuators have been in use all around At the heart of the company is an exceptional workforce -
the world for over 50 years. In this time Rotork the highly trained, forward-thinking engineers, technicians
and support staff who each have a crucial role to play in
has grown to become the leader in the valve
maintaining Rotork’s unrivalled reputation for innovation,
automation industry. With manufacturing, reliability and first class customer support.
service centres, offices and representatives
The Rotork family of products also includes pneumatic,
throughout the world, Rotork is able to offer
hydraulic and electro-hydraulic actuators as well as a
global service solutions to your company. comprehensive range of gearboxes and valve accessories.
Rotork’s bespoke Pakscan digital control system offers market
In the 50 years since the company was founded, Rotork has leading features whilst all our actuators offer the ability to
become a byword for excellence in the field of valve, sluice interface with other digital control systems.
gate and damper actuation products for the oil, gas, power,
water and waste treatment industries - worldwide. Rotork. Established leaders in valve actuation technology.
2
IQ - In Control
IQ Pro - the first valve actuator you New Setting Tool Pro Setting Tool Specification
can commission and interrogate Configuration and datalogger files Waterproof IP67, Certified EEx ia
without removing electrical covers. can be extracted from the actuator IIC T4 (intrinsically safe).
With the infra-red IQ Setting located in the field using the Setting
Tool Pro and PC based IQ-Insight, Power Supply 2x AA 1.5 V Batteries
Tool Pro for transfer to office based
commissioning and analysis of IQ (supplied & fitted).
PC. The Tool is watertight and
Pro actuators is simple, fast and intrinsically safe so can be used in Operating range 0.75 m from actuator
convenient. wet and/or hazardous areas. Data display window.
upload/download is non-intrusive via
IQ Insight –Actuator Setting Tool(s) are dispatched with
IrDA™. The tool can store up to 10
each order. Setting Tools are suitable
configuration and analysis configuration files or 4 datalogger files
for use with any IQ or IQT range
tool for PC. (which includes unit configuration file.
actuator.
IQ-Insight PC software allows all IQ If required, a PC running IQ-Insight
For more information on Setting
set-up configuration and datalogger with a USB IrDA™ dongle can be
Tool and commissioning, refer to
information to be reviewed, analysed directly connected to an actuator to
publication E170-3E.
and reconfigured. The visually allow set-up, adjustment and analysis.
interactive application is a stand-alone Alternatively, a PDA running IQ Pocket-
program running under Microsoft Insight, may be used.
Windows 2000™ or XP™ operating For more information refer to
systems. Intuitive and clear menus publication E117E available at
make analysing data from an IQ simple www.rotork.com.
and fast.
Features:
• Actuator configuration.
• Valve torque profile - open/closed
instantaneous and average torque
against valve position.
• Virtual nameplate.
• Number of operations.
• Control option card configuration.
• Valve and actuator position
starts log.
• Operation signal log.
• Actuator control status log.
• Operational statistics.
4
IQM - Optional Facilities
Optional Facilities Action on loss of input signal: Current Position Transmitter (CPT)
The following optional facilities are Stay-put or move to high signal The CPT provides an internally
available, and are covered by the position or move to low signal powered electrically isolated 4-20 mA
appropriate alternative wiring diagrams position. Available for minimum analogue valve position feedback
as indicated in the wiring diagram set ‘low’ signal of 0.5 mA. Response signal, which is available at terminals
number matrix on page 5. on loss of signal will occur if signal falls 22 (+ve) and 23 (-ve). The maximum
below 50% of set ‘low’ signal. external impedence that may be
Folomatic Controller connected to the signal is 500 ohms.
Overall accuracy (actuator Repeatability is within ±1% and
The Folomatic enables standard IQM mechanical output position/ linearity ±2.5% of total valve travel.
actuators to control the position of demand value):
a valve in proportion to an analogue 0.5% of maximum signal with Extra Indication Contacts
current or voltage signal. dynamic braking and minimum
of 10 turns for full valve stroke, The extra indication contacts option
A voltage derived from the actuator
assuming a deadband setting of provides four additional changeover
position sensor is electronically
<0.2%. contacts, S5, S6, S7 and S8. Each
compared with a voltage proportional
contact is latching, volt free and rated
to the input signal. The difference
at 5 mA to 5 A, 120 VAC, 30 VDC.
between them (error) triggers the Connections
The extra indication contact functions
open or close thyristor circuit, via The analogue signal should be
are independently configurable in the
logic circuits, to drive the actuator connected to terminals 26 (+ve) and
same way as the standard contacts
in the direction which will cancel 27 (-ve). If no remote manual control
using the IQ Setting Tool Pro. The
the error. Valve position is therefore is required, link terminals 39 to 5
indication contact functions are
automatically adjusted in proportion and 41 to 4. Terminal 39 is provided
shown below:
to analogue signal. Unnecessarily for remote manual/auto selection.
frequent switching is prevented by the The remote control connections for • Valve Position
Motion Inhibit feature. actuators to standard wiring diagrams Fully open, fully closed or
are as follows: intermediate positions
The Folomatic can be configured to
(0-99% open).
suit the following: Auto
39
•
To external supply line/+ve Status
Analogue signals/ Manual
Link 36-41 and Valve opening, closing, moving
connect 0/-ve
input impedence: of supply to 36 (continuous or pulsing signal),
0-5 mA/1 kΩ 0-5 V/1 MΩ
Close local stop selected, local selected,
33
0-10 mA/500 Ω 0-10 V/78 kΩ remote selected, open or close
Open
0-20 mA/250 Ω 0-20 V/52 kΩ 35 interlock active, ESD active.
• Valve Alarms
Position corresponding to low Fig 1a. Externally fed remote controls Motor tripped on torque
input signal: in mid travel, motor tripped
Closed limit, or percentage Open Manual on torque going open, going
Link terminals 4-36-41
or Open limit. 5 closed, valve jammed,
Auto actuator being operated by
39
Position corresponding to high hand wheel.
Close
input signal: 33 • Actuator Alarms
Closed limit, or percentage Open Open Lost phase, customer 24 VDC
or Open limit. 35
supply lost, battery low,
actuator alarm, thermostat
Deadband: Fig 1b. Internally fed remote controls
tripped.
0-9.9% of travel between Open
The following optional facilities
and Closed limit positions.
available on standard IQPro actuators
are also available on IQM units.
Motion Inhibit time:
2-99 secs. between actuator Negative Switching
movements. (see publication E120E)
Interrupter Timer
(see publication E120E)
Pakscan
(see publication S000E)
Positive switching remote controls. Refer to Rotork for non-standard voltage option. Type 1
Circuit is drawn with power supply off. TAP NOM 50/60 HZ 50 HZ 60 HZ
W 220/230 176-242 198-259
X 380/400 304-418 342-446
Y 415/420 332-457 374-487
Z 440/460 352-484 396-517
Fuse FS1 - 250 mA Anti-Surge
Type 2
6
IQM - Optional Features
Remote 30
Selected S8 46
47
IQ Setting Tool Pro Configuration In addition, the IQ Setting Tool Pro will
enable configuration of the following
The IQ Setting Tool Pro makes it The following actuator functions are optional assemblies when fitted to the
possible to read and set all the configured by the IQ Setting Tool Pro: actuator:
actuator functions, such as valve travel
and torque or travel limit control, • Direction of actuator output • CPT - selection of open or closed
without removing any covers. The rotation for closing the valve. valve position corresponding to a
IQ Setting Tool Pro transmits signals
• Selection of torque or turns maximum signal.
to an infra-red receiver built into the
limitation for valve opening and • Pakscan - address, baud rate
actuator.
closing travel. and protocol.
The IQ Setting Tool Pro has a
• Torque setting for Open and Close • Folomatic - signal range,
‘programming’ mode which enables
valve operation. increasing signal is to correspond
the valve manufacturer to configure
the actuator to suit his valve and • Setting of actuator output turns to to opening or closing of the valve,
the site commissioning engineer to suit the valve travel. action on loss of signal, amount of
configure the actuator for a variety deadband and the motion inhibit
• “Open/close” remote control time delay.
of different control functions. The
signal priority.
IQ Setting Tool also has a ‘checking’
mode which enables all the existing • Selection of function and contact Publication E170-3E, supplied with
actuator settings to be interrogated. mode for each of the four each actuator gives full instructions for
Protection against unauthorised standard indication contacts. the operation of the IQ Setting Tool Pro.
changes to setting is provided by a
• Valve to Open or Close with
‘password’.
ESD signal.
• External interlock facility.
es)
tch
The typical remote control circuits
wi
ro)
s
shown below apply to these unless
ss ( /
DIL
(ze
pa wn
VD
4 V te
otherwise stated.
DC
-ve
n 2 mo
tdo
24
ls o r re
ost shu
ply
ply
by
le
le
sup
sup
tro fo
ab
ab
at
rm cy
ain
con on
the en
en
en
al
al
Max. external load on 24 VDC supply from actuator
mm
erg
ern
ern
int
ke
ke
en
se
Bra
Bra
Clo
Ma
Em
Op
terminals 4-5 to be 5 W.
Int
Int
Co
Form A 4 36 33 34 35 5 25
Open/close push to run control (local control remains
†
self maintained).
Close Open
To external 24 VDC supply or
terminal 5 (see note † below)
Form F
4 36 33 34 35 5 25
Emergency shut-down to close valve overriding
thermostat (actuator hazardous enclosure certification †
is invalidated while thermostat overidden) and any ESD switch
existing signal may be added to any of the circuits
To external supply or
above. terminal 5 (see note † below)
Actuators may be configured so that thermostat is
by-passed during ESD operation.
To override external interlocks on ESD additional
remote contacts must be provided.
4 24 30 5
Brake enable connections
† Note
8
IQML10 to IQML25 Actuator Dimensions
IQML10 IQML25
10
0 pt
Notes
www.rotork.com