1. Objective ............................................................................................................................................................... 3
2. Scope of Application ........................................................................................................................................... 3
3. Reference Documents ........................................................................................................................................ 3
4. Codes and Standards ......................................................................................................................................... 3
5. Terminology, Definitions, Abbreviations ........................................................................................................ 4
6. Requirements ....................................................................................................................................................... 4
6.1. Cable Technical Requirements ....................................................................................................................... 4
6.2. Special Cables .................................................................................................................................................. 5
6.2.1. High temperature cable (If applicable) ........................................................................................ 5
6.3. Laying conditions .............................................................................................................................................. 5
6.4. Cable Marking Requirements .......................................................................................................................... 6
6.5. Drum Requirements and Cable Length .......................................................................................................... 6
6.6. Drum Marking Requirements........................................................................................................................... 6
7. Test Requirements .............................................................................................................................................. 7
8. Documentation..................................................................................................................................................... 7
9. CONTRACT EXTRACT ........................................................................................................................................ 8
Cable management .................................................................................................................................. 8
1. OBJECTIVE
This document defines the requirements for (I&C) Instrumentation and Control Cables.
Instrumentation and Control Cables are used to connect signals from field devices to the I/O modules
of the DCS system by means of hardwiring.
2. SCOPE OF APPLICATION
24 VDC from potential free contacts from field devices such as level switches, position
switches, valves, contacts and interposing relays from electrical panels.
0/4...20 mA from field transmitters such as temperature, pressure and position transducers
3. REFERENCE DOCUMENTS
none
ASTM D2863 Standard Test Method for Measuring the Minimum Oxygen Concentration to
Support Candle-Like Combustion of Plastics (Oxygen Index)
EN 50288-7 Multi-element metallic cables used in analogue and digital communication and
control Sectional specification for instrumentation and control cables
EN 50525-3-11 Electric cables. Low voltage energy cables of rated voltages up to and
including 450/750 V (U0/U). Cables with special fire performance. Flexible
cables with halogen-free thermoplastic insulation, and low emission of smoke
IEC 60332-3-24 Tests on electric cables under fire conditions – Part 3-24: Test for vertical
flame spread of vertically-mounted bunched wires or cables – Category C
IEC 60364-5-51 Electrical installations of buildings - Part 5-51: Selection and erection of
electrical equipment - Common rules
IEC 60811 Common test methods for insulating and sheathing materials of electric cables
6. REQUIREMENTS
These cables should be suitable for working temperature of 200 °C. Insulation of cable shall be silicon
or equivalent suitable for higher temperature. These cable are mentioned as High temperature cable
(HT) in BOQ document.
Suitable for underground conduit or pipe, with possible water ingress from pull pit or pipe cracks, wet
or moist condition, conditions may continue over prolonged period of entire plant lifetime.
Suitable for use in hazardous areas (Ex Zone) in accordance with EN60079-14 and suitable cable
glands.
The cable shall be embossed or ink-jet marked with the following data:
Sequential marking of length of the cable in meters at every one meter. The embossing /
engraving shall be progressive, automatic, in line and marking shall be legible and indelible.
Cable designation
Name of manufacturer
Date of manufacturing
Example:
<1234M LiYCY 8x2x0.75MM2 PiMF/TriMF* MANUFACTURERNAME YEAR
*) PiMF (pairs in metal foil)
TriMF (triples in metal foil) as applicable
Cable drums shall be non-returnable and shall be made of timber. The ends of all cable lengths shall
be sealed to prevent ingress of moisture. Cables on drum shall be protected by a wrapped foil and
wooden sheets.
The cable on the drum shall be uninterrupted. The ordered length shall be spread to as little drums as
possible; drums shall be filled to its capacity.
The cable drum shall be marked on the outside of one flange with the following data:
Cable voltage and number of pairs
Conductor stranding, material and size
Insulation type and thickness, outer diameter of cable
Length and weight of cable on drum
Gross weight and dimensions of drum
Manufacturer's name and country of origin
Expedition address and purchase order number
Nr identyfikacyjny / Identification number Zm./ Data / Date Język / Str./
Gas Power Systems 1GP033986 Rev. Lan Sheet
A en 6/9
© COPYRIGHT 2020 General Electric Company Wewnętrzny
Wszelkie prawa zastrzeżone. Informacje zawarte w niniejszym dokumencie stanowią wyłączną własność firmy General Electric Company i/lub jej spółek podrzędnych.
The cable on the drum shall be provided with the sequential length-meters, marked at consecutive
intervals of one (1) meter. The length markings shall be started at the inner ends of the drum.
7. TEST REQUIREMENTS
The following tests shall be performed in accordance with the latest issue of the applicable standard.
Existing type test certificates are acceptable.
- conductor resistance
- dielectric strength
- Insulation resistance
- Check of dimension:
- thickness of insulation
- thickness of non-metallic sheath
- outer diameter
- mechanical test
- Insulation resistance
- Mutual Capacitance
- Capacitance unbalance
- Inductance
- L/R ratio
8. DOCUMENTATION
9. CONTRACT EXTRACT
Cable management
Cables must meet the requirements of the most recent PN-EN IEC standards, CPR Directive, as well as:
1. Signal cables shall have stranded conductors and 0.3/ 0.5 kV insulation,
2. Power supply cables shall have 0.6/1 kV insulation,
3. Cross-section of the signal conductor must not be smaller than 0.5 mm2,
4. Conductor cross-section of the power supply cable which feeds the I&C equipment must not be smaller
than 1.5 mm2.
5. Signal cables and power supply cables shall be separated wherever possible.
6. Collective twin screened pairs with 24 or 48 conductors are permitted,
7. Collective signal cables should be provided with conductor reserve of at least 15%,
8. Optical fiber cables should be provided with fiber reserve of at least 30%, not less than four fibers – 2
pairs,
9. For communication cables with a length exceeding 90 m, optical fiber cables should be used,
10. In a particularly hazardous area (high-temperature or risk of mechanical damage) cables with proper
resistance class should be used (e.g. in accordance with PN-EN 60332 standard or equivalent European
standards),
11. Signals for the needs of special measurements shall be transmitted by means of shielded cables in
accordance with the requirements of equipment manufacturers (e.g.: shielded pairs, shielded triples),
12. Signals having the same potential shall be transmitted by multi-conductor cables,
13. All cables (except for optical fiber cables) and conductors must be made as stranded copper conductors
with halogen-free or PVC insulation; in special cases cables with an additional shield should be provided
(steel-wire armored),
14. For intrinsically safe equipment, cables of appropriate type which also meet the above-specified
requirements are recommended.
15. Cables with halogen free or PVC insulation and external sheath to prevent the flame propagation shall be
applied meeting the requirements of PN-EN 603322-24 category C, or equivalent European standards.
This requirement does not apply to special cables, e.g. intrinsically safe, high temperature or oil resistant,
coaxial, TCP/IP network cables, as well as earthing and internal connection cables in cabinets/boxes,
which should comply with the standards for this type of cables.
16. Signal cables, power supply cables (impulse tubes, digital data transmission cables, etc.) shall be laid
taking into account the requirements set out in the SEP-E-004 standard and the requirements of the
applied DCS.
17. I&C cables shall be conducted with the use of main cable routes, designed and executed within the
framework of the electrical part, on separate cable ladders and racks.
18. Cables in enclosed rooms should be conducted under raised floors on cable racks and trays or in special
ducts. For outdoor cables, the Contractor shall design and provide appropriate cable racks and trays,
starting from the main cable routes up to the individual I&C equipment (intermediate boxes, measuring
sensors and transmitters, etc.).
Nr identyfikacyjny / Identification number Zm./ Data / Date Język / Str./
Gas Power Systems 1GP033986 Rev. Lan Sheet
A en 8/9
© COPYRIGHT 2020 General Electric Company Wewnętrzny
Wszelkie prawa zastrzeżone. Informacje zawarte w niniejszym dokumencie stanowią wyłączną własność firmy General Electric Company i/lub jej spółek podrzędnych.
19. Cables at site shall be laid underground in cable conduits, cable ducts or on cable racks and trays. Buried
cables shall be additionally protected in places where there is a risk of their damage. They shall be
protected by means of protective elements, such as steel pipes, concrete culverts, etc.
20. Cables of different classes shall be laid on different racks and ladders in the following sequence from top
to bottom: HV power cables, LV power cables, signaling cables
21. (deleted)
22. Electric shock protection system inspection certificates shall be provided by the Contractor in accordance
with PN-HD 60364-4-41 Polish standard.
23. The routes of the bus network for the master communication (redundant) should be independent and
should protect cables from physical damage and impact of external electromagnetic fields,
24. The main cable routes shall be provided with a reserve of at least 30%.
25. Optical fiber cables shall be laid in cable conduits,
26. All cables shall be permanently marked on both ends, as well as at places of penetrations. Marking
technology shall be adjusted to the local conditions and shall secure legibility over a long period of time.
KKS codes shall be compliant with the Employer’s requirements.
Compensating/thermoelectric cables:
The principles of selection, layout, marking and acceptance tests specified in the Appendix to the I&C part
PFU_02.Zal6 shall apply to the cable routes and cables in the I&C part.