SUBSTATION PREVENTIVE MAINTENANCE PROCEDURE

POWER CIRCUIT BREAKER TEST REPORT

Location: BridgetowneMakati Type: WSA 6/36-2/623 Weather: Cloudy


Switch No.: 417MAK4BRI SCIC: 16kA Amb. Temp.: 30oC
Make: Schneider Electric kV: 36 Rel. Hum.: 60%
Serial No.: TO574967-1899478-1 Amp.: 1250

Function: [ ] Line Breaker [ ] Bank Breaker [ ] Cap. Bank Breaker [ X ] Tie BreakerStation Service
Insulating Medium: [ ] Oil [ X ] SF6 [ ] Air [ ] Vacuum
[X ]
Reason for Test: [ ] PMT [ ] Servicing [ ] Faulted Others:_______________New

I. TIMING TEST

A. OPERATION: CLOSE

PARAMETERS VALUE UNIT


Close Time A 41.4 ms

Close Time A 41.3 ms

Close Time A 41.6 ms

B. OPERATION: OPEN
Retention: Twenty (20) years EQUIPMENT LIFE
SUBSTATION PREVENTIVE MAINTENANCE PROCEDURE
POWER CIRCUIT BREAKER TEST REPORT

PARAMETERS VALUE UNIT


Open Time A 41.6 ms

Open Time A 41.7 ms

Open Time A 41.5 ms

VISUAL INSPECTION
Oil Level / SF6 Pres. Main Contacts Control Mechanism
Contamination Wooden Members Condition
Grounding Interrupters Clearance

LEAK TEST / CHECK [ ] No leaks found [ ] Leaks found at: (enumerate below)

Instruments Used: CBA-1600366


Remarks: SATISFACTORY TEST RESULTS

Date: September 13November 18, 2019 Received by:

Tested by: ED2, RG, AEEM GF JS AE (4040) Checked by:

Witnessed by: Mr. Abarquez Approved by:

Retention: Twenty (20) years EQUIPMENT LIFE