You are on page 1of 2

Arc-wall and arc-electrode interactions are dominant phenomena.

Pressure (ba)
.........
Computed solution Indeed, we estimate that in a medium voltage circuit breaker more than
Experiments 75 percent and in a low voltage circuit breaker more than 90 percent
of the arc energy is absorbed by walls and electrodes.
1.0 We have developed a model which is built on an energy balance at
the boundary between the flow and the wall (or the electrode). In the
gas SF6, we solve the Navier Stokes equations and, in the wall material,
we account for thermal conduction.
0.5 With the above model, a computation has been done on a puffer
circuit breaker geometry. In this kind of breaker, a piston creates an
over pressure creating a flow along the electrical arc. The flow is guided
by a loaded teflon nozzle. During the switching phenomenon, the
electrical arc induces ablation of the nozzle material. Figure 3 presents
Time (ms)
comparisons of the pressure in the puffer chamber.
0.0 3.(0

Figure 1. Comparisons of the pressure in the expansion volume


Transformers

96 WM 224-6 PWRD, T-PWRD October 1996


Arc Voltage (V) EHV Transformer Bank Unbalance:
Practical Issues and Solutions
R. Gutman (Senior Member, IEEE; American Electric Power
Service Corporation, Columbus, OH), L.B. Wagenaar (Senior
Member, IEEE; American Electric Power Service Corporation)
50 An unconventional tap configuration has been implemented in
AEP's South Canton 765/345/34.5 kV, 3-500 MVA transformer bank
to counter the combined effects of impedance mismatch within the
bank and natural unbalance of the extra-high-voltage (EHV) transmis-
sion system. These effects manifest themselves as unequal phase volt-
Tinme (ms) ages and loadings and as elevated neutral and tertiary circulating
3.0 6.0 9.0
currents in the bank. This paper describes the South Canton bank
unbalance, the concerns it raised, and the actions taken by AEP to
Figure 2. Comparisons of the arc voltage (i=8 kA, 50 Hz) control its possible adverse effects on the integrity and operation of the
South Canton Station facilities.
South Canton Bank Unbalance: Heavy loadings with signifi-
Pressure (ba) ~ experimenEs cantly unbalanced phase currents were observed in the South Canton
bank of three single-phase 765/345/34.5 kV, 500 MVA transformers
following their return to service with a new, mismatched transformer
in the Phase 1 position. On-site measurements taken by field personnel
on several occasions, supplemented by three-phase readings from the
AEP data acquisition system, confirmed the presence of this unbal-
anced operating condition. The condition raised concerns about possi-
ble overloading of one or more phases of this bank, which provides
principal supply of electric service for Canton, Ohio and the surround-
ing communities. In addition, unbalance effects had been observed in
the neutral and tertiary connections of the bank, where current flows
were reaching relatively high magnitudes. Sustained exposure to high
neutral currents was deemed undesirable due to potential safety prob-
lems in the station, accelerated corrosion of the station grounding mat
6 9
and its neutral connections, and possible interference with nearby
Figure 3. Comparison of pressure in a puffer circuit breaker telecommunication lines.
The new South Canton single-phase transformer represents a con-
We assume that a part of the spectrum of the emitted light is absorbed siderable mismatch at that station; its high-to-low reactance, tertiary
in the cold gas and that another part isn't absorbed (this part is called reactance, and summer-normal rating are about 30 percent higher, 50
the thin radiation). The absorption in the cold gas is defined using an percent higher, and 10 percent lower, respectively, compared with the
exponential law, determined through experimental measurements. transformers operating in Phases 2 and 3. The South Canton trans-
To validate the model, a thermal expansion medium voltage circuit former bank is fed radially from Kammer Station through an 80-mile
breaker has been simulated. The switching principle of thermal expan- 765 kV line which, by itself, is a source of unbalance because of its
sion circuit breaker is the following: the electrical arc heats the gas in flat nontransposed configuration.
the expansion volume, press then increases; at the current 0, this Several strategies were considered for controlling the South Canton
over-pressure blows the arc. The validation consists in a comparison
bank unbalance, including energization of a single-phase 100 MVAr
spare shunt reactor located at Kammer, changing tap(s) on one or more
between experiments and calculations for the pressure in the expansion
volume together with the arc voltage. The peak of current is 8 kA and phases of the South Canton bank, inserting an air-core reactor in the
the arc's time 9 ms (Figure 1 and Figure 2). The good agreement bank's tertiary delta, and opening the delta and/or neutral connections.
between experiments and computations shows that macroscopically the All of these methods were analyzed for their effectiveness in reducing
energy exchanges are well taken into account.
the bank unbalance, but the last two were dismissed due to increased
equipment risk. Consideration was also given to changing the assigned

54 IEEE Power Engineering Review, October 1996


phase positions of the South Canton transformers by either electrical previous experience while the fuzzy-set represents the decision rules
reconnection or physical moves, but the high cost of this approach by using vague quantities. Artificial neural network method (ANN) has
made it difficult to justify. also been used for this purpose since the hidden relationships between
Raising taps on Phase 2 and 3 transformers by one position to the fault types and dissolved gases can be recognized by ANN through
746 kV, while holding the Phase 1 tap at 727 kV, was considered training process.
sufficiently effective and secure, and was selected for implementa- A two-step neural-network classifier has been developed and care-
tion. A number of other tap arrangements were also studied, but fully tested for transformer fault diagnosis using dissolved gas-in-oil
none were found as effective. The selected approach, while uncon- analysis. Several feature types have been evaluated and several neural-
ventional, reduces the neutral and delta currents in the South Canton net topologies have been considered. Patterns with different identifica-
bank by about 50 percent and 10 percent, respectively. The added tion sensitivity are detected by different ANNs to obtain the highest
advantages of this approach include lower reactive flow through the accuracy for each pattern. The two-step approach makes ANN easier
bank and improved voltage profile on the 345 kV bus. The 765 kV to train and more accurate in detecting faults.
bus voltages at South Canton are more unbalanced as Phases 2 and The results of this study show that the two-ANN approach is prom-
3 rise by about 1.5 percent each, but this is expected to pose no ising for transformer fault diagnosis even with limited sample data.
operating problems even during light load conditions. Voltages at Theoretically, the ANN can be trained to represent any observable
Kammer rise by less than 0.5 percent. Load losses in the South phenomenon if there are sufficient data available. The more complex
Canton bank are reduced by up to 70 kW, or 3-4 percent. Similar a relationship is, the more training data are needed. The transformer
performance improvements, although smaller in magnitude, exist fault diagnosis could be very complicated. For example, it is desirable
during other operating conditions. to distinguish between faults of oil and cellulosic materials (paper),
Conclusion: As the remaining useful life of existing EHV trans- different temperatures (low, medium, and high) for overheating, in oil,
formers declines over time and these transformers are replaced with or low energy and high energy sustained arcing. To deal with such a
new units of different designs, purchased from new suppliers world- complicated diagnosis problem, the available input data may not always
wide, the use of dissimilar single-phase transformers in a common be enough. It can be a very effective way to construct different ANNs
bank has and will become more widespread. Experience shows that for different pattern recognitions to obtain the highest diagnosis accu-
unbalanced operation of transformers is technically feasible, pro- racy for each pattern.
vided that the capability of each of the single-phase transformers is The accuracy of the diagnosis can be improved with the increase
adhered to and care is taken to control their neutral and tertiary of training data. Another very important part of dissolved gas-in-oil
circulating currents, including possible adverse effects of these analysis is evaluation of trends - the increasing rates of gas generation.
currents on station facilities. Once this information is available, the diagnosis can be made more
It is noteworthy that the operating condition achieved at South reliable. Due to the limited trend data available, this work will be done
Canton through the use of unbalanced transformer taps would be at a later stage.
attainable with no tap changes, if transformer reactance mismatch were
only about one-third of that actually encountered. Further work in this
area could provide useful insights with regard to both acceptable manu-
facturing tolerances for single-phase EHV transformers and operational Transmission and Distribution
flexibilities available to the electric utilities.
95 ESMO, T-PWRD October 1996
Transmission Towers Inventory
96 WM 225-3 PWRD, T-PWRD October 1996
VI. Kogan (Senior Member, IEEE; American Electric Power
An Artificial Neural Network Approach Co., Columbus, OH), R.J. Gursky (Member, IEEE; American
to Transformer Fault Diagnosis Electric Power Co.)
Y. Zhang (The Bradley Department of Electrical Engineering, The transmission network of an electric power utility constitutes a
Virginia Tech, Blacksburg, VA), X. Ding (Virginia Tech), Y Liu critical part of the whole power system. It is clearly not desirable to
(Virginia Tech), PJ. Griffin (Doble Engineering Company, lose any major transmission lines for longer than a few weeks because
Watertown, MA) of the increased probability of loss of load for multiple contingencies.
Because new transmission towers are not readily available, it is impor-
As a major apparatus in a power system, the power transformer is tant to maintain an adequate inventory of towers to prevent long-term
vital to system operation. Techniques for diagnosis and incipient fault outages.
detection are valuable. This paper discusses a statistical procedure to analyze failure data
A transformer is subject to electrical and thermal stresses. These for transmission towers and to determine adequate levels of inventory.
two stresses could break down the insulating materials and release The failure of a transmission tower is defined as a damaged condition
gaseous decomposition products. Overheating, corona and arcing are that prevents operation of the associated transmission line.
three primary causes of fault related gases. Principally, the fault related A standard approach to inventory assessment is to minimize the
gases commonly used are hydrogen (H2), carbon monoxide (CO), expected cost of a reasonable number of spares. That cost is a sum of
carbon dioxide (CO2), methane (CH4), acetylene (C2H2), ethane two parts: one is associated with cost of owning spares, another is
(C2H6), and ethylene (C2H4). The analysis of dissolved gases is a associated with the cost of nonavailability of spares. Unavailability of
powerful tool to diagnose developing faults in power transformers. transmission towers may lead to the inability to supply power to the
Many diagnostic criteria have been developed for the interpretation of utility's customers, which is unacceptable. Therefore, the cost of
the dissolved gases. These methods would find the relationship between nonavailability of spares is assumed to be so large that the above
the gases and the fault conditions, some of which are obvious and some mentioned standard approach is inapplicable.
of which may not be apparent (hidden relationships). However, much As an alternate, this paper suggests a methodology based on
of the diagnostics relies on experts to interpret the results correctly. historical data of failures, using the homogeneous Poisson process
New computer-aided techniques can consistently diagnose incipient- (HPP) as a mathematical model of the failure process. Such a choice
fault conditions for the novice and in some cases may provide further is based on the common failure causes of transmission towers,
insight to the expert. Expert system and fuzzy-set approach have been including tornadoes, combinations of severe icing and wind, and
developed to reveal some of the hidden relationships in transformer vandalism. Theoretically, these causes could lead to tower failure
fault diagnosis. Expert system derives the decision rules from the or weakening of the structures. However, such weakening is not

IEEE Power Engineering Review, October 1996 5s

You might also like