1 2 3 4 5 6 7 8 9 10 11 12 13

55000
5000 9000 9000 9000 9000 9000 5000
3800 1200 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 1825 3175
1575

C
STO.
HE

3150
RISER
SHE DOWN
RISER
DOWN
CLASS ROOM CLASS ROOM CLASS ROOM CLASS ROOM CLASS ROOM
7000

FHC

1 2 3 4 5
9500

BLACKBOARD BASE

BLACKBOARD BASE

BLACKBOARD BASE

BLACKBOARD BASE

BLACKBOARD BASE
3850

FE FE FE FE FE
UP UP
B
DN FE FE DN
2500

C O R R I D O R C O R R I D O R C O R R I D O R

1 FIRE EXTINGUISHER AND


13 FIRE HOSE CABINET LAYOUT
50mmØ PIPE-CONNECT
DOWN TO RISER (DRYPIPE)
1 FOURTH FLOOR PLAN
FIRE HOSE CABINET (FHC) SCALE 1:100M
FP-4

FOURTH FLOOR LINE


FIRE EXTINGUISHER
SCHEDULE OF EQUIPMENT
WEIGHT
TYPE MAXIMUM VOLUME
DESIGNATION QUANTITY DISCHARGE RANGE DIAMETER EXTINGUISHING AGENT REMARKS
(LOCATION) OF PROTECTION
GROSS AGENT

FE 36 18.8 lbs. 10 LBS WALL MOUNTED 6.00 m. 15.2 cm. 51 m³ HCFC 123 ENVIRONMENT FRIENDLY, BRAND NEW AND READY FOR SERVICE

THIRD FLOOR LINE

G.A. No.16 STEEL BODY WITH WHITE PAINT FINISH

0.20
INTERIOR AND RED PAINT FINISH EXTERIOR
10 LBS. CO FIRE
EXTINGUISHER ALUMINUM FRAME FOR 3mm THK. FULL GLASS

SECOND FLOOR LINE 38mmØ ANGLE VALVE, BRONZE FINISH

mm SEMI-AUTOMATIC FIREHOSE RACK


63mm Ø G.I. SCH.40 50
38PLAIN STRAIGHT NOOZLE

0.90
6 mm x 50 mm

800 mm (H)
FLAT BAR 38mmØ X 30m FIREHOSE,
WALL 100% POLYESTER SINGLE JACKETED
BRACKET AND SYNTHETIC RUBBER LINING,
UL/FM APPROVED
12mmØ
BOLT SCREW
100mm Ø G.I. SCH.40

1.50
RISER PIPE (TYP.) G.A. 16 RED GLOSSY POLYESTER COATED STEEL
175 0.70
m CYLINDER 9Kg. ABC TYPE PORTABLE FIRE
m
EXTINGUISHER WITH HOSE, SQUEEZE GRIP
GROUND FLOOR LINE CONTROL NOZZLE AND DISCHARGE HORN
ELEVATION CONTENT PRESSURIZED AT APPROX. 195 P.S.I.

1500
WALL UL LISTED/FM APPROVED
100mm Ø FIN. FLOOR LINE
SIAMESE TWIN
CONNECTION PIPE WALL BRACKET WALL MOUNTED
100 X 63 X 63mm FIN.ISH FLOOR LINE
SIAMESE TWIN
FIRE HOSE CABINET (FHC)
2 DRY STAND PIPE RISER DIAGRAM CONNECTION 3 DET. OF FIRE DEPT. CONNECTION 4 FIRE EXTINGUISHER DETAIL 5 FIRE HOSE CABINET DETAIL
NOT TO SCALE FP-4 NOT TO SCALE NOT TO SCALE NOT TO SCALE
FP-4 FP-4 FP-4

DESIGNED: SIGNED
REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO. SHEET NO.
BENJAMIN R. GALMAK
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS ENGINEER II
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
MODIFIED STANDARD DPWH - DEPED FOURTH FLOOR FE AND FHC LAYOUT CADD: SIGNED SIGNED
BUREAU OF DESIGN SCHEDULE OF EQUIPMENT
EB FUMAR
ENGINEERING ASSISTANT
BR GALMAK
ENGINEER II
APPROVED WITH SIGNATURE BOD
FP- 2
BUILDINGS DIVISION FOUR (4) STOREY, TWENTY (20) MISCELLANEOUS DETAILS JOSEPHINE P. ISTURIS LEA N. DELFINADO GILBERTO S. REYES LEONOR M. BRIONES
CLASSROOM SCHOOL BUILDING
CHECKED: SIGNED B 8 90
CORNELIO T. EVANGELISTA JR.4 OIC, UNDERSECRETARY FOR
BONIFACIO DRIVE PORT AREA, MANILA CHIEF, BUILDINGS DIVISION OFFICER-IN-CHARGE SECRETARY, DEP ED
ENGINEER III TECHNICAL SERVICES, DPWH