Professional Documents
Culture Documents
BAE
0 18.FEB.2014 ISSUED FOR CONSTRUCTION K.H.PARK H.K.LEE S.H.BAE
A 15.NOV.2013 ISSUED FOR INFORMATION K.H.PARK H.K.LEE S.H.BAE
REV. DATA DESCRIPTION DESIGNED CHECKED APPROVED
OWNER
PROJECT
ENGINEER
CONTRACTOR
N/A
DOCUMENT TITLE
TR COMPOUND FOUNDATION
CALCULATION SHEET
TABLE OF CONTENTS
1. DESIGN CRITERIA……………………………………………………………… 3
1.1 GENERAL…………………………………………………………………… 3
1.2 MATERIAL SPECIFICATION……………………………………………… 3
1.3 DESIGN DATA……………………………………………………………… 3
1.5 DESIGN DATA……………………………………………………………… 4
2. DESIGN DATA…………………………………………………………………… 5
3. DESIGN LOAD…………………………………………………………………… 7
4. LOAD COMBINATION………………………………………………………… 20
5. STABILITY CHECK………………………………………………………………21
6. STRUCTURE ANALYSIS……………………………………………………… 26
7. MEMBER DESIGN……………………………………………………………… 32
8. REBAR SKETCH…………………………………………………………………90
Page 2 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
1. DESIGN CRITERIA
1.1 GENERAL
- Reinforcing bar (ASTM A615/A615M grade 60) (Refer to clause 4.2 of 00-TAA-C-35-001-001)
· Yield Strength : fy = 420 MPa
· Modulus of Elastic : Es = 200000 MPa
Page 3 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Load
Load Factor Remark
Combinations
L/C-1 1.0D + 1.0L + 1.0H Normal Operation
L/C-2 1.0D + 1.0W + 1.0H Empty Load + Wind Load
L/C-3 1.0D + 0.7S + 1.0H Empty Load + Seismic Load
L/C-4 1.0D + 0.75L + 0.7W + 1.0H Operation Load + Wind Load
L/C-5 1.0D + 0.75L + 0.525S + 1.0H Operation Load + Seismic Load
Load
Load Factor Remark
Combinations
L/C-21 1.2D + 1.6L + 1.6H Normal Operation
L/C-22 0.9D + 1.6W + 1.6H Empty Load + Wind Load
L/C-23 0.9D + 1.0S + 1.6H Empty Load + Seismic Load
L/C-24 1.2D + 1.0L + 1.6W + 1.6H Operation Load + Wind Load
L/C-25 1.2D + 1.0L + 1.0S + 1.6H Operation Load + Seismic Load
L/C-26 1.4D + 1.6H Test Only
※ Notations
D : Dead load
L : Live Load
H : Earth Pressure load
W : Wind Load
S : Seismic Load
-Each compound tank shall accommodate total quantity & maximum runoff quantity as follows.
Total
Reference KKS Oily Water Drainage Volume (m³) Waste Drainage Quantity (m³/s)
Area Volume (m
NO. F/F Deluge Lube Oil ³) F/F Deluge Runoff
GROUP#1 11BAT01GT001 19.00 86.69 194.00 299.69 0.03 0.14 0.18
STG TR 11BBT01GT001 19.00 41.41 58.40 118.81 0.03 0.07 0.10
Area 11BBT02GT001 19.00 38.01 43.20 100.21 0.03 0.06 0.10
GROUP#2 12BAT01GT001 19.00 86.69 194.00 299.69 0.03 0.14 0.18
STG TR 12BBT01GT001 19.00 41.41 58.40 118.81 0.03 0.07 0.10
Area 12BBT02GT001 19.00 38.01 43.20 100.21 0.03 0.06 0.10
GROUP#3 13BAT01GT001 19.00 86.69 194.00 299.69 0.03 0.14 0.18
STG TR 13BBT01GT001 19.00 41.41 58.40 118.81 0.03 0.07 0.10
Area 13BBT02GT001 19.00 38.01 43.20 100.21 0.03 0.06 0.10
GROUP#4 14BAT01GT001 19.00 86.69 194.00 299.69 0.03 0.14 0.18
STG TR 14BBT01GT001 19.00 41.41 58.40 118.81 0.03 0.07 0.10
Area 14BBT02GT001 19.00 38.01 43.20 100.21 0.03 0.06 0.10
Page 4 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
2. DESIGN DATA
Y [Unit : m]
38.30
0.25
0.45
0.45
0.45 Dike 2 ⑤ 0.45
2.55
2.10
5.025
0.25 Dike 1 ② Fire Wall 1 ⑧
P3
4.39
4.04
Dike 1 ⓛ
Fire Wall 1 ⑦
Fire Wall 2 ⑨
Fire Wall 2 ⑩
P1 P2
16.35
15.85
14.74
6.00
6.40
22.80
23.70
5.46
5.41
P4 2.05 P5 2.20
0.25 Dike 1 ③ Dike 1 ④
3.035
4.35
4.80
0.25
0.45
0.45
11.65 12.40 12.85
24.55 13.75
PLAN
[Unit : m]
X
0.30 0.30
Z 0.25
Fire Wall 2
Fire Wall 2
Fire Wall 1
Fire Wall 1
11.60
8.35
CAT UAT GUT
0.20 0.20
Dike 1
Dike 1
P1 P2 P3
1.10
Dike 2
Dike 2
SECTION
Page 5 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
※Equipment Size
Approximately Dimension of Equipment
Item
X-direction, (m) Y-direction, (m) Height, (m)
CAT 11.75 6.70 6.71
UAT 9.46 6.80 6.99
GUT 14.40 10.20 10.26
Page 6 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
3. DESIGN LOAD
1) Foundation Weight
- Concrete Weight, Wc
- Fluid Weight, Wf
- Gravel,Grating,H-beam Weight, Wg
2) Eqiupment Weight
Page 7 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
3) Eccentric Load
Page 8 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 9 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
1) Live Load
2) Eccentric Load
Page 10 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
q0 (Surcharge Load)
= 12.00 kN/m²
(H1)
2.00
0.40
0.20 (H4)
Page 11 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Fw = (qz x G x Cf) x Af
where, - qz : velocity pressure at height 'Z'
= 0.613 x Kz x Kzt x Kd x V² x I (N/m²)
and, - V : basic wind speed = 42.00 m/sec
- I : important factor = 1.15 (for category III)
- Kd : wind directionality factor
*for solid sign = 0.90
*for Chimneys, Tanks, and Similar Structures
· Round = 0.95
· Square = 0.90
- Kzt : topographic factor
= (1 + K1 x K2 x K3)² = 1.00
- Kz : velocity pressure exposure coefficient (See 'ASCE 7-05 Table 6-3')
· The exposure category : D
- G : gust effect factor = 0.85
- Cf : force coefficient
*ASCE7-05 Figure 6-20 : Force coefficient, Cf (for Solid freestanding walls)
Clearance Aspect Ratio
Ratio ≤ 0.05 0.1 0.2 0.5 1.0 2.0 4.0 5.0 10.0 20.0 30.0 45.0 ≥
1.00 1.80 1.70 1.65 1.55 1.45 1.40 1.35 1.35 1.30 1.30 1.30 1.30
*ASCE7-05 Figure 6-21 : Force coefficient, Cf
(for Chimney, Tanks, Rooftop equipment & Similar Str.)
h/D 1 7 25 Cross Section & Type of Surface
0.7 0.8 0.9 Round Rough (D'/D=0.02)
Cf
1.3 1.4 2.0 Square (wind normal to face)
where, h : height of equipment
D : diameter of equipment
- Af : surface area
- X-Direction
*Aspect Ratio = 1.00 / 8.55 = 0.12 , ∴ Cf = 1.69
( h : height of wall = 8.55 m , w : width of wall = 1.00 m )
H ΔH qz Cf Af Hw Arm Mw
(m) (m) (kN/m²) (m²) (kN) (m) (kN·m)
0.00 ~ 4.60 4.60 1.15 1.69 4.60 7.62 2.30 17.54
4.60 ~ 6.10 1.50 1.21 1.69 1.50 2.61 5.35 13.95
6.10 ~ 7.60 1.50 1.25 1.69 1.50 2.70 6.85 18.52
7.60 ~ 8.55 0.95 1.30 1.69 0.95 1.77 8.08 14.32
Page 12 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Y-Direction
*Aspect Ratio = 12.65 / 8.55 = 1.48 , ∴ Cf = 1.43
( h : height of wall = 8.55 m , w : width of wall = 12.65 m )
H ΔH qz Cf Af Hw Arm Mw
(m) (m) (kN/m²) (m²) (kN) (m) (kN·m)
0.00 ~ 4.60 4.60 1.15 1.43 58.19 81.31 2.30 187.01
4.60 ~ 6.10 1.50 1.21 1.43 18.98 27.80 5.35 148.73
6.10 ~ 7.60 1.50 1.25 1.43 18.98 28.83 6.85 197.49
7.60 ~ 8.55 0.95 1.30 1.43 12.02 18.91 8.08 152.71
- X-Direction
*Aspect Ratio = 23.70 / 11.80 = 2.01 , ∴ Cf = 1.40
( h : height of wall = 11.80 m , w : width of wall = 23.70 m )
H ΔH qz Cf Af Hw Arm Mw
(m) (m) (kN/m²) (m²) (kN) (m) (kN·m)
0.00 ~ 4.60 4.60 1.15 1.40 4.60 6.31 2.30 14.51
4.60 ~ 6.10 1.50 1.21 1.40 1.50 2.16 5.35 11.54
6.10 ~ 7.60 1.50 1.25 1.40 1.50 2.24 6.85 15.32
7.60 ~ 9.10 1.50 1.30 1.40 1.50 2.32 8.35 19.35
9.10 ~ 11.80 2.70 1.37 1.40 2.70 4.39 10.45 45.84
Page 13 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- X-Direction
*h / D = 6.71 / 11.75 = 0.57 , ∴ Cf = 0.69
( h : height of equipment = 6.71 m , D : width of equipment = 11.75 m )
H ΔH qz Cf Af Hw Arm Mw
(m) (m) (kN/m²) (m²) (kN) (m) (kN·m)
0.00 ~ 4.60 4.60 1.15 0.69 4.60 3.12 2.30 7.18
4.60 ~ 6.10 1.50 1.21 0.69 1.50 1.07 5.35 5.71
6.10 ~ 6.71 0.61 1.25 0.69 0.61 0.45 6.41 2.88
- Y-Direction
*h / D = 6.71 / 6.70 = 1.00 , ∴ Cf = 0.70
( h : height of equipment = 6.71 m , D : width of equipment = 6.70 m )
H ΔH qz Cf Af Hw Arm Mw
(m) (m) (kN/m²) (m²) (kN) (m) (kN·m)
0.00 ~ 4.60 4.60 1.15 0.70 4.60 3.16 2.30 7.26
4.60 ~ 6.10 1.50 1.21 0.70 1.50 1.08 5.35 5.77
6.10 ~ 6.71 0.61 1.25 0.70 0.61 0.45 6.41 2.91
Page 14 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- X-Direction
*h / D = 6.99 / 9.46 = 0.74 , ∴ Cf = 0.70
( h : height of equipment = 6.99 m , D : width of equipment = 9.46 m )
H ΔH qz Cf Af Hw Arm Mw
(m) (m) (kN/m²) (m²) (kN) (m) (kN·m)
0.00 ~ 4.60 4.60 1.15 0.70 4.60 3.14 2.30 7.21
4.60 ~ 6.10 1.50 1.21 0.70 1.50 1.07 5.35 5.74
6.10 ~ 6.99 0.89 1.25 0.70 0.89 0.66 6.55 4.32
- Y-Direction
*h / D = 6.99 / 6.80 = 1.03 , ∴ Cf = 0.70
( h : height of equipment = 6.99 m , D : width of equipment = 6.80 m )
H ΔH qz Cf Af Hw Arm Mw
(m) (m) (kN/m²) (m²) (kN) (m) (kN·m)
0.00 ~ 4.60 4.60 1.15 0.70 4.60 3.16 2.30 7.26
4.60 ~ 6.10 1.50 1.21 0.70 1.50 1.08 5.35 5.78
6.10 ~ 6.99 0.89 1.25 0.70 0.89 0.66 6.55 4.35
Page 15 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- X-Direction
*h / D = 10.26 / 14.40 = 0.71 , ∴ Cf = 0.70
( h : height of equipment = 10.26 m , D : width of equipment = 14.40 m )
H ΔH qz Cf Af Hw Arm Mw
(m) (m) (kN/m²) (m²) (kN) (m) (kN·m)
0.00 ~ 4.60 4.60 1.15 0.70 4.60 3.13 2.30 7.21
4.60 ~ 6.10 1.50 1.21 0.70 1.50 1.07 5.35 5.73
6.10 ~ 7.60 1.50 1.25 0.70 1.50 1.11 6.85 7.61
7.60 ~ 9.10 1.50 1.30 0.70 1.50 1.15 8.35 9.61
9.10 ~ 10.26 1.16 1.37 0.70 1.16 0.94 9.68 9.06
- Y-Direction
*h / D = 10.26 / 10.20 = 1.01 , ∴ Cf = 0.70
( h : height of equipment = 10.26 m , D : width of equipment = 10.20 m )
H ΔH qz Cf Af Hw Arm Mw
(m) (m) (kN/m²) (m²) (kN) (m) (kN·m)
0.00 ~ 4.60 4.60 1.15 0.70 4.60 3.16 2.30 7.26
4.60 ~ 6.10 1.50 1.21 0.70 1.50 1.08 5.35 5.77
6.10 ~ 7.60 1.50 1.25 0.70 1.50 1.12 6.85 7.66
7.60 ~ 9.10 1.50 1.30 0.70 1.50 1.16 8.35 9.68
9.10 ~ 10.26 1.16 1.37 0.70 1.16 0.94 9.68 9.12
6) Load Summary
X-direction Y-direction
Load
Fx Mpy Mfy Fy Mpx Mfx
Case
(kN) (kN.m) (kN.m) (kN) (kN.m) (kN.m)
Fire Wall 1 14.71 - 89.32 156.85 - -952.58
Fire Wall 2 17.41 - 136.15 - - -
CAT ( P1 ) 4.64 21.81 23.67 4.69 -22.04 -23.91
UAT ( P2 ) 4.87 23.59 25.54 4.90 -23.76 -25.72
GUT ( P3 ) 7.40 54.02 57.36 7.45 -54.40 -57.76
∑ 49.03 99.43 332.04 173.89 -100.20 -1059.96
Page 16 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 17 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 18 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
4) Load Summary
X-direction Y-direction
Load
Fx Mpy Mfy Fy Mpx Mfx
Case
(kN) (kN.m) (kN.m) (kN) (kN.m) (kN.m)
CAT ( P1 ) 383.34 2213.15 2366.49 383.34 -2213.15 -2366.49
UAT ( P2 ) 460.01 2741.65 2925.65 460.01 -2741.65 -2925.65
GUT ( P3 ) 1521.75 13452.23 14137.02 1521.75 -13452.23 -14137.02
∑ 2365.09 18407.04 19429.16 2365.09 -18407.04 -19429.16
Page 19 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
4. LOAD COMBINATION
※ Legend
- DL : Dead Load
- EL : Equipment Load
- LL : Live Load
- WLX : Wind Load in X-direction
- WLY : Wind Load in Y-direction
- SLX : Seismic Load in X-direction
- SLY : Seismic Load in Y-direction
- H : Earth Pressure Laod
Load
Load Factor Remark
Comb.
L/C-1 1.00 DL + 1.00 EL + 1.00 LL + 1.00 H Normal Operation
L/C-2 1.00 DL + 1.00 EL + 1.00 WLX + 1.00 H Empty with Wind X-direction
L/C-3 1.00 DL + 1.00 EL - 1.00 WLX + 1.00 H Empty with Wind -X-direction
L/C-4 1.00 DL + 1.00 EL + 1.00 WLY + 1.00 H Empty with Wind Y-direction
L/C-5 1.00 DL + 1.00 EL - 1.00 WLY + 1.00 H Empty with Wind -Y-direction
L/C-6 1.00 DL + 1.00 EL + 0.70 SLX + 1.00 H Empty with Seismic X-direction
L/C-7 1.00 DL + 1.00 EL - 0.70 SLX + 1.00 H Empty with Seismic -X-direction
L/C-8 1.00 DL + 1.00 EL + 0.70 SLY + 1.00 H Empty with Seismic Y-direction
L/C-9 1.00 DL + 1.00 EL - 0.70 SLY + 1.00 H Empty with Seismic -Y-direction
L/C-10 1.00 DL + 1.00 EL + 0.75 LL + 0.75 WLX + 1.00 H Operation with Wind X-direction
L/C-11 1.00 DL + 1.00 EL + 0.75 LL - 0.75 WLX + 1.00 H Operation with Wind -X-direction
L/C-12 1.00 DL + 1.00 EL + 0.75 LL + 0.75 WLY + 1.00 H Operation with Wind Y-direction
L/C-13 1.00 DL + 1.00 EL + 0.75 LL - 0.75 WLY + 1.00 H Operation with Wind -Y-direction
L/C-14 1.00 DL + 1.00 EL + 0.75 LL + 0.53 SLX + 1.00 H Operation with Seismic X-direction
L/C-15 1.00 DL + 1.00 EL + 0.75 LL - 0.53 SLX + 1.00 H Operation with Seismic -X-direction
L/C-16 1.00 DL + 1.00 EL + 0.75 LL + 0.53 SLY + 1.00 H Operation with Seismic Y-direction
L/C-17 1.00 DL + 1.00 EL + 0.75 LL - 0.53 SLY + 1.00 H Operation with Seismic -Y-direction
Page 20 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Load
Load Factor Remark
Comb.
L/C-U1 1.20 DL + 1.20 EL + 1.60 LL + 1.60 H Normal Operation
L/C-U2 0.90 DL + 0.90 EL + 1.60 WLX + 1.60 H Empty with Wind X-direction
L/C-U3 0.90 DL + 0.90 EL - 1.60 WLX + 1.60 H Empty with Wind -X-direction
L/C-U4 0.90 DL + 0.90 EL + 1.60 WLY + 1.60 H Empty with Wind Y-direction
L/C-U5 0.90 DL + 0.90 EL - 1.60 WLY + 1.60 H Empty with Wind -Y-direction
L/C-U6 0.90 DL + 0.90 EL + 1.00 SLX + 1.60 H Empty with Seismic X-direction
L/C-U7 0.90 DL + 0.90 EL - 1.00 SLX + 1.60 H Empty with Seismic -X-direction
L/C-U8 0.90 DL + 0.90 EL + 1.00 SLY + 1.60 H Empty with Seismic Y-direction
L/C-U9 0.90 DL + 0.90 EL - 1.00 SLY + 1.60 H Empty with Seismic -Y-direction
L/C-U10 1.20 DL + 1.20 EL + 1.00 LL + 1.60 WLX + 1.60 H Operation with Wind X-direction
L/C-U11 1.20 DL + 1.20 EL + 1.00 LL - 1.60 WLX + 1.60 H Operation with Wind -X-direction
L/C-U12 1.20 DL + 1.20 EL + 1.00 LL + 1.60 WLY + 1.60 H Operation with Wind Y-direction
L/C-U13 1.20 DL + 1.20 EL + 1.00 LL - 1.60 WLY + 1.60 H Operation with Wind -Y-direction
L/C-U14 1.20 DL + 1.20 EL + 1.00 LL + 1.00 SLX + 1.60 H Operation with Seismic X-direction
L/C-U15 1.20 DL + 1.20 EL + 1.00 LL - 1.00 SLX + 1.60 H Operation with Seismic -X-direction
L/C-U16 1.20 DL + 1.20 EL + 1.00 LL + 1.00 SLY + 1.60 H Operation with Seismic Y-direction
L/C-U17 1.20 DL + 1.20 EL + 1.00 LL - 1.00 SLY + 1.60 H Operation with Seismic -Y-direction
L/C-U18 1.40 DL + 1.40 EL + 1.60 H Test Only
5. STABILITY CHECK
Page 21 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 22 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Qa = 150.00 kN/m²
- A = 727.27 m²
- Zx = 1958.38 m³
- Zy = 4375.37 m³
Page 23 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 24 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 25 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
6. STRUCTURE ANALYSIS
2) Property of Section
Thickness
Section Element Material Remark
(m)
Dike 1 Shell 0.25 Concrete
Dike 2 Shell 0.45 Concrete
Fire Wall 1 Shell 0.25 Concrete
Fire Wall 2 Shell 0.30 Concrete
Bottom Slab 1 Shell 0.40 Concrete
Bottom Slab 2 Shell 0.45 Concrete
Page 26 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
1) Dead Load, D
- Bottom Slab & Dike & Fire Wall weight is inputted by program selfweight function automatically.
*Wd = Hp x γc + E / Ap
Wd1 = 1.30 x 25.00 + 1617.00 / 16.20 = 132.31 kN/m²
Wd2 = 1.30 x 25.00 + 1940.40 / 18.56 = 137.05 kN/m²
Wd4 = 1.30 x 25.00 = 32.50 kN/m² (Apply to P4 Area)
Wd5 = 1.30 x 25.00 = 32.50 kN/m² (Apply to P5 Area)
*Wd = Hp x γc
Wd3 = 2.00 x 25.00 = 50.00 kN/m²
*Wd = E / Lp
Wd3 = 6105.40 / 56.08 = 108.87 kN/m
Wd3 = 313.60 / 17.10 = 18.34 kN/m
*SAP Modeling Input Loading
Page 27 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
2) Live Load, L
Z
L1 L1+L2 L2+L3 L3
Page 28 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
(1) Surcharge Load, (Ps0) (2) Not considering ground water, (Ps1)
4) Wind Load, W
- for X-direction
·Pf = ∑Hw / ∑Af = 14.71 / 8.55 = 1.72 kN/m²
- for Y-direction
·Pf = ∑Hw / ∑Af = 156.85 / 108.16 = 1.45 kN/m²
X Y
kN/m²
kN/m²
Fire Wall 1
Fire Wall 1
Z Z
1.45
1.72
- for X-direction
·Pf = ∑Hw / ∑Af = 17.41 / 11.80 = 1.48 kN/m²
X
kN/m²
Fire Wall 2
Z
1.48
Page 29 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- for X-direction
- for Y-direction
- for X-direction
- for Y-direction
- for X-direction
- for Y-direction
Page 30 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- for X-direction
- for Y-direction
- for X-direction
- for Y-direction
- for X-direction
- for Y-direction
Page 31 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
7. MEMBER DESIGN
1) Dike 1
Page 32 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 33 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 34 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
2) Dike 2
Page 35 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 36 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 37 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
3) Fire Wall 1
Page 38 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 39 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 40 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
4) Fire Wall 2
Page 41 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Critcal Area
Critcal Area
*Normal Area
Max. Bending Moment
Section / Case Remark
M11 (Hori.-Dir.) M22 (Vert.-Dir.)
Positive Value 85.00 kN 140.00 kN
Fire Wall 2
Negative Value 76.00 kN 130.00 kN
* Critical Area
Max. Bending Moment
Section / Case Remark
M11 (Hori.-Dir.) M22 (Vert.-Dir.)
Positive Value 112.00 kN 210.00 kN
Fire Wall 2
Negative Value 127.00 kN 230.00 kN
Page 42 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
*Normal Area
Max. Bending Moment
Section / Case Remark
M11 (Hori.-Dir.) M22 (Vert.-Dir.)
Positive Value 50.00 kN 85.00 kN
Fire Wall 2
Negative Value 44.00 kN 85.00 kN
* Critical Area
Max. Bending Moment
Section / Case Remark
M11 (Hori.-Dir.) M22 (Vert.-Dir.)
Positive Value 85.00 kN 130.00 kN
Fire Wall 2
Negative Value 50.00 kN 120.00 kN
Page 43 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
5) Bottom Slab 1
Page 44 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 45 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 46 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
6) Bottom Slab 2
Page 47 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 48 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 49 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
7) P3
Page 50 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 51 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 52 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 53 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
80.00 56.00 78.00 37.5 420 0.75 0.90 250 1000 175 75
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 80.00 x 10 6
Required Rn = = = 2.90 MPa
Φb x b x d 2
0.90 x 1000 x 175 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 2.90
= x 1 - 1 - = 0.0073
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0073 x 1000 x 175 = 1271 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 250 / 2 = 225 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 175 = 583 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 175 = 638 mm²
4/3 As(req.) = 4 / 3 x 1271 = 1695 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 1271 mm²
Page 54 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Crack Check
fs = Mo / ( As x j x d )
= 56.00 x 10 6 / ( 2094.67 x 0.889 x 175 ) = 171.85 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 24.92 x ( 3.35 x 39.53 ) x 10 = 0.012 in.
= 0.29 mm
Page 55 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
130.00 85.00 78.00 37.5 420 0.75 0.90 250 1000 175 75
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 130.00 x 10 6
Required Rn = = = 4.72 MPa
Φb x b x d 2 0.90 x 1000 x 175 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 4.72
= x 1 - 1 - = 0.0122
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0122 x 1000 x 175 = 2138 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 250 / 2 = 225 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 175 = 583 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 175 = 638 mm²
4/3 As(req.) = 4 / 3 x 2138 = 2851 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 2138 mm²
Page 56 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Crack Check
fs = Mo / ( As x j x d )
= 85.00 x 10 6 / ( 3272.67 x 0.8679 x 175 ) = 171.00 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 24.80 x ( 3.44 x 40.69 ) x 10 = 0.012 in.
= 0.30 mm
Page 57 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
150.00 100.00 119.00 37.5 420 0.75 0.90 450 1000 375 75
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 150.00 x 10 6
Required Rn = = = 1.19 MPa
Φb x b x d 2 0.90 x 1000 x 375 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 1.19
= x 1 - 1 - = 0.0029
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0029 x 1000 x 375 = 1079 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 450 / 2 = 405 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 375 = 1250 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 375 = 1367 mm²
4/3 As(req.) = 4 / 3 x 1079 = 1439 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 1367 mm²
Page 58 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Crack Check
fs = Mo / ( As x j x d )
= 100.00 x 10 6 / ( 2094.67 x 0.9192 x 375 ) = 138.50 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 20.09 x ( 3.35 x 39.53 ) x 10 = 0.009 in.
= 0.24 mm
Page 59 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
220.00 150.00 119.00 37.5 420 0.75 0.90 450 1000 375 75
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 220.00 x 10 6
Required Rn = = = 1.74 MPa
Φb x b x d 2
0.90 x 1000 x 375 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 1.74
= x 1 - 1 - = 0.0043
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0043 x 1000 x 375 = 1597 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 450 / 2 = 405 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 375 = 1250 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 375 = 1367 mm²
4/3 As(req.) = 4 / 3 x 1597 = 2129 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 1597 mm²
Page 60 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Crack Check
fs = Mo / ( As x j x d )
= 150.00 x 10 6 / ( 3272.67 x 0.9024 x 375 ) = 135.45 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 19.64 x ( 3.44 x 40.69 ) x 10 = 0.009 in.
= 0.24 mm
Page 61 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
69.00 52.00 39.00 37.5 420 0.75 0.90 300 1000 240 60
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 69.00 x 10 6
Required Rn = = = 1.33 MPa
Φb x b x d 2 0.90 x 1000 x 240 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 1.33
= x 1 - 1 - = 0.0032
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0032 x 1000 x 240 = 778 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 300 / 2 = 270 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 240 = 800 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 240 = 875 mm²
4/3 As(req.) = 4 / 3 x 778 = 1037 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 875 mm²
Page 62 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Crack Check
fs = Mo / ( As x j x d )
= 52.00 x 10 6 / ( 1340.67 x 0.9192 x 240 ) = 175.82 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 25.50 x ( 2.68 x 31.62 ) x 10 = 0.010 in.
= 0.26 mm
Page 63 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
83.00 52.00 39.00 37.5 420 0.75 0.90 300 1000 240 60
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 83.00 x 10 6
Required Rn = = = 1.60 MPa
Φb x b x d 2
0.90 x 1000 x 240 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 1.60
= x 1 - 1 - = 0.0039
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0039 x 1000 x 240 = 940 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 300 / 2 = 270 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 240 = 800 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 240 = 875 mm²
4/3 As(req.) = 4 / 3 x 940 = 1253 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 940 mm²
Page 64 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Crack Check
fs = Mo / ( As x j x d )
= 52.00 x 10 6 / ( 1340.67 x 0.9192 x 240 ) = 175.82 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 25.50 x ( 2.68 x 31.62 ) x 10 = 0.010 in.
= 0.26 mm
Page 65 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
85.00 50.00 119.00 37.5 420 0.75 0.90 300 1000 240 60
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 85.00 x 10 6
Required Rn = = = 1.64 MPa
Φb x b x d 2 0.90 x 1000 x 240 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 1.64
= x 1 - 1 - = 0.0040
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0040 x 1000 x 240 = 963 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 300 / 2 = 270 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 240 = 800 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 240 = 875 mm²
4/3 As(req.) = 4 / 3 x 963 = 1284 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 963 mm²
Page 66 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
fs = Mo / ( As x j x d )
= 50.00 x 10 6 / ( 1340.67 x 0.9192 x 240 ) = 169.06 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 24.52 x ( 2.68 x 31.62 ) x 10 = 0.010 in.
= 0.25 mm
Page 67 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
140.00 85.00 119.00 37.5 420 0.75 0.90 300 1000 240 60
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 140.00 x 10 6
Required Rn = = = 2.70 Mpa
Φb x b x d 2 0.90 x 1000 x 240 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 2.70
= x 1 - 1 - = 0.0067
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0067 x 1000 x 240 = 1615 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 300 / 2 = 270 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 240 = 800 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 240 = 875 mm²
4/3 As(req.) = 4 / 3 x 1615 = 2153 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 1615 mm²
Page 68 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Crack Check
fs = Mo / ( As x j x d )
= 85.00 x 10 6 / ( 2094.67 x 0.9024 x 240 ) = 187.37 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 27.18 x ( 2.76 x 32.55 ) x 10 = 0.011 in.
= 0.28 mm
Page 69 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
127.00 85.00 119.00 37.5 420 0.75 0.90 300 1000 240 60
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 127.00 x 10 6
Required Rn = = = 2.45 MPa
Φb x b x d 2 0.90 x 1000 x 240 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 2.45
= x 1 - 1 - = 0.0061
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0061 x 1000 x 240 = 1459 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 300 / 2 = 270 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 240 = 800 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 240 = 875 mm²
4/3 As(req.) = 4 / 3 x 1459 = 1945 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 1459 mm²
Page 70 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
fs = Mo / ( As x j x d )
= 85.00 x 10 6 / ( 2094.67 x 0.9024 x 240 ) = 187.37 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 27.18 x ( 2.76 x 32.55 ) x 10 = 0.011 in.
= 0.28 mm
Page 71 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
230.00 130.00 119.00 37.5 420 0.75 0.90 300 1000 240 60
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 230.00 x 10 6
Required Rn = = = 4.44 Mpa
Φb x b x d 2 0.90 x 1000 x 240 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 4.44
= x 1 - 1 - = 0.0114
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0114 x 1000 x 240 = 2742 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 300 / 2 = 270 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 240 = 800 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 240 = 875 mm²
4/3 As(req.) = 4 / 3 x 2742 = 3656 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 2742 mm²
Page 72 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Crack Check
fs = Mo / ( As x j x d )
= 130.00 x 10 6 / ( 3272.67 x 0.8831 x 240 ) = 187.43 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 27.18 x ( 2.85 x 33.71 ) x 10 = 0.011 in.
= 0.29 mm
Page 73 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
89.00 65.00 145.00 37.5 420 0.75 0.90 400 1000 325 75
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 89.00 x 10 6
Required Rn = = = 0.94 MPa
Φb x b x d 2 0.90 x 1000 x 325 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 0.94
= x 1 - 1 - = 0.0023
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0023 x 1000 x 325 = 736 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 400 / 2 = 360 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 325 = 1083 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 325 = 1185 mm²
4/3 As(req.) = 4 / 3 x 736 = 981 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 981 mm²
Page 74 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
fs = Mo / ( As x j x d )
= 65.00 x 10 6 / ( 1340.67 x 0.9292 x 325 ) = 160.55 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 23.29 x ( 3.27 x 38.60 ) x 10 = 0.011 in.
= 0.27 mm
Page 75 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
142.00 105.00 145.00 37.5 420 0.75 0.90 400 1000 325 75
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 142.00 x 10 6
Required Rn = = = 1.49 Mpa
Φb x b x d 2 0.90 x 1000 x 325 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 1.49
= x 1 - 1 - = 0.0036
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0036 x 1000 x 325 = 1185 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 400 / 2 = 360 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 325 = 1083 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 325 = 1185 mm²
4/3 As(req.) = 4 / 3 x 1185 = 1580 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 1185 mm²
Page 76 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Crack Check
fs = Mo / ( As x j x d )
= 105.00 x 10 6 / ( 2094.67 x 0.9141 x 325 ) = 168.74 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 24.47 x ( 3.35 x 39.53 ) x 10 = 0.011 in.
= 0.29 mm
Page 77 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
283.00 177.00 145.00 37.5 420 0.75 0.90 450 1000 375 75
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 283.00 x 10 6
Required Rn = = = 2.24 MPa
Φb x b x d 2 0.90 x 1000 x 375 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 2.24
= x 1 - 1 - = 0.0055
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0055 x 1000 x 375 = 2072 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 450 / 2 = 405 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 375 = 1250 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 375 = 1367 mm²
4/3 As(req.) = 4 / 3 x 2072 = 2763 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 2072 mm²
Page 78 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
fs = Mo / ( As x j x d )
= 177.00 x 10 6 / ( 3272.67 x 0.9024 x 375 ) = 159.83 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 23.18 x ( 3.44 x 40.69 ) x 10 = 0.011 in.
= 0.28 mm
Page 79 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
127.00 79.00 145.00 37.5 420 0.75 0.90 450 1000 375 75
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 127.00 x 10 6
Required Rn = = = 1.00 Mpa
Φb x b x d 2 0.90 x 1000 x 375 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 1.00
= x 1 - 1 - = 0.0024
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0024 x 1000 x 375 = 911 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 450 / 2 = 405 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 375 = 1250 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 375 = 1367 mm²
4/3 As(req.) = 4 / 3 x 911 = 1215 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 1215 mm²
Page 80 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Crack Check
fs = Mo / ( As x j x d )
= 79.00 x 10 6 / ( 1340.67 x 0.9335 x 375 ) = 168.33 MPa
ω = 0.076 x βc x fs x ( dc x A ) 1/3 x 10 -3
1/3 -3
= 0.076 x 1.2 x 24.41 x ( 3.27 x 38.60 ) x 10 = 0.011 in.
= 0.28 mm
Page 81 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
3) P3 : Top Re-bar
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
185.00 142.00 130.00 37.5 420 0.75 0.90 2000 1000 1925 75
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 185.00 x 10 6
Required Rn = = = 0.06 Mpa
Φb x b x d 2 0.90 x 1000 x 1925 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 0.06
= x 1 - 1 - = 0.0001
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0001 x 1000 x 1925 = 255 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 2000 / 2 = 1800 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 1925 = 6417 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 1925 = 7017 mm²
4/3 As(req.) = 4 / 3 x 255 = 340 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 1800 mm²
Page 82 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
4) : Bottom Re-bar
Mu Mo Vu f'c fy φ φ h b d cover
(kN.m) (kN) (kN) (MPa) (MPa) (Shear) (Bending) (mm) (mm) (mm) (mm)
283.00 173.00 130.00 37.5 420 0.75 0.90 2000 1000 1925 75
where, Mu : factored bending moment
Mo : non-factored bending moment
Vu : factored shear force
f'c : compressive strength of concrete
fy : yield strength of reinforcing bar
φ : strength reduction factor
- Rebar Check
Mu 283.00 x 10 6
Required Rn = = = 0.08 Mpa
Φb x b x d 2 0.90 x 1000 x 1925 2
0.85 x fck 2 x Rn
ρ= x 1 - 1 -
fy 0.85 x fck
0.85 x 38 2 x 0.08
= x 1 - 1 - = 0.0002
420 0.85 x 38
As(req.) = ρ x b x d
= 0.0002 x 1000 x 1925 = 390 mm²
As(temp.) = 0.0018 x b x h / 2
= 0.0018 x 1000 x 2000 / 2 = 1800 mm²
As(min.1) = 1.4 / fy x b x d
= 1.4 / 420 x 1000 x 1925 = 6417 mm²
As(min.2) = 0.25 x √fck / fy x b x d
= 0.25 x √ 38 / 420 x 1000 x 1925 = 7017 mm²
4/3 As(req.) = 4 / 3 x 390 = 520 mm²
Selected As = Max[As(req.) , As(temp.) , Min{4/3As(req.) , Max(As(min.1) , As(min.2))}] = 1800 mm²
Page 83 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 84 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Member Check
ㆍTotal As = - x 86 ea = 0 mm
Page 85 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 86 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Member Check
Page 87 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 88 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
- Member Check
Page 89 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
8. REBAR SKETCH
D16 @ 150
D25 @ 150 ( Fire Wall 1: Horizontal)
( Dike 1: Vertical)
Dike 1
Dike 1
P1 P2
D20 @ 150
D20 @ 150 ( Bottom Slab 1: Bottom)
( Dike 1: Horizontal)
D16 @ 150
( Bottom Slab 1: Top)
Page 90 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
D20 @ 150
( Fire Wall 2: Vertical)
(Normal Area)
8.60
(Normal Area) D25 @ 150
( Fire Wall 2: Vertical)
(Critical Area)
(Critical Area)
Fire Wall 2
3.00
D20 @ 150
( Dike 2: Horizontal) D25 @ 200
( P3: Top)
P3
Dike 2
Dike 2
Dike 2
2.00
Bottom Slab 2
Page 91 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
P1 P2
One Side : 74 ea - D 16
Total : 212 ea - D 16
P3
Page 92 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 93 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 94 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 95 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 96 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 97 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
-Each transformer dike size has been designed with following volume check.
Page 98 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0
Page 99 of 101
Doc No : 00-UBF-C-51-001-001
TR COMPOUND FOUNDATION Rev No : X0