DRP SPAM RELAY SETTING

DRP-1
New Silo Roots Roots Combustion
RMHS-II RMHS 2 Rotary WT
BC-3 BC-2A bag filter ID blower blower Air Fan
DES-2 IMPACTOR Cooler MAIN
fan 192 178 306
Motor Name 228.10 DRIVE
Motor Kw 125 kw 110 kw 110 kw 132 kw 132 kw 110 kw 110 kw 132 Kw 56 kw 75 kW
Motor FLC 240A 180A 180 A 240 A 226 A 180A 180A 212.5 A 92 A 135A
SR NOPARAMETER PARAMETER DESCRIPTION
1 IøIn Motor full load current (FLC/CT R) 0.53 0.72 0.5 0.54 0.75 0.6 0.6 0.85 0.59 0.54
2 t6xs Safe stall Time (Sec) 11 9 9 10 10 7 7 10 10 10
3 P% weighting factor for thermal unit curves (%) 20.00% 70.00% 70 70 50 70 70.00% 70.00% 90.00% 50
4 øa% Prior alarm level 50.00% 80 80 95 95 80 80 70 70 95
5 øi Thermal inhibit level 40 50 50 50 40 50 50 80 80 40
6 Kc Cooling time multiplier 40 40 1 1 1 1 1 1 1 1
7 Is/In startup supervision 5 5 5 5 4 5 5 6.5 6.5 4
8 ts(s) Start up time 12.8 12 6 5 10 8 5 12 12 10
9 I>>/In High set overcurrent 1.5 1 1.6 10.8 4 10.8 10.8 8.5 8.5 4
10 t>>(s) Time setting stage operate time in seconds 12.8 10 1 1 0.4 1 1 1 1 0.4
11 Io(%In) Earth fault protection 8 8 6 8 1 8 8 15 15 1
12 to(s) Operate time of E/F unit 1 1 0.5 1 0.05 1 1 1 1 0.05
13 ∆I(%IL) Unbalance protection in % of highest phase cur 20 40 15 20 10 20 20 30 40 10
14 t∆(s) Operate time at the starting level 20 20 40 40 20 40 40 20 20 20
15 I<(%Iø) Starting value of the undercurrent unit in % of ----- ----- ------ --- ------ ------ ---- ------ ---
16 t<(s) Operate time of the undercurrent unit 2 2 2 2 2 2 2 2 2 2
17 ∑tsi(s) Time based start inhibit counter setting 15 15 15 15 5 15 15 15 15 5
18 ∆∑ts(s/n) Countdown rate of the start time counter in sec/ 2 2 20 2 2 20 20 2 2 2
19 SGF The checksum of the selector switchgrop SGF 127 115 127 115 21 127 127 115 115 21
20 SGB The checksum of the selector switchgrop SGB 4 4 0 128 0 0 0 128 128 0
21 SGR-1 The checksum of the selector switchgrop SGR1 128 129 129 129 129 129 129 129 129 129
22 SGR-2 The checksum of the selector switchgrop SGR2 250 250 250 250 250 250 250 250 250 250
23 CT RATIO =300/5 400 / 5 250 / 5 400/1 400 / 5 300/5 300 / 5 300 / 5 250 / 5 150/5 250/1
24 Motor full load current = Relay setting X Relay rated current X CT Ratio

Iø Full load (rated) currrent ( setting from 0.5 to 1.5 x In)


In Nominal current = Max current of CT
Is Startup current
I running current
Io Neutral current
Cold well Cold well
BC-2B
pump-1 pump-2

55 kw 75kw 75kw
110A 132A 132A

0.73
9
70.00%
80
50
40
5
12
1
10
8
1
40
20
-----
2
15
2
115
4
129
250
150/5
MCC I Breaker Relay
SR NO PARAMETER DESCRIPTION VALUE
1 I> / In Starting current range WRT CT pri.current 0.60
2 t> / [S] Tripping timing for I>/In 0.15
3 I>> / In Starting curren at multiple range WRT CT pri.current 1.50
4 t>> / [S] Tripping timing for I>> / In 0.05
5 Io > In Earth current 0.10
6 to> [S] Tripping timing for I0 / In 0.05
7 Io>> / In Earth current 0.20
8 to >> [S] Tripping timing for I0 >> / In 0.15
9 SGF Group of switch 114
10 SGB Group of switch 225
11 SGR Group of switch 171
12 C T retio 3000 / 5