Annexure-1

General

1. Please submit the bill of materials for the submitted structural drawings.
Reply: - Attached herewith.
WAPCOS REPLY:-
a) One addition member SA 11A included in middle cross of submitted BoM. May please
correct the same.
b) The number of pieces for member number SA 29 is 2 which is supposed to be 1. May
please correct the same in BoM.
c) The length of member number SA 40L in BoM is not matching with submitted drawing.
d) The length of plate number SA 46 in BoM is not matching with submitted drawing.
e) Please change the name of member SA 50A to SA 50X in BoM with respect to drawing.
f) The quantity for member number SA 225,226,227 & 228 in BoM should be 4 each as per
members considered in projected area calculation in both faces of approved SA tower
design.
g) Member name SA 241 with size 97x8x282 should be changed to SA 244 in BoM.
h) The length of member number SA 250 in BoM is not matching with submitted drawing.
i) The length & number of member for member number SA 214,221 & 295 in BoM is not
matching with approved design of SA tower.
j) The length & number of member for member number SA 304 in BoM is not matching with
approved design of SA tower.
k) The number of pieces for member number SA 353H is 4 which is supposed to be 8. May
please correct the same in BoM.
l) Please change the name of member SA 400SH & 400H with length 2731 to SA 400SHX &
400HX in BoM with respect to drawing.
m) One summary sheet for BoM with details of normal tower weight along with extensions
(with separate column of tower member weight & nut bolt weight) to be submitted along
with BoM. 

2. Please give the zoom view of butt and gusset joints with sectional view.
Reply: - The same can be detailed in our shop drawing but for easy understanding we have given
the spliced zoom view.
WAPCOS Reply:- No zoom view of all gusset plates shown. May please display the same.

3. Number plate & Bird guard arrangement should be provided as per clause3.18.4 of technical
specification.
Reply: - Modified and attached herewith.
Page 1 of 3
Annexure-1

WAPCOS Reply:- No bird guard arrangement shown.

4. With reference to clause 3.5.2.1(iii) of TS, no individual member should be longer than 6000mm.
But some leg members are more than 6000mm. Please clarify the same.
Reply: - Modified and attached herewith.
WAPCOS Reply:- Noted

5. Please indicate the distance of tower accessories from ground level & it should be complying with
clause 6.7.7 of IS 5613 part 2 sec 1.
Reply: - Modified and attached herewith.
WAPCOS Reply:- Noted

6. Distance of holes for circuit plate & danger plate should be in accordance with IS 5613 part 2 sec
1.
Reply: - Modified and attached herewith.
WAPCOS Reply:- Noted

7. Please indicate distance of step bolt from ground level & it should be complying with clause
3.5.2.1 (vi) of TS.
Reply: - Modified and attached herewith.
WAPCOS Reply:- Noted

8. Please mention the cut edge & rolled edge distance of holes in lap joint & butt joints.
Reply: - Modified and attached herewith.
WAPCOS Reply:- Noted

9. Indicate back to back distance at every cross arm level.


Reply: - Dimension shown for each cross arm in elevation view.
WAPCOS Reply:-
a) Show back to back distance for middle cross arm in cage drawing.
b) Please recheck the back to back distance for body II top with design document.
10. Please give the zoom view of suspension arrangement of cross arm. Indicate the hole size for
suspension arrangement.
Reply: - Modified and attached herewith.
WAPCOS Reply:- Noted

Page 2 of 3
Annexure-1

11. Please display slope diagram in other section of drawings as indicated in cross arm diagram.
Photo attached for reference.
Reply: - Cross arm slope calculation is different from the tower slope calculation therefore it is
shown in separate diagram but for the rest of the tower the slope can be checked from the values
given Tower Slope table.

WAPCOS Reply:- Noted.

12. Please correct the description box of page no 6 from top, middle, bottom cross arm to mid body
to +0m level.
Reply: - Modified and attached herewith.
WAPCOS Reply:-Noted

13. Please correct the description box of page no 7 from 9m body extension to 3m body extension.
Reply: - Modified and attached herewith.
WAPCOS Reply:-Noted
14. The number of double shear bolt for butt joint in top & middle cross arm is not matching with
approved design document.