You are on page 1of 8

07/12/2021 531778786.

xlsx Cond Unit MT - Fix CAP+Stepless

Declared cooling capacity at full load DC = declared cooling capacity at temperatures A, B, C and D DC at rating points B, C and D shall n
7.00 of the cooling demand (PR) -- CR < 1
i.e. Point A (DC, in kW)

Degradation Calculation
DC in kW COP at this DC Degradation Capacity Ratio
Cooling demand (PR) (measured or (measured or coefficient Cd CR COP at Part Load COP(PL)
COP (=DC(full load)*Partload) calculated) calculated) (=PR/DC) (=COP@full cap)*(1-Cd*(1-CR))
COP A 2.10 7.00 7.00 2.10 0.25 1.00 2.10
COP B 2.57 6.27 7.76 2.57 0.25 0.81 2.45
COP C 3.27 5.24 8.74 3.27 0.25 0.60 2.94
COP D 4.00 4.20 9.61 4.00 0.25 0.44 3.44
Please consider: Selection of COPA, COPB, COPC, COPD depends on Ratio between refrigerant demand and declared capacity
different ambient temp conditions, load profile and application (CR=1, in case of a continuous capacity adjustment)
temperature (MT, LT)

j Tj (°C) hj partload% refrigeration demand COPPL Ph*Tj PH*Tj/COPDC

1 -19 0.08 60% 4.20 3.44 0 0


2 -18 0.41 60% 4.20 3.44 2 0
3 -17 0.65 60% 4.20 3.44 3 1
4 -16 1.05 60% 4.20 3.44 4 1
5 -15 1.74 60% 4.20 3.44 7 2
6 -14 2.98 60% 4.20 3.44 13 4
7 -13 3.79 60% 4.20 3.44 16 5
8 -12 5.69 60% 4.20 3.44 24 7
9 -11 8.94 60% 4.20 3.44 38 11
10 -10 11.81 60% 4.20 3.44 50 14
11 -9 17.29 60% 4.20 3.44 73 21
12 -8 20.02 60% 4.20 3.44 84 24
13 -7 28.73 60% 4.20 3.44 121 35
14 -6 39.71 60% 4.20 3.44 167 49
15 -5 56.61 60% 4.20 3.44 238 69
16 -4 76.36 60% 4.20 3.44 321 93
17 -3 106.07 60% 4.20 3.44 445 130
18 -2 153.22 60% 4.20 3.44 644 187
19 -1 203.41 60% 4.20 3.44 854 249
20 0 247.98 60% 4.20 3.44 1,041 303
21 1 282.01 60% 4.20 3.44 1,184 345
22 2 275.91 60% 4.20 3.44 1,159 337
23 3 300.61 60% 4.20 3.44 1,263 367
24 4 310.77 60% 4.20 3.44 1,305 380
D 25 5 336.48 60% 4.20 3.44 1,413 411
26 6 350.48 61% 4.30 3.39 1,508 445
27 7 363.49 63% 4.41 3.34 1,602 480
28 8 368.91 64% 4.51 3.29 1,664 506
29 9 371.63 66% 4.61 3.24 1,715 529
30 10 377.32 67% 4.72 3.19 1,780 558
31 11 376.53 69% 4.82 3.14 1,816 578
32 12 386.42 70% 4.93 3.09 1,903 616
33 13 389.84 72% 5.03 3.04 1,961 645
34 14 384.45 73% 5.13 2.99 1,973 660
C 35 15 370.45 75% 5.24 2.94 1,940 659
36 16 344.96 76% 5.34 2.89 1,842 637
37 17 328.02 78% 5.44 2.84 1,786 628
38 18 305.36 79% 5.55 2.79 1,694 606
39 19 261.87 81% 5.65 2.74 1,480 539
40 20 223.90 82% 5.76 2.69 1,289 478
41 21 196.31 84% 5.86 2.65 1,150 435
42 22 163.04 85% 5.96 2.60 972 375
43 23 141.78 87% 6.07 2.55 860 338
44 24 121.93 88% 6.17 2.50 752 301
B 45 25 104.46 90% 6.27 2.45 655 268
46 26 85.77 91% 6.38 2.40 547 228
47 27 71.54 93% 6.48 2.35 464 197
48 28 56.57 94% 6.59 2.30 373 162
49 29 43.35 96% 6.69 2.25 290 129
50 30 31.02 97% 6.79 2.20 211 96
51 31 20.21 99% 6.90 2.15 139 65
A 52 32 11.85 100% 7.00 2.10 83 40
53 33 8.17 100% 7.00 2.10 57 27
54 34 3.83 100% 7.00 2.10 27 13
55 35 2.09 100% 7.00 2.10 15 7
56 36 1.21 100% 7.00 2.10 8 4
57 37 0.52 100% 7.00 2.10 4 2
58 38 0.40 100% 7.00 2.10 3 1
total 43,032 14,299

SEPR 3.01
07/12/2021 531778786.xlsx Cond Unit MT - Step CAP

Declared cooling capacity at full load DC = declared cooling capacity at temperatures A, B, C and D
7.00
i.e. Point A (DC, in kW)

Degradation Calculation
DC in kW COP at this DC DC at part load COP at part load Degradation Capacity Ratio
Cooling demand (PR) (measured or (measured or (measured or (measured or coefficient Cd CR
COP (=DC(full load)*Partload) calculated) calculated) calculated) calculated) (=PR/DC)
COP A 2.10 7.00 7.00 2.10 − − 0.25 1.00
COP B 2.57 6.27 7.76 2.57 3.10 2.44 0.25 0.81
COP C 3.27 5.24 8.74 3.27 3.50 3.10 0.25 0.60
COP D 4.00 4.20 9.61 4.00 3.84 3.80 0.25 0.44
Please consider: Selection of COPA, COPB, Measured or calculated cooling Measured or calculated part load capacity below cooling
COPC, COPD depends on different ambient temp capacity equal or above cooling demand. Leave DC and COP blank if step control not
conditions, load profile and application demand available/necessary.
temperature (LT, MT) Lowest part load DC limited to > 10% of DC at full load.

refrigeration Ratio
j Tj (°C) hj partload% COPPL Ph*Tj PH*Tj/COPDC
demand capa
1 -19 0.1 60% 4.20 3.81 0 0
2 -18 0.4 60% 4.20 3.81 2 0
3 -17 0.6 60% 4.20 3.81 3 1
4 -16 1.1 60% 4.20 3.81 4 1
5 -15 1.7 60% 4.20 3.81 7 2
6 -14 3.0 60% 4.20 3.81 13 3
7 -13 3.8 60% 4.20 3.81 16 4
8 -12 5.7 60% 4.20 3.81 24 6
9 -11 8.9 60% 4.20 3.81 38 10
10 -10 11.8 60% 4.20 3.81 50 13
11 -9 17.3 60% 4.20 3.81 73 19
12 -8 20.0 60% 4.20 3.81 84 22
13 -7 28.7 60% 4.20 3.81 121 32
14 -6 39.7 60% 4.20 3.81 167 44
15 -5 56.6 60% 4.20 3.81 238 62
16 -4 76.4 60% 4.20 3.81 321 84
17 -3 106.1 60% 4.20 3.81 445 117
18 -2 153.2 60% 4.20 3.81 644 169
19 -1 203.4 60% 4.20 3.81 854 224
20 0 248.0 60% 4.20 3.81 1,041 273
21 1 282.0 60% 4.20 3.81 1,184 311
22 2 275.9 60% 4.20 3.81 1,159 304
23 3 300.6 60% 4.20 3.81 1,263 331
24 4 310.8 60% 4.20 3.81 1,305 342
D 25 5 336.5 60% 4.20 3.81 1,413 371
26 6 350.5 61% 4.30 3.75 1,508 403
27 7 363.5 63% 4.41 3.68 1,602 435
28 8 368.9 64% 4.51 3.62 1,664 460
29 9 371.6 66% 4.61 3.55 1,715 483
30 10 377.3 67% 4.72 3.48 1,780 511
31 11 376.5 69% 4.82 3.42 1,816 531
32 12 386.4 70% 4.93 3.35 1,903 568
33 13 389.8 72% 5.03 3.29 1,961 596
34 14 384.4 73% 5.13 3.22 1,973 613
C 35 15 370.5 75% 5.24 3.16 1,940 615
36 16 345.0 76% 5.34 3.09 1,842 596
37 17 328.0 78% 5.44 3.03 1,786 589
38 18 305.4 79% 5.55 2.97 1,694 571
39 19 261.9 81% 5.65 2.91 1,480 509
40 20 223.9 82% 5.76 2.84 1,289 453
41 21 196.3 84% 5.86 2.78 1,150 414
42 22 163.0 85% 5.96 2.72 972 358
43 23 141.8 87% 6.07 2.65 860 324
44 24 121.9 88% 6.17 2.59 752 290
B 45 25 104.5 90% 6.27 2.53 655 259
46 26 85.8 91% 6.38 2.47 547 222
47 27 71.5 93% 6.48 2.41 464 193
48 28 56.6 94% 6.59 2.34 373 159
49 29 43.3 96% 6.69 2.28 290 127
50 30 31.0 97% 6.79 2.22 211 95
51 31 20.2 99% 6.90 2.16 139 64
A 52 32 11.9 100% 7.00 2.10 83 40
53 33 8.2 100% 7.00 2.10 57 27
54 34 3.8 100% 7.00 2.10 27 13
55 35 2.1 100% 7.00 2.10 15 7
56 36 1.2 100% 7.00 2.10 8 4
57 37 0.5 100% 7.00 2.10 4 2
58 38 0.4 100% 7.00 2.10 3 1
total 43,032 13,277
07/12/2021 531778786.xlsx Cond Unit MT - Step CAP

SEPR 3.24
07/12/2021 531778786.xlsx Cond Unit LT - Fix Cap+Stepless

Declared cooling capacity at full load DC = declared cooling capacity at temperatures A, B, C and D DC at rating points B, C and D shall not be lo
5.25
i.e. Point A (DC, in kW) of the cooling demand (PR) -- CR < 1.03

Degradation Calculation
DC in kW COP at this DC Degradation Capacity Ratio
Cooling demand (PR) (measured or (measured or coefficient Cd CR COP at Part Load COP(PL)
COP (=DC(full load)*Partload) calculated) calculated) (=PR/DC) (=COP@full cap)*(1-Cd*(1-CR))
COP A 1.07 5.25 5.25 1.07 0.25 1.00 1.07
COP B 1.28 4.98 5.70 1.28 0.25 0.87 1.24
COP C 1.63 4.59 6.25 1.63 0.25 0.73 1.52
COP D 2.05 4.20 6.75 2.05 0.25 0.62 1.86

Please consider: Selection of COPA, COPB, COPC, COPD depends on Ratio between refrigerant demand and declared capacity (=1,
different ambient temp conditions, load profile and application in case of a continuous capacity adjustment)
temperature (LT, MT)

j Tj (°C) hj partload% refrigeration demand COPPL Ph*Tj PH*Tj/COPDC

1 -19 0.1 80% 4.20 1.86 0 0


2 -18 0.4 80% 4.20 1.86 2 1
3 -17 0.6 80% 4.20 1.86 3 1
4 -16 1.1 80% 4.20 1.86 4 2
5 -15 1.7 80% 4.20 1.86 7 4
6 -14 3.0 80% 4.20 1.86 13 7
7 -13 3.8 80% 4.20 1.86 16 9
8 -12 5.7 80% 4.20 1.86 24 13
9 -11 8.9 80% 4.20 1.86 38 20
10 -10 11.8 80% 4.20 1.86 50 27
11 -9 17.3 80% 4.20 1.86 73 39
12 -8 20.0 80% 4.20 1.86 84 45
13 -7 28.7 80% 4.20 1.86 121 65
14 -6 39.7 80% 4.20 1.86 167 90
15 -5 56.6 80% 4.20 1.86 238 128
16 -4 76.4 80% 4.20 1.86 321 173
17 -3 106.1 80% 4.20 1.86 445 240
18 -2 153.2 80% 4.20 1.86 644 347
19 -1 203.4 80% 4.20 1.86 854 460
20 0 248.0 80% 4.20 1.86 1,041 561
21 1 282.0 80% 4.20 1.86 1,184 638
22 2 275.9 80% 4.20 1.86 1,159 624
23 3 300.6 80% 4.20 1.86 1,263 680
24 4 310.8 80% 4.20 1.86 1,305 703
D 25 5 336.5 80% 4.20 1.86 1,413 761
26 6 350.5 81% 4.24 1.82 1,486 815
27 7 363.5 81% 4.28 1.79 1,555 869
28 8 368.9 82% 4.32 1.76 1,592 907
29 9 371.6 83% 4.36 1.72 1,619 940
30 10 377.3 84% 4.39 1.69 1,658 982
31 11 376.5 84% 4.43 1.66 1,669 1,008
32 12 386.4 85% 4.47 1.62 1,728 1,065
33 13 389.8 86% 4.51 1.59 1,759 1,107
34 14 384.4 87% 4.55 1.56 1,749 1,125
C 35 15 370.5 87% 4.59 1.52 1,700 1,117
36 16 345.0 88% 4.63 1.49 1,596 1,069
37 17 328.0 89% 4.67 1.47 1,531 1,045
38 18 305.4 90% 4.71 1.44 1,437 1,000
39 19 261.9 90% 4.74 1.41 1,242 882
40 20 223.9 91% 4.78 1.38 1,071 776
41 21 196.3 92% 4.82 1.35 947 700
42 22 163.0 93% 4.86 1.32 793 599
43 23 141.8 93% 4.90 1.30 695 536
44 24 121.9 94% 4.94 1.27 602 475
B 45 25 104.5 95% 4.98 1.24 520 420
46 26 85.8 96% 5.02 1.22 430 354
47 27 71.5 96% 5.06 1.19 362 304
48 28 56.6 97% 5.09 1.17 288 247
49 29 43.3 98% 5.13 1.14 223 195
50 30 31.0 99% 5.17 1.12 160 143
51 31 20.2 99% 5.21 1.09 105 96
A 52 32 11.9 100% 5.25 1.07 62 58
53 33 8.2 100% 5.25 1.07 43 40
54 34 3.8 100% 5.25 1.07 20 19
55 35 2.1 100% 5.25 1.07 11 10
56 36 1.2 100% 5.25 1.07 6 6
57 37 0.5 100% 5.25 1.07 3 3
58 38 0.4 100% 5.25 1.07 2 2
total 39,132 24,551

SEPR 1.59
07/12/2021 531778786.xlsx Cond Unit LT - Step CAP

Declared cooling capacity at full load DC = declared cooling capacity at temperatures A, B, C and D
5.25
i.e. Point A (DC, in kW)

Degradation Calculation
DC in kW COP at this DC DC at part load COP at part load Degradation Capacity Ratio
Cooling demand (PR) (measured or (measured or (measured or (measured or coefficient Cd CR
COP (=DC(full load)*Partload) calculated) calculated) calculated) calculated) (=PR/DC)
COP A 1.07 5.25 5.25 1.07 − − 0.25 1.00
COP B 1.28 4.98 5.70 1.28 2.85 1.22 0.25 0.87
COP C 1.63 4.59 6.25 1.63 3.15 1.55 0.25 0.73
COP D 2.05 4.20 6.75 2.05 3.40 1.95 0.25 0.62
Please consider: Selection of COPA, COPB, Measured or calculated cooling Measured or calculated part load capacity below cooling
COPC, COPD depends on different ambient temp capacity equal or above cooling demand. Leave DC and COP blank if step control not
conditions, load profile and application demand available/necessary.
temperature (LT, MT) Lowest part load DC limited to > 10% of DC at full load.

refrigeration Rati
j Tj (°C) hj partload% COPPL Ph*Tj PH*Tj/COPDC
demand cap
1 -19 0.1 80% 4.20 1.97 0 0
2 -18 0.4 80% 4.20 1.97 2 1
3 -17 0.6 80% 4.20 1.97 3 1
4 -16 1.1 80% 4.20 1.97 4 2
5 -15 1.7 80% 4.20 1.97 7 4
6 -14 3.0 80% 4.20 1.97 13 6
7 -13 3.8 80% 4.20 1.97 16 8
8 -12 5.7 80% 4.20 1.97 24 12
9 -11 8.9 80% 4.20 1.97 38 19
10 -10 11.8 80% 4.20 1.97 50 25
11 -9 17.3 80% 4.20 1.97 73 37
12 -8 20.0 80% 4.20 1.97 84 43
13 -7 28.7 80% 4.20 1.97 121 61
14 -6 39.7 80% 4.20 1.97 167 84
15 -5 56.6 80% 4.20 1.97 238 120
16 -4 76.4 80% 4.20 1.97 321 162
17 -3 106.1 80% 4.20 1.97 445 226
18 -2 153.2 80% 4.20 1.97 644 326
19 -1 203.4 80% 4.20 1.97 854 433
20 0 248.0 80% 4.20 1.97 1,041 528
21 1 282.0 80% 4.20 1.97 1,184 600
22 2 275.9 80% 4.20 1.97 1,159 587
23 3 300.6 80% 4.20 1.97 1,263 640
24 4 310.8 80% 4.20 1.97 1,305 661
D 25 5 336.5 80% 4.20 1.97 1,413 716
26 6 350.5 81% 4.24 1.94 1,486 768
27 7 363.5 81% 4.28 1.90 1,555 820
28 8 368.9 82% 4.32 1.86 1,592 857
29 9 371.6 83% 4.36 1.82 1,619 890
30 10 377.3 84% 4.39 1.78 1,658 931
31 11 376.5 84% 4.43 1.74 1,669 958
32 12 386.4 85% 4.47 1.70 1,728 1,015
33 13 389.8 86% 4.51 1.66 1,759 1,057
34 14 384.4 87% 4.55 1.63 1,749 1,076
C 35 15 370.5 87% 4.59 1.59 1,700 1,071
36 16 345.0 88% 4.63 1.55 1,596 1,027
37 17 328.0 89% 4.67 1.52 1,531 1,005
38 18 305.4 90% 4.71 1.49 1,437 964
39 19 261.9 90% 4.74 1.46 1,242 852
40 20 223.9 91% 4.78 1.43 1,071 751
41 21 196.3 92% 4.82 1.39 947 679
42 22 163.0 93% 4.86 1.36 793 582
43 23 141.8 93% 4.90 1.33 695 523
44 24 121.9 94% 4.94 1.30 602 464
B 45 25 104.5 95% 4.98 1.26 520 411
46 26 85.8 96% 5.02 1.24 430 348
47 27 71.5 96% 5.06 1.21 362 299
48 28 56.6 97% 5.09 1.18 288 244
49 29 43.3 98% 5.13 1.15 223 193
50 30 31.0 99% 5.17 1.13 160 143
51 31 20.2 99% 5.21 1.10 105 96
A 52 32 11.9 100% 5.25 1.07 62 58
53 33 8.2 100% 5.25 1.07 43 40
54 34 3.8 100% 5.25 1.07 20 19
55 35 2.1 100% 5.25 1.07 11 10
56 36 1.2 100% 5.25 1.07 6 6
57 37 0.5 100% 5.25 1.07 3 3
58 38 0.4 100% 5.25 1.07 2 2
total 39,132 23,464
07/12/2021 531778786.xlsx Cond Unit LT - Step CAP

SEPR 1.67
Tool version 1.4.2_rev06.16
2016-06-18

About this calculation tool


This calculation tool is provided to help suppliers to calculate the Seasonal Energy Performance Ratio (SEPR) for
their products based upon 4 rating point measurements (or calculations) of COP.

It is intended to assist suppliers to assess the seasonal performance of their products according to a
methodology that is to be used under the proposed European ecodesign regulation for condensing units.

This tool is provided free of charge and in good faith but without guarantee of accuracy. Users should satisfy
themselves that the output meets the requirements of EU Regulation No. 2015/1095.
Calculation methodology is based on prEN13215:2015 Annex A.

What is SEPR? Seasonal Energy Performance Ratio

SEPR is the seasonal energy performance ratio of a condensing unit. It is calculated from the COP of the
condensing unit at 4 different ambient temperatures (see table) and cooling loads, called rating points. The
required rating points are specified in prEN13215:2015, Annex A, showing for each rating point the necessary
part load ratio and condenser inlet air dry bulb temperature. Ambient temperature references see table.

How to use the tool


Due to different load profiles for MT and LT conditions there are in total four sheets for SEPR calculation: Two
each for fixed capacity and stepless condensing units and two more for stepped capacity condensing units. Use
the one appropriate to the condensing unit.
To use the spreadsheet:
1. Please insert the full load rated capacity in cell D3,
2. AND THEN declared rated capacity at the 3 part load rating points (B, C and D - cells D9:11)
3. Insert the declared COP at 4 rating points (cells E8:11).
4. In case of step capacity control also insert part load DC and COP at 3 rating points (B, C, D - cells F9:F11
and G9:G11)

The spreadsheet then calculates the SEPR automatically using a linear interpolation between the rating
points A, B, C, and D and an assumption of a constant capacity for temperatures above A and below D.
Temperature References (°C):
A B C D

AIR (inlet) 32 25 15 5

MT -10 -10 -10 -10


Evaporation
LT -35 -35 -35 -35