You are on page 1of 6

ITEM DESCRIPTION UNIT QTY RATE

US$

NOTE:- This pworks should be executed by a to be


approved by the Engineer

2.0 WATER TREATMENT PLANT

A
Water Treatment Plant as Dayliff WP 250. The treatment
provided should include flocculation, sedimentation,
chlorination and filtration process.The treatment plant to be
complete with 2 No. Grundfos CH 2-30 filter pumps, 2 No.
chlorine & alum dosage equipment CX 500, intergrale
balance tank, 2 No. WP filters all mounted on a base frame.

The treatment plant should have the following features;

High efficiency sedimentation basin

Automatic chemical dosage of alum and chlorine

High quality filter pumps

Double filtration through two series of pressure sand filters

Fully intergrated unit with fully automatic operation NO 1

B Allow for construction of a concrete plinth base for the water


treatment plant, size 5400mm x 3400mm. sum

WATER BOOSTER PUMP ANT TANK

C 10,000 litre polyethylene tank on concrete plinth adjascent to


the water treantment plant for holding clean water. The tank
should be complete with screwed inlet, outlet, overflow
connections and high pressure peglar ball valve. The tank to
be as Kentank CCV 1000, diameter 2360mm, height
2660mm.
NO 1

D Allow for construction of a concrete plinth base for the water


and pump, size 5000mm x 5000mm. SUM

E Domestic water pump set (duty and standby) complete with


the following:-

Duplicate automatic electric motor driven pump, capacity


4m3/hr against a total head of 70m. As Grundfos CR10 - 9 or
approved equivalent, complete with mounting base frame and
control panel for controls and power cables interconnecting
the pump controls to low level and high level electrodes in
the ground level and high level tanks as follows;
-Automatic electric control panel as per specification

for above pumps complete with autocycle changeover switch

B/4 November 2008


Total Carried to Collection Page
ITEM DESCRIPTION UNIT QTY RATE
US$

-Controls and control wiring


-Base frame with antivibration mountings
- Electrode for stopping above pumps should the level in of
water in the tank be too low
-100 mm dial pressure gauge (0-10 bar)
-100 litres air pressure vessel of the diaphragm type
similar to that manufactured by 'Davey'
or equal and approved and to be installed in series NO 1

F Allow for electrical connection from isolator to control panel


and from control panel to electric motors includding all the
necessary cabling and conduiting. NO 1

G 3,500 litre polyethylene tank elevated or installed in roof at


the laundry building. The tank should be complete with
screwed inlet, outlet, overflow connections and high pressure
peglar ball valve. The tank to be as Kentank CCV 350,
diameter 1650mm, height 1870mm. NO 1

PIPE WORK AND ACCESSORIES (PROVISIONAL)

Supply and install 50mm diameter rising main galvanised mild


steel pipes class ‘C’ complying to BS 1387 with screwed and
socket joints to BS 143 and 1256 and of approved
manufacturer with galvanised to BS 729. Tenders must allow
in their pipework prices for all the couplings, unions,
connectors, joints, reducers etc as required in running lengths
of pipework and also where necessary for pipe fixing clips
holder bats plugged and screwed. LM 600

I 50mm diameter gate valve as ‘peglar’ or equal NO 4

J 50mm diameter non-return valve as pegler or equal NO 1

K 50mm diameter GI bend NO 12

L 50mm diameter GI union NO 10

M Allow for installation labour cost

M Any other item necessary to complete the works SUM

B/5 November 2008


Total Carried to Collection Page
ITEM DESCRIPTION UNIT QTY RATE
US$

Collection Page

O TOTAL FROM PAGE 1

P TOTAL FROM PAGE 2

G CONTINGENCY SUM

Total Carried Forward to Summary Page

B/6 November 2008


AMOUNT
US$

B/7 November 2008


AMOUNT
US$

B/8 November 2008


-
AMOUNT
US$

5,000.00

B/9 November 2008

You might also like