Định nghĩa
4
Giá trị tức thời lớn nhất của dòng ngắn mạch (MV)
Initial peak value Ip or Idyn (kA peak)
The value of Ip
determine the making capacity of the
required
i d circuit
i it bbreakers
k
define the electrodynamic forces that
the installation as a whole must be
capable of withstanding.
Giá trị tức thời lớn nhất của dòng ngắn mạch (LV)
6
Dòng ngắn mạch máy phát điện
Fault near the generator (the fault occurs in the immediate vicinity of the generator
supplying the circuit)
The successive effect of the three reactances leads to a gradual reduction in the short
circuit current which is the sum of four components :
- the three alternating components (subtransient,
(subtransient transient and steady
steady-state);
state);
- the aperiodic component resulting from the development of the current in the
circuit (inductive).
8
Dòng ngắn mạch máy phát điện
2/ Vị trí:
• Bên trong thiết bị (ngắn mạch bên
trong máy biến áp, động cơ,…)
• Bên ngoài
3/ Thời gian:
• Thoáng qua (self-extinguishing):
thời gian xảy ra ngắn mạch rất
ngắn để bị phát hiện ngắt bảo vệ
• Quá độ (transient): sự cố hết sau
khi ngắt bảo vệ và đóng lặp lại
• Xác lập (steady-state): sự cố vẫn
còn sau khi đã ngắt bảo vệ 10
11
1. Sự cố ngắn mạch pha – đất: chiếm 80% các trường hợp sự cố,
2. Sự cố ngắn mạch pha – pha: chiếm 15% các trường hợp sự cố, thường phát
triển thành sự cố ngắn mạch 3 pha
3. Sự cố ngắn mạch 3 pha: chiếm 5% các trường hợp sự cố xảy ra đầu tiên,
thường là dòng ngắn mạch lớn nhất
12
Hậu quả của dòng ngắn mạch
Sụt áp
Z=1 Z=1
1 2 3 4
Z=7 Z=1
13
D
I
F
Ngay cả bên trong máy ngắt: I
F = 10-7 I2 x 2x a / D N/m
Ví dụ :
2 thanh dẫn dài 30cm, đặt cách nhau 10cm, dòng ngắn
mạch chạy qua là 100kA đỉnh. Tính lực điện động tác
động lên hệ thống thanh dẫn?
F = [2 .10 -7 .(100 000)² .0,3] / 0.1 = 6000 N
14
Ứng suất nhiệt cho phép
(thermal stress withstand capacity)
for whatever type of short-circuit current (min. or max.), the protection device
must clear the Isc within a time t < 5sec that is compatible with the thermal
stress that can be withstood by the protected cable
∫ I2dt k2.S2
S2
t k2
I2
t duration in s,
S cross-sectional area in mm2
I effective short-circuit current in A expressed, for a.c., as the r.m.s. value,
k is a factor that takes into account the resistivity, temperature factor and heat
capacity of the conductor material, and the appropriate initial and final temperatures.
15
Standardized Isc calculations
standard IEC 909 (VDE 0102) : used primarily for MV-HV networks
methods use the superposition principle
17
in accordance with the rules in articles IEC 364-434.2, 434.3 and IEC 364-533.2,
the maximum prospective short-circuit current at the origin of the circuit and
the minimum prospective short-circuit current at the end of the circuit must be
determined for each circuit.
in all cases, protection must be compatible with the cable heat stress
∫ I2dt K2 S2
18
Short-circuit calculation procedure
upstream Ssc
Isc at transformer
terminals
conductor characteristics breaking capacity main
- power factor, - busbars : inst. trip setting circuit breaker
- coincidence factor, length,
- duty factor width, Isc of main LV
- foreseeable thickness. switchboard outgoers main LV
expansion factor - cables : breaking capacity switchboard
type of insulation inst. trip setting distribution
single-core or multicore, circuit breaker
length, Isc at head of
cross-section. secondary switchboards
- feeder - environment : breaking capacity secondary
- current ambient temperature, distribution
ratings installation method,, inst. trip setting circuit breaker
- voltage number of contiguous circuits. Isc at head of final
drops switchboards
breaking capacity final
distribution
inst. trip setting circuit breaker
load Isc at end of final
rating outgoers
19
Zsc Zsc
A
U
Zs U Zs
20
Calculation of Isc by the impedance method
three-phase fault
Zsc ZSC
U/ 3
~ U/ 3 I sc3
Zsc
Zsc
Zsc
phase-to-phase fault
Zsc ZSC
U
~ U I sc2
2. Zsc
Zsc ZSC
Isc 3
21
U/ 3
I sc1
ZLn
~ U/ 3 Zsc + Z Ln
ZLn Icc3 If ZLN=ZSC
phase-to-PE fault
Zsc ZSC
U/ 3
ZPE
~ U/ 3 IscPE
Zsc + Z PE
Z
ZPE
22
Example : impedance method
U U2
three phase short circuit Isc Z sc R X ; Psc U.Isc 3
2 2
avec
3 Z sc Z cc
U2 R # 0
0,15
15
upstream
t network
t k Z ;
Ssc X
U2 Usc% R
synchronous generator Z X ; # 0,15
Pn 100 X
24
How to calculate Isc
ρ = 1.8
1 8 • 10
10-6
6 Ω cm Copper
R = ρ • L/S
ρ = 2.8 • 10-6 Ω cm Aluminium
U2 20 to 25
asynchronous motors Z= Only subtransient impedance
Pn 100
25
Phương pháp các thành phần đối xứng
Tröôøng hôïp heä thoáng 3 pha ñoái xöùng ñöa veà baøi toaùn 1 pha (pha-trung tính)
Tröôøng hôïp heä thoáng 3 pha khoâng ñoái xöùng giaûi maïch baèng phöông phaùp caùc
thaønh p
phaàn ñoái xöùng
27
28
Phương pháp IEC (tiêu chuẩn 60909)
• I''k,
I''k see the
th equations
ti for
f I''k in
i the
th tables
t bl opposite,it where
h voltage
lt ffactor
t c isi defined
d fi d
by the standard; geometric or algebraic summing,
• ip = k • 2 • I''k, where k is less than 2, depending on the R/X ratio of the positive sequence
impedance for the given branch; peak summing,
• Ib = m • q • I''k, where m and q are less than 1, depending on the generators and motors,
and the minimum current interruption delay; algebraic summing,
• Ik = I''k, when the fault is far from the generator,
• Ik = l • Ir, for a generator, where Ir is the rated generator current and l is a factor
depending on its saturation inductance; algebraic summing.
29
Ảnh hưởng của dòng ngắn mạch đến các thành phần trong hệ thống điện
Phần tử thụ động: cáp, thanh cái, máy ngắt phụ tải, máy biến áp, cuộn kháng nối
tiếp, tụ bù, máy biến áp đo lường phải có khả năng tải dòng điện định mức và cả
dòng ngan mach trong mot khoảng thơi gian ngan được đặc trưng bởi:
- Độ bền điện động (tính bằng kA đỉnh): độ bền cơ đối với lực điện động
- Độ bền nhiệt ( tính rms . giây): độ tăng nhiệt nằm trong giới hạn cho phép
trong thời gian xảy ra ngắn mạch
Phần tử tích cực: máy ngắt bảo vệ bảo vệ ngắt dòng điện NM được đặc trưng
bởi:
30