You are on page 1of 52

WORLD UNIVERSITY

O F B A N G L A D E S H

DEPARTMENT
OF
CIVIL ENGINEERING

Course Code :- CE 806

Course Title :- Structural Analysis and Design Sessional II

Project

A Six Storied Residential Building Analysis,


Design
&
Reinforcement Detailing

Instructed By :-
Ishtiaque Ahmed Tuhin
Lecturer, Department of Civil Engineering
World University of Bangladesh

Prepared By :-
Group : I
Roll No : 446, 447, 449, 450, 451 & 452
Batch ID : CIVIL, 15th
Semester : 9th

General Information Page 1


Six Storied Residential Building Analysis, Design &
Reinforcement Detailing

Design Consideration :

- To Consider Lateral Load (Earth Quake & Wind Load)

- Frame Analysis
● To design all components e.g.; Beam. Column, Slab, Footing etc.

- Additional
● Water tank, Reservoir & Stair

General Information :
- Building Type
● 6 Story, each floor height is 10 '- 0.0 "
~

● Frame Structure e.g.: Beam-Column Supported Slab


● All Brick wall thick is - 5.0 "

- Building Location → Dhaka

- Plot Area → 3139.00 sft

- Soil Investigation (based on soil report)


● Allowable bearing capacity of Soil = 5.00 ksf

- Grade Level → 7 '- 0.0 "


~
= 7.00 feet

- Design Criteria
● Shallow Foundation is required

General Consideration :

- Loading Pattern
● Live Load = 60.00 psf (slab)
= 100.00 psf (stair)

● Floor Finish = 30.00 psf

General Information Page 2


- Material Properties
● Concrete Strength, f'c = 3000 psi
● Steel Strength, fs = 60000 psi

Primary Assumption :

- Column Size
● Interior = 10.00 " x 20.00 "
● Exterior = 10.00 " x 15.00 "
● Corner = 10.00 " x 15.00 "

- Beam Size
● Floor Beam = 10.00 " x 18.00 "
● Grade Beam = 12.00 " x 18.00 "

- Slab Thickness
Assuming Primary Slab Thickness with respect to largest Slab Panel
Slab Panel : 17.08 ft. x 18.50 ft.
Clear Span of Slab
● Short Direction = 16.25 feet
● Long Direction = 17.67 feet

Slab Perimeter
Primary Slab Thickness, h(min) =
180
( 16.25 + 17.67 ) x 2
= x 12
180
= 4.52 inch.
≈ 5.00 inch.

General Information Page 3


General Information Page 4
SV4 DL =
LL =
2.06

0.41 SV4 DL =
LL =
2.06

0.41

S4 S4
DL = 2.06 DL = 2.06
LL = LL =
0.41 0.41

S3 S3
DL = 2.06 DL = 2.06
LL = LL = 0.41
0.41

( Slab Load- psf )


S2 S2
DL = 2.06 DL = 2.06
LL = LL = 0.41
0.41

S1 S1
DL = 2.06 DL = 2.06
LL = LL = 0.41
0.41

SV1 DL =
LL =
2.06

0.41 SV1 DL =
LL =
2.06

0.41

General Information Page 5


52.80 52.80

54.70
54.70

60.55 60.55 60.55 60.55

54.70
54.70

( Slab Tributary Area - sft )


57.08 57.08

32.96 32.96
22.96 22.96

67.08 67.08

87.97 87.97

78.03 78.03 78.03 78.03

87.97 87.97

87.48 87.48

72.25 72.25 72.25


72.25

87.48 87.48

71.60 71.60

General Information Page 6


SV4 ● Short Direction = 3 ' - 2.5 " = 3.21 feet
~

● Long Direction = 16 ' - 5.5 " = 16.46 feet


~

● Short Area = 52.80 sft

S4 ● Short Direction = 14 ' -


~ 9.5 " = 14.79 feet
● Long Direction = 15 ' -
~ 7.0 " = 15.58 feet
● Short Area = 54.70 sft
● Large area = 60.55 sft

S3 ● Short Direction = 9 ' -


~ 7.0 " = 9.58 feet
● Long Direction = 18 ' -
~ 9.5 " = 18.79 feet
● Short Area = 22.96 sft = 32.96 sft
● Large area = 67.08 sft = 57.08 sft

S2 ● Short Direction = 17 ' -


~ 8.0 " = 17.67 feet
● Long Direction = 18 ' -
~ 9.5 " = 18.79 feet
● Short Area = 78.03 sft
● Large area = 87.97 sft

S1 ● Short Direction = 17 ' -


~ 0.0 " = 17.00 feet
● Long Direction = 18 ' -
~ 9.5 " = 18.79 feet
● Short Area = 72.25 sft
● Large area = 87.48 sft

SV4 ● Short Direction = 3 ' - 6.0 " = 3.50 feet


~

● Long Direction = 20 ' - 5.5 " = 20.46 feet


~

● Short Area = 71.60 sft

General Information Page 7


DL = 1.42
LL =
0.86

B14 B15 B14


DL = 2.06 DL = 2.06
LL = LL =
0.41 0.41

B13 B12 B12 B13


DL = 1.18
DL = 1.18 DL = 1.18
DL = 1.18
LL =
LL = 0.22 LL = LL =
0.22 0.22 0.22

B10 B11 B10


DL = 1.49 DL = 1.18 DL = 1.49
LL = 0.43
LL = 1.02
LL = 0.43

B9 B8 B9
DL = 0.89
DL = 1.08 DL = 0.89
LL = 0.13 LL = LL =
0.25 0.13

B7 B7

( Beam Load- k/' )


DL = 1.50 DL = 1.50
LL = LL = 0.47
0.47

B6 B5 B6
DL = 1.16 DL = 1.63 DL = 1.16
LL = LL = LL = 0.25
0.25 0.51

B4 B4
DL = 1.79 DL = 1.79
LL = 0.54
LL = 0.54

B2 B1 B2
DL = 1.24 DL = 1.79 DL = 1.24
LL = 0.24 LL = LL =
0.49 0.24

B3 B3
DL = 2.14 DL = 2.14
LL = LL = 0.49
0.49

General Information Page 8


C9 C10 C10 C9
DL = 168.50 DL = 216.32 DL = 216.32 DL = 168.50
LL = LL = LL = LL =
38.26 65.29 65.29 38.26

Combined footing

C7 C8 C8 C7
DL = 170.76 DL = 187.63 DL = 187.63 DL = 170.76
LL = LL = LL = LL =
45.77 70.01 70.01 45.77

( Column Load- k )
C5 C6 C5
DL = 196.42 DL = 322.43 DL = 196.42
LL = LL = LL =
58.22 108.86 58.22

Square footing

C3 C4 C3
DL = 252.84
DL = 252.84 DL = 419.68 LL =
LL = LL = 72.62
72.62 136.16

Rectangular footing

DL = 207.24 DL = 365.23 DL = 207.24


LL = LL = LL =
51.00 97.55 51.00

C1 C2 C1

General Information Page 9


General Information Page 10
Load Calculation :

Gravity Load

(a) Load on Slab :

Slab Panel ID - S1

Length of Partition wall = 36 ' -


~ 0.0 " = 36.00 feet

Slab Panel
● Short Direction = 17 ' - ~ 10.0 " = 17.83 feet
● Long Direction = 19 ' - ~ 7.5 " = 19.63 feet

36.00 x (5/12) x 8.50 x 120


(a) Load from Partition wall = = 43.72 psf
17.83 x 19.63
(b) Load from Floor Finish = 30.00 psf
5.00
(c) Self Weight = x 150 = 62.50 psf
12
(d) Live Load = 60.00 psf

Slab Panel ID - S2

Length of Partition wall = 16 ' -


~ 0.0 " = 16.00 feet

Slab Panel
● Short Direction = 18 ' - ~ 6.0 " = 18.50 feet
● Long Direction = 19 ' - ~ 7.5 " = 19.63 feet

16.00 x (5/12) x 8.50 x 120


(a) Load from Partition wall = = 18.73 psf
18.50 x 19.63
(b) Load from Floor Finish = 30.00 psf
5.00
(c) Self Weight = x 150 = 62.50 psf
12
(d) Live Load = 60.00 psf

Slab Load Page 11


Slab Panel ID - S3

Length of Partition wall = 0'-


~ 0.0 " = 0.00 feet

Slab Panel
● Short Direction = 10 ' - ~ 5.0 " = 10.42 feet
● Long Direction = 19 ' - ~ 7.5 " = 19.63 feet

0.00 x (5/12) x 8.50 x 120


(a) Load from Partition wall = = 0.00 psf
10.42 x 19.63
(b) Load from Floor Finish = 30.00 psf
5.00
(c) Self Weight = x 150 = 62.50 psf
12
(d) Live Load = 60.00 psf

Slab Panel ID - S4

Length of Partition wall = 24 ' -


~ 0.0 " = 24.00 feet

Slab Panel
● Short Direction = 15 ' - ~ 7.5 " = 15.63 feet
● Long Direction = 16 ' - ~ 5.0 " = 16.42 feet

24.00 x (5/12) x 8.50 x 120


(a) Load from Partition wall = = 39.76 psf
15.63 x 16.42
(b) Load from Floor Finish = 30.00 psf
5.00
(c) Self Weight = x 150 = 62.50 psf
12
(d) Live Load = 60.00 psf

Slab Load Page 12


Slab Panel ID - SV1

Length of Partition wall = 23 ' -


~ 6.0 " = 23.50 feet

Slab Panel
● Short Direction = 3 ' - ~ 7.5 " = 3.63 feet
● Long Direction = 19 ' - ~ 7.5 " = 19.63 feet

23.50 x (5/12) x 8.50 x 120


(a) Load from Partition wall = = 140.39 psf
3.63 x 19.63
(b) Load from Floor Finish = 30.00 psf
5.00
(c) Self Weight = x 150 = 62.50 psf
12
(d) Live Load = 60.00 psf

Slab Panel ID - CV4

Length of Partition wall = 21 ' -


~ 7.5 " = 21.63 feet

Slab Panel
● Short Direction = 3 ' - ~ 4.0 " = 3.33 feet
● Long Direction = 15 ' - ~ 7.5 " = 15.63 feet

21.63 x (5/12) x 8.50 x 120


(a) Load from Partition wall = = 176.46 psf
3.33 x 15.63
(b) Load from Floor Finish = 30.00 psf
5.00
(c) Self Weight = x 150 = 62.50 psf
12
(d) Live Load = 60.00 psf

Slab Load Page 13


Table : 1 Gravity Load on Slab

Slab Load Total Load


Length of
Panel
Wall PW FF SW LL Wdl Wll
ID
1 2 3 4 6 5 7 8

S1 36.00 43.72 30.00 62.50 60.00 136.22 60.00

S2 16.00 18.73 30.00 62.50 60.00 111.23 60.00

S3 0.00 0.00 30.00 62.50 60.00 92.50 60.00

S4 24.00 39.76 30.00 62.50 60.00 132.26 60.00

SV1 23.50 140.39 30.00 62.50 60.00 232.89 60.00

SV4 21.63 176.46 30.00 62.50 60.00 268.96 60.00

Slab Load Page 14


Stair Case load Analysis :

5"
Rise 6"

5'- 0" Trade 10"

5"

5"

3'- 6" 8'- 4" 5'- 4"

Dead Load :
1 6.00 10.00
Weight of one Step = x x x 150 = 31.25 plf
2 12 12
31.25
Load of Steps = x 12 = 37.50 psf
10.00
5.00
Weight of Slab (inclined) = x 150 = 62.50 psf
12
2 2
62.50 x 8.33 + 5.00
Vertical load = = 72.89 psf
8.33
Total Vertical load = 37.50 + 72.89 = 110.39 psf

DL = 62.50 psf DL = 110.40 psf DL = 62.50 psf


+ + +
LL = 100 psf LL = 100 psf LL = 100 psf

3'- 6" 8'- 4" 5'- 4"

( 62.50 x 3.50 ) + ( 110.39 x 8.33 ) + ( 62.50 x 5.33 )


UDL (DL) = = 85.75 psf
3.50 + 8.33 + 5.33
1
DL for Each Beam = x 85.75 x 17.16 = 0.74 k / '
2

Live Load :
1
LL for Each Beam = x 100.00 x 17.16 = 0.86 k / '
2

Stair Load Page 15


(b) Load on Beam :

Beam ID - B1

Length of Beam = 17 '- 10.0 " = 17.83 feet


~

Length of Main Wall = 17 '- 10.0 " = 17.83 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S1 = 72.25 sft


● S1 = 72.25 sft

17.83 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
17.83
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
72.25 x 136.22 + 72.25 x 136.22
DL = = 1.10 k / '
17.83
72.25 x 60.00 + 72.25 x 60.00
LL = = 0.49 k / '
17.83

Beam ID - B2

Length of Beam = 17 '- 10.0 " = 17.83 feet


~

Length of Main Wall = 17 '- 10.0 " = 17.83 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S1 = 72.25 sft

17.83 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
17.83
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
72.25 x 136.22
DL = = 0.55 k / '
17.83
72.25 x 60.00
LL = = 0.24 k / '
17.83

Beam Load Page 16


Beam ID - B3

Length of Beam = 19 '- 7.5 " = 19.63 feet


~

Length of Main Wall = 19 '- 7.5 " = 19.63 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S1 = 87.48 sft


● SV1 = 71.60 sft

19.63 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
19.63
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
87.48 x 136.22 + 71.60 x 232.89
DL = = 1.46 k / '
19.63
87.48 x 60.00 + 71.60 x 60.00
LL = = 0.49 k / '
19.63

Beam ID - B4

Length of Beam = 19 '- 7.5 " = 19.63 feet


~

Length of Main Wall = 19 '- 7.5 " = 19.63 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S1 = 87.48 sft


● S2 = 87.97 sft

19.63 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
19.63
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
87.48 x 136.22 + 87.97 x 111.23
DL = = 1.11 k / '
19.63
87.48 x 60.00 + 87.97 x 60.00
LL = = 0.54 k / '
19.63

Beam Load Page 17


Beam ID - B5

Length of Beam = 18 '- 6.0 " = 18.50 feet


~

Length of Main Wall = 18 '- 6.0 " = 18.50 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S2 = 78.03 sft


● S2 = 78.03 sft

18.50 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
18.50
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
78.03 x 111.23 + 78.03 x 111.23
DL = = 0.94 k / '
18.50
78.03 x 60.00 + 78.03 x 60.00
LL = = 0.51 k / '
18.50

Beam ID - B6

Length of Beam = 18 '- 6.0 " = 18.50 feet


~

Length of Main Wall = 18 '- 6.0 " = 18.50 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S2 = 78.03 sft

18.50 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
18.50
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
78.03 x 111.23
DL = = 0.47 k / '
18.50
78.03 x 60.00
LL = = 0.25 k / '
18.50

Beam Load Page 18


Beam ID - B7

Length of Beam = 19 '- 7.5 " = 19.63 feet


~

Length of Main Wall = 19 '- 7.5 " = 19.63 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S2 = 87.97 sft


● S3 = 67.08 sft

19.63 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
19.63
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
87.97 x 111.23 + 67.08 x 92.50
DL = = 0.81 k / '
19.63
87.97 x 60.00 + 67.08 x 60.00
LL = = 0.47 k / '
19.63

Beam ID - B8

Length of Beam = 10 '- 5.0 " = 10.42 feet


~

Length of Main Wall = 10 '- 5.0 " = 10.42 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S3 = 32.96 sft = 66.66 % x 32.96 = 21.97 sft


● S3 = 32.96 sft = 66.66 % x 32.96 = 21.97 sft

10.42 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
10.42
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
21.97 x 92.50 + 21.97 x 92.50
DL = = 0.39 k / '
10.42
21.97 x 60.00 + 21.97 x 60.00
LL = = 0.25 k / '
10.42

Beam Load Page 19


Beam ID - B9

Length of Beam = 10 '- 5.0 " = 10.42 feet


~

Length of Main Wall = 10 '- 5.0 " = 10.42 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S3 = 22.96 sft

10.42 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
10.42
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
22.96 x 92.50
DL = = 0.20 k / '
10.42
22.96 x 60.00
LL = = 0.13 k / '
10.42

Beam ID - B10

Length of Beam = 15 '- 7.5 " = 15.63 feet


~

Length of Main Wall = 15 '- 7.5 " = 15.63 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S3 = 57.08 sft


● S4 = 54.70 sft

15.63 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
15.63
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
57.08 x 92.50 + 54.70 x 132.26
DL = = 0.80 k / '
15.63
57.08 x 60.00 + 54.70 x 60.00
LL = = 0.43 k / '
15.63

Beam Load Page 20


Beam ID - B11

Length of Beam = 8 '- 0.0 " =


~
8.00 feet

Length of Main Wall = 0 '- 0.0 " =


~
0.00 feet
Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S3 = 32.96 sft = 33.33 % x 32.96 = 10.99 sft


● S3 = 32.96 sft = 33.33 % x 32.96 = 10.99 sft

0.00 x (5/12) x 8.50 x 120


(a) Load from Main wall = = 0.00 k / '
8.00
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
10.99 x 92.50 + 10.99 x 92.50
DL = = 0.25 k / '
8.00
10.99 x 60.00 + 10.99 x 60.00
LL = = 0.16 k / '
8.00

(d) Load from Stair


DL = 0.74 k / ' LL = 0.86 k / '

Beam ID - B12

Length of Beam = 16 '- 5.0 " = 16.42 feet


~

Length of Main Wall = 16 '- 5.0 " = 16.42 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S4 = 60.55 sft

16.42 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
16.42
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
60.55 x 132.26
DL = = 0.49 k / '
16.42
60.55 x 60.00
LL = = 0.22 k / '
16.42

Beam Load Page 21


Beam ID - B13

Length of Beam = 16 '- 5.0 " = 16.42 feet


~

Length of Main Wall = 16 '- 5.0 " = 16.42 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S4 = 60.55 sft

16.42 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
16.42
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
60.55 x 132.26
DL = = 0.49 k / '
16.42
60.55 x 60.00
LL = = 0.22 k / '
16.42

Beam ID - B14

Length of Beam = 15 '- 7.5 " = 15.63 feet


~

Length of Main Wall = 15 '- 7.5 " = 15.63 feet


~

Beam Size = 10.00 " x 18.00 "

Slab Tributary Area ● S4 = 54.70 sft


● SV4 = 52.80 sft

15.63 x (5/12) x 10.00 x 120


(a) Load from Main wall = = 0.50 k / '
15.63
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Slab
54.70 x 132.26 + 52.80 x 268.96
DL = = 1.37 k / '
15.63
54.70 x 60.00 + 52.80 x 60.00
LL = = 0.41 k / '
15.63

Beam Load Page 22


Beam ID - B15

Length of Beam = 8 '- 0.0 " =


~
8.00 feet

Length of Main Wall = 8 '- 0.0 " =


~
8.00 feet
Beam Size = 10.00 " x 18.00 "
8.00 x (5/12) x 10.00 x 120
(a) Load from Main wall = = 0.50 k / '
8.00
10.00 18.00
(c) Self Weight of Beam = ( x ) x 150 = 0.19 k / '
12 12
(d) Load from Stair
DL = 0.74 k / ' LL = 0.86 k / '

Beam Load Page 23


Table : 2 Gravity Load on Beam

Tributary Area Load from Slab Total Load


Beam Length of Length of
ID Beam Main Wall
A1 A2 DL (k/') LL (k/') Wdl (k/') Wll (k/')
1 2 3 4 5 6 7 8 9

B1 17.83 17.83 72.25 72.25 1.10 0.49 1.79 0.49


B2 17.83 17.83 72.25 0.00 0.55 0.24 1.24 0.24
B3 19.63 19.63 87.48 71.60 1.46 0.49 2.14 0.49
B4 19.63 19.63 87.48 87.97 1.11 0.54 1.79 0.54
B5 18.50 18.50 78.03 78.03 0.94 0.51 1.63 0.51
B6 18.50 18.50 78.03 0.00 0.47 0.25 1.16 0.25
B7 19.63 19.63 87.97 67.08 0.81 0.47 1.50 0.47
B8 10.42 10.42 21.97 21.97 0.39 0.25 1.08 0.25
B9 10.42 10.42 22.96 0.00 0.20 0.13 0.89 0.13
B10 15.63 15.63 57.08 54.70 0.80 0.43 1.49 0.43
B11 8.00 0.00 10.99 10.99 0.25 0.16 1.18 1.02
B12 16.42 16.42 60.55 0.00 0.49 0.22 1.18 0.22
B13 16.42 16.42 60.55 0.00 0.49 0.22 1.18 0.22
B14 15.63 15.63 54.70 52.80 1.37 0.41 2.06 0.41
B15 8.00 8.00 0.00 0.00 0.00 0.00 1.42 0.86

Beam Load Page 24


Over Head Tank & Chilakotha Load Analysis :

- Number of Unit
● 10 Units (GF will be use for Parking)

- Number of Person
● 8 Member per Units (Average)
Total Person of the building = 10 x 8 = 80 Nos.

- Water requirement
● 150 LPCD
Requirement of water = 80 x 150 = 12000 Litter/day
Add. 10% = 1200 Litter/day
= 13200 Litter/day

- Volume of the Tank


● Water tank will be refill 2 Times per day
13200
Volume of Tank = = 6600.00 Litter
2
= 233.05 cft

- Dimension of the Tank


● Tank will be placed on the stair case
Length of Tank = 10 '- 0.0 "
~

Width of Tank = 8 '- 0.0 "~

233.05
Height of Tank = = 3.55 feet
9.17 x 7.17
Free board = 1.00 feet
Bottom & Top Slab thickness = 0.83 feet
Total Height = 5.38 feet

≈ 5 '- 6.0 "


~

Tank (OH) Load Page 25


A A
10'- 0" X 8'- 0"

Fig : Plan

4"

1' - 0" Free Board

5'- 6"
5" 5"

6"
B12
C8 Roof of Cilakotha C10 2'- 0"

5"
B12
16'- 6"
7'- 6"
Roof Floor

Fig : Section A-A

(1) Dead Load from Water Tank :

4.00 k
(a) Load from Top Slab = ( 10.00 x 8.00 x ) x 150 = 4.00
12
6.00 k
(b) Load from Bott. Slab = ( 10.00 x 8.00 x ) x 150 = 6.00
12
5.00 k
(c) Load from Side Wall = ( 36.00 x 4.67 x ) x 150 = 10.50
12
10.00 18.00 k
(d) Self Weight of Beam = ( 36.00 x x ) x 150 = 6.75
12 12

Tank (OH) Load Page 26


10.00 20.00 k
(e) Column -C8 (Each) = ( 2.00 x x ) x 150 = 0.42
12 12
10.00 15.00 k
(f) Column-C10 (Each) = ( 2.00 x x ) x 151 = 0.31
12 12

(2) Live Load from Water Tank :

k
(a) Load from Water = 233.05 x 62.40 = 14.54

k
(b) Load from Cleaner = 2 Person x ( 10.00 x 8.00 ) 20 = 3.20

(3) Dead Load from Chilakotha :

5.00 k
(a) Chilakotha Slab = ( 16.50 x 8.00 x ) x 152 = 8.36
12
10.00 18.00 k
(b) Self Weight of Beam = ( 36.00 x x ) x 150 = 6.75
12 12
10.00 20.00 k
(c) Column-C8 (Each) = ( 7.50 x x ) x 150 = 1.56
12 12
10.00 15.00 k
(d) Column-C10 (Each) = ( 7.50 x x ) x 151 = 1.18
12 12

Tank (OH) Load Page 27


Load from Load from
Total Load Each Column Load
Water Tank Chilakotha Number of
Column
DL (k) LL (k) DL (k) LL (k) Wdl (k) Wll (k) Wdl (k) Wll (k)

1 2 3 4 5 6 7 8 9

4.00 14.54 8.36 -


6.00 3.20 6.75 -
45.10 17.74 4 11.28 4.44
10.50 - 1.56 -
6.75 - 1.18 -

Load from Water Tank &


Total Load of each column
Number of Self weight Chilakotha
Column ID
Column of Column
Wdl (k) Wll (k) Wdl (k) Wll (k)

1 2 3 8 9 5 6

C8 2 1.98 11.28 4.44 13.25 4.44

C10 2 1.49 11.28 4.44 12.77 4.44

Tank (OH) Load Page 28


(c) Load at Base :

Column ID - C1

Column Size = 10.00 " x 15.00 "


Length of Column = 6 x 10 '- 0.0 " +
~
7 '- 0.0 " = 67.00 feet
~

Surrounding Beam = Beam ID Length Wdl Wll


B2 8.92 1.24 0.24
B3 9.81 2.14 0.49

10.00 15.00
(a) Self Weight of Column = ( x ) x 150 = 0.16 k / '
12 12

k
(b) DL from Beam = (i) 8.92 x 1.24 = 11.05
k
(ii) 9.81 x 2.14 = 21.04
k
Total = 32.09

k
(c) LL from Beam = (i) 8.92 x 0.24 = 2.17
k
(ii) 9.81 x 0.49 = 4.77
k
Total = 6.94

12.00 18.00
(d) Self Weight of GB = ( x ) x 150 = 0.23 k / '
12 12

k
(e) DL from GB = (i) 8.92 x 0.23 = 2.01
k
(ii) 9.81 x 0.23 = 2.21
k
Total = 4.21

k
(f) LL from GB = (i) 8.92 x 0.50 = 4.46
k
(ii) 9.81 x 0.50 = 4.91
k
Total = 9.36

Column Load Page 29


Column ID - C2

Column Size = 10.00 " x 15.00 "


Length of Column = 6 x 10 '- 0.0 " +
~
7 '- 0.0 " = 67.00 feet
~

Surrounding Beam = Beam ID Length Wdl Wll


B1 8.92 1.79 0.49
B3 9.81 2.14 0.49

10.00 15.00
(a) Self Weight of Column = ( x ) x 150 = 0.16 k / '
12 12

k
(b) DL from Beam = (i) 8.92 x 1.79 = 15.97
k
(ii) 9.81 x 2.14 = 21.04
k
(iii) 9.81 x 2.14 = 21.04
k
Total = 58.06

k
(c) LL from Beam = (i) 8.92 x 0.49 = 4.34
k
(ii) 9.81 x 0.49 = 4.77
k
(iii) 9.81 x 0.49 = 4.77
k
Total = 13.88

12.00 18.00
(d) Self Weight of GB = ( x ) x 150 = 0.23 k / '
12 12

k
(e) DL from GB = (i) 8.92 x 0.23 = 2.01
k
(ii) 9.81 x 0.23 = 2.21
k
(iii) 9.81 x 0.23 = 2.21
k
Total = 6.42

k
(f) LL from GB = (i) 8.92 x 0.50 = 4.46
k
(ii) 9.81 x 0.50 = 4.91
k
(iii) 9.81 x 0.50 = 4.91
k
Total = 14.27

Column Load Page 30


Column ID - C3

Column Size = 10.00 " x 15.00 "


Length of Column = 6 x 10 '- 0.0 " +
~
7 '- 0.0 " = 67.00 feet
~

Surrounding Beam = Beam ID Length Wdl Wll


B2 8.92 1.24 0.24
B4 9.81 1.79 0.54
B6 9.25 1.16 0.25

10.00 15.00
(a) Self Weight of Column = ( x ) x 150 = 0.16 k / '
12 12

k
(b) DL from Beam = (i) 8.92 x 1.24 = 11.05
k
(ii) 9.81 x 1.79 = 17.60
k
(iii) 9.25 x 1.16 = 10.70
k
Total = 39.35

k
(c) LL from Beam = (i) 8.92 x 0.24 = 2.17
k
(ii) 9.81 x 0.54 = 5.26
k
(iii) 9.25 x 0.25 = 2.34
k
Total = 9.77

12.00 18.00
(d) Self Weight of GB = ( x ) x 150 = 0.23 k / '
12 12

k
(e) DL from GB = (i) 8.92 x 0.23 = 2.01
k
(ii) 9.81 x 0.23 = 2.21
k
(iii) 9.25 x 0.23 = 2.08
k
Total = 6.30

k
(f) LL from GB = (i) 8.92 x 0.50 = 4.46
k
(ii) 9.81 x 0.50 = 4.91
k
(iii) 9.25 x 0.50 = 4.63
k
Total = 13.99

Column Load Page 31


Column ID - C4

Column Size = 10.00 " x 20.00 "

Length of Column = 6 x 10 '- 0.0 " + ~


7 '- 0.0 " = 67.00 feet
~

Surrounding Beam = Beam ID Length Wdl Wll


B1 8.92 1.79 0.49
B4 9.81 1.79 0.54
B5 9.25 1.63 0.51

10.00 20.00
(a) Self Weight of Column = ( x ) x 150 = 0.21 k / '
12 12

k
(b) DL from Beam = (i) 8.92 x 1.79 = 15.97
k
(ii) 9.81 x 1.79 = 17.60
k
(iii) 9.25 x 1.63 = 15.04
k
(iv) 9.81 x 1.79 = 17.60
k
Total = 66.20

k
(c) LL from Beam = (i) 8.92 x 0.49 = 4.34
k
(ii) 9.81 x 0.54 = 5.26
k
(iii) 9.25 x 0.51 = 4.68
k
(iv) 9.81 x 0.54 = 5.26
k
Total = 19.54

12.00 18.00
(d) Self Weight of GB = ( x ) x 150 = 0.23 k / '
12 12

k
(e) DL from GB = (i) 8.92 x 0.23 = 2.01
k
(ii) 9.81 x 0.23 = 2.21
k
(iii) 9.25 x 0.23 = 2.08
k
(iv) 9.81 x 0.23 = 2.21
k
Total = 8.50

k
(f) LL from GB = (i) 8.92 x 0.50 = 4.46
k
(ii) 9.81 x 0.50 = 4.91
k
(iii) 9.25 x 0.50 = 4.63
k
(iv) 9.81 x 0.50 = 4.91
k
Total = 18.90

Column Load Page 32


Column ID - C5

Column Size = 10.00 " x 15.00 "

Length of Column = 6 x 10 '- 0.0 " +


~
7 '- 0.0 " = 67.00 feet
~

Surrounding Beam = Beam ID Length Wdl Wll


B6 9.25 1.16 0.25
B7 9.81 1.50 0.47
B9 5.21 0.89 0.13

10.00 15.00
(a) Self Weight of Column = ( x ) x 150 = 0.16 k / '
12 12

k
(b) DL from Beam = (i) 9.25 x 1.16 = 10.70
k
(ii) 9.81 x 1.50 = 14.74
k
(iii) 5.21 x 0.89 = 4.64
k
Total = 30.08

k
(c) LL from Beam = (i) 9.25 x 0.25 = 2.34
k
(ii) 9.81 x 0.47 = 4.65
k
(iii) 5.21 x 0.13 = 0.69
k
Total = 7.68

12.00 18.00
(d) Self Weight of GB = ( x ) x 150 = 0.23 k / '
12 12

k
(e) DL from GB = (i) 9.25 x 0.23 = 2.08
k
(ii) 9.81 x 0.23 = 2.21
k
(iii) 5.21 x 0.23 = 1.17
k
Total = 5.46

k
(f) LL from GB = (i) 9.25 x 0.50 = 4.63
k
(ii) 9.81 x 0.50 = 4.91
k
(iii) 5.21 x 0.50 = 2.60
k
Total = 12.14

Column Load Page 33


Column ID - C6

Column Size = 10.00 " x 20.00 "

Length of Column = 6 x 10 '- 0.0 " +~


7 '- 0.0 " = 67.00 feet
~

Surrounding Beam = Beam ID Length Wdl Wll


B5 9.25 1.63 0.51
B7 9.81 1.50 0.47
B8 5.21 1.08 0.25

10.00 20.00
(a) Self Weight of Column = ( x ) x 150 = 0.21 k / '
12 12

k
(b) DL from Beam = (i) 9.25 x 1.63 = 15.04
k
(ii) 9.81 x 1.50 = 14.74
k
(iii) 5.21 x 1.08 = 5.61
k
(iv) 9.81 x 1.50 = 14.74
k
Total = 50.13

k
(c) LL from Beam = (i) 9.25 x 0.51 = 4.68
k
(ii) 9.81 x 0.47 = 4.65
k
(iii) 5.21 x 0.25 = 1.32
k
(iv) 9.81 x 0.47 = 4.65
k
Total = 15.30

12.00 18.00
(d) Self Weight of GB = ( x ) x 150 = 0.23 k / '
12 12

k
(e) DL from GB = (i) 9.25 x 0.23 = 2.08
k
(ii) 9.81 x 0.23 = 2.21
k
(iii) 5.21 x 0.23 = 1.17
k
(iv) 9.81 x 0.23 = 2.21
k
Total = 7.67

k
(f) LL from GB = (i) 9.25 x 0.50 = 4.63
k
(ii) 9.81 x 0.50 = 4.91
k
(iii) 5.21 x 0.50 = 2.60
k
(iv) 9.81 x 0.50 = 4.91
k
Total = 17.04

Column Load Page 34


Column ID - C7

Column Size = 10.00 " x 15.00 "

Length of Column = 6 x 10 '- 0.0 " +


~
7 '- 0.0 " = 67.00 feet
~

Surrounding Beam = Beam ID Length Wdl Wll


B9 5.21 0.89 0.13
B10 7.81 1.49 0.43
B13 8.21 1.18 0.22

10.00 15.00
(a) Self Weight of Column = ( x ) x 150 = 0.16 k / '
12 12

k
(b) DL from Beam = (i) 5.21 x 0.89 = 4.64
k
(ii) 7.81 x 1.49 = 11.63
k
(iii) 8.21 x 1.18 = 9.65
k
Total = 25.92

k
(c) LL from Beam = (i) 5.21 x 0.13 = 0.69
k
(ii) 7.81 x 0.43 = 3.35
k
(iii) 8.21 x 0.22 = 1.82
k
Total = 5.86

12.00 18.00
(d) Self Weight of GB = ( x ) x 150 = 0.23 k / '
12 12

k
(e) DL from GB = (i) 5.21 x 0.23 = 1.17
k
(ii) 7.81 x 0.23 = 1.76
k
(iii) 8.21 x 0.23 = 1.85
k
Total = 4.78

k
(f) LL from GB = (i) 5.21 x 0.50 = 2.60
k
(ii) 7.81 x 0.50 = 3.91
k
(iii) 8.21 x 0.50 = 4.10
k
Total = 10.61

Column Load Page 35


Column ID - C8

Column Size = 10.00 " x 20.00 "

Length of Column = 6 x 10 '- 0.0 " +


~
7 '- 0.0 " = 67.00 feet
~

Surrounding Beam = Beam ID Length Wdl Wll


B10 7.81 1.49 0.43
B11 4.00 1.18 1.02
B12 8.21 1.18 0.22

10.00 20.00
(a) Self Weight of Column = ( x ) x 150 = 0.21 k / '
12 12

k
(b) DL from Beam = (i) 7.81 x 1.49 = 11.63
k
(ii) 4.00 x 1.18 = 4.71
k
(iii) 8.21 x 1.18 = 9.65
k
Total = 25.99

k
(c) LL from Beam = (i) 7.81 x 0.43 = 3.35
k
(ii) 4.00 x 1.02 = 4.09
k
(iii) 8.21 x 0.22 = 1.82
k
Total = 9.26

12.00 18.00
(d) Self Weight of GB = ( x ) x 150 = 0.23 k / '
12 12

k
(e) DL from GB = (i) 7.81 x 0.23 = 1.76
k
(ii) 4.00 x 0.23 = 0.90
k
(iii) 8.21 x 0.23 = 1.85
k
Total = 4.50

k
(f) LL from GB = (i) 7.81 x 0.50 = 3.91
k
(ii) 4.00 x 0.50 = 2.00
k
(iii) 8.21 x 0.50 = 4.10
k
Total = 10.01

Column Load Page 36


Column ID - C9

Column Size = 10.00 " x 15.00 "

Length of Column = 6 x 10 '- 0.0 " +~


7 '- 0.0 " = 67.00 feet
~

Surrounding Beam = Beam ID Length Wdl Wll


B13 8.21 1.18 0.22
B14 7.81 2.06 0.41

10.00 15.00
(a) Self Weight of Column = ( x ) x 150 = 0.16 k / '
12 12

k
(b) DL from Beam = (i) 8.21 x 1.18 = 9.65
k
(ii) 7.81 x 2.06 = 16.09
k
Total = 25.74

k
(c) LL from Beam = (i) 8.21 x 0.22 = 1.82
k
(ii) 7.81 x 0.41 = 3.23
k
Total = 5.04

12.00 18.00
(d) Self Weight of GB = ( x ) x 150 = 0.23 k / '
12 12

k
(e) DL from GB = (i) 8.21 x 0.23 = 1.85
k
(ii) 7.81 x 0.23 = 1.76
k
Total = 3.60

k
(f) LL from GB = (i) 8.21 x 0.50 = 4.10
k
(ii) 7.81 x 0.50 = 3.91
k
Total = 8.01

Column Load Page 37


Column ID - C10

Column Size = 10.00 " x 15.00 "

Length of Column = 6 x 10 '- 0.0 " +


~
7 '- 0.0 " = 67.00 feet
~

Surrounding Beam = Beam ID Length Wdl Wll


B12 8.21 1.18 0.22
B14 7.81 2.06 0.41
B15 4.00 1.42 0.86

10.00 15.00
(a) Self Weight of Column = ( x ) x 150 = 0.16 k / '
12 12

k
(b) DL from Beam = (i) 8.21 x 1.18 = 9.65
k
(ii) 7.81 x 2.06 = 16.09
k
(iii) 4.00 x 1.42 = 5.69
k
Total = 31.43

k
(c) LL from Beam = (i) 8.21 x 0.22 = 1.82
k
(ii) 7.81 x 0.41 = 3.23
k
(iii) 4.00 x 0.86 = 3.43
k
Total = 8.47

12.00 18.00
(d) Self Weight of GB = ( x ) x 150 = 0.23 k / '
12 12

k
(e) DL from GB = (i) 8.21 x 0.23 = 1.85
k
(ii) 7.81 x 0.23 = 1.76
k
(iii) 4.00 x 0.23 = 0.90
k
Total = 4.50

k
(f) LL from GB = (i) 8.21 x 0.50 = 4.10
k
(ii) 7.81 x 0.50 = 3.91
k
(iii) 4.00 x 0.50 = 2.00
k
Total = 10.01

Column Load Page 38


Table : 3 Total Gravity Load at Base

Total Load of each


Self Existing Floor Beam Grade Beam Others Number Total Load
Column column
weight of of
ID
Column Beam ID Length DL (k) LL (k) Length DL (k) LL (k) DL (k) LL (k) Wdl (k) Wll (k) Column Wdl (k) Wll (k)

1 3 4 5 6 7 8 9 10 11 12 13 14 2 13 14
B2 8.92 66.31 13.01 8.92 2.01 4.46 - -
C1 10.47 207.24 51.00 2 414.48 102.01
B3 9.81 126.25 28.64 9.81 2.21 4.91 - -
B1 8.92 95.83 26.01 8.92 2.01 4.46 - -
C2 10.47 B3 9.81 126.25 28.64 9.81 2.21 4.91 - - 365.23 97.55 1 365.23 97.55
B3 9.81 126.25 28.64 9.81 2.21 4.91 - -
B2 8.92 66.31 13.01 8.92 2.01 4.46 - -
C3 10.47 B4 9.81 105.58 31.58 9.81 2.21 4.91 - - 252.84 72.62 2 505.68 145.24
B6 9.25 64.19 14.05 9.25 2.08 4.63 - -
B1 8.92 95.83 26.01 8.92 2.01 4.46 - -
B4 9.81 105.58 31.58 9.81 2.21 4.91 - -
C4 13.96 419.68 136.16 1 419.68 136.16
B5 9.25 90.23 28.09 9.25 2.08 4.63 - -
B4 9.81 105.58 31.58 9.81 2.21 4.91 - -
B6 9.25 64.19 14.05 9.25 2.08 4.63 - -
C5 10.47 B7 9.81 88.45 27.91 9.81 2.21 4.91 - - 196.42 58.22 2 392.85 116.44
B9 5.21 27.86 4.13 5.21 1.17 2.60 - -

Load Abstract Page 39


Total Load of each
Self Existing Floor Beam Grade Beam Others Number Total Load
Column column
weight of of
ID
Column Beam ID Length DL (k) LL (k) Length DL (k) LL (k) DL (k) LL (k) Wdl (k) Wll (k) Column Wdl (k) Wll (k)

1 3 4 5 6 7 8 9 10 11 12 13 14 2 13 14
B2
B5 8.92
9.25 66.31
90.23 13.01
28.09 8.92
9.25 2.01
2.08 4.46
4.63 - -
C1 10.47 207.24 51.00 2 414.48 102.01
B7 9.81 88.45 27.91 9.81 2.21 4.91 - -
C6 13.96 322.43 108.86 1 322.43 108.86
B8 5.21 33.68 7.91 5.21 1.17 2.60 - -
B7 9.81 88.45 27.91 9.81 2.21 4.91 - -
B9 5.21 27.86 4.13 5.21 1.17 2.60 - -
C7 10.47 B10 7.81 69.77 20.12 7.81 1.76 3.91 - - 170.76 45.77 2 341.52 91.54
B13 8.21 57.89 10.90 8.21 1.85 4.10 - -
B10 7.81 69.77 20.12 7.81 1.76 3.91
C8 13.96 B11 4.00 28.25 24.55 4.00 0.90 2.00 13.25 4.44 187.63 70.01 2 375.26 140.03
B12 8.21 57.89 10.90 8.21 1.85 4.10
B13 8.21 57.89 10.90 8.21 1.85 4.10 - -
C9 10.47 168.50 38.26 2 336.99 76.52
B14 7.81 96.54 19.35 7.81 1.76 3.91 - -
B12 8.21 57.89 10.90 8.21 1.85 4.10
C10 10.47 B14 7.81 96.54 19.35 7.81 1.76 3.91 12.77 4.44 216.32 65.29 2 432.65 130.58
B15 4.00 34.16 20.59 4.00 0.90 2.00

G. Total Load 3906.77 1144.92

Number of Floor = 6 Nos. Load per Floor 651.13 190.82

Load Abstract Page 40


(a) Earthquake

ZIC
Total Base Shear, V = ( )W
R
Where :
Z - Seismic Zone Co-efficient
I - Structural Importance
R - Response Modification Co-efficient for Structural System
C - Numerical Co-efficient
W - Total Seismic Dead Load

Seismic Zone Co-efficient, Z = 0.150


Figure-6.2.10 (BNBC)
Z (Seismic Zone Co-efficient)
Zone 1 : 0.075
Zone 2 : 0.150
Zone 3 : 0.250

Structural Importance, I = 1.00


Table-6.2.23 (BNBC)
I (Structural Importance)
Essential Facilities 1.25
Hazardous Facilities 1.25
Special Occupancy Structures 1.00
Standard Occupancy Structures 1.00
Low-risk Structures 1.00

1.25 S Where :
Numerical Co-efficient, C =
T2/3 S - Site Soil Characteristics
T - Period of Vibration (Sec)

Site Soil Characteristics, S = 1.50


Table-6.2.25 (BNBC)
S (Site Soil Characteristics)
A Soil Profile 21 meters or more in depth and containing more than 6 meters of soft
to medium stiff clay but not more than 12 meters of soft clay : 1.5

Period of Vibration, T = Ct ( hn )3/4

Ct = 0.073

(BNBC)
Ct - 0.083 for steel moment resisting frames
Ct - 0.073 for reinforced concrete moment resisting frames, and eccentric braced steel frames

Lateral Load Page 41


Height of building above base level, hn = Floor Height + Base Level
" "
= 6 x 10 '- 0.0 ~
+ 0 '- 0.0 ~

= ( 60.00 + 0.00 ) feet


= 60.00 feet = 18.29 Meter

T = 0.073 ( 18.29 )3/4 = 0.65 Sec

1.25 x 1.50
Numerical Co-efficient, C = = 2.51
( 0.65 )2/3

Response Modification Co-efficient for Structural System, R = 12


Table-6.2.24 (BNBC)
R (Response Modification Co-efficient for Structural System)
Special Moment Resisting Frame - Steelet : 12
Special Moment Resisting Frame - Concrete : 12

Total Dead Load, W = 3906.77 kips


= 17384.10 KN

0.150 x 1.00 x 2.51


Total Base Shear, V = ( ) 17384.10
12
= 545.46 KN

Dead Load per floor, wx = 651.13 kips


= 2897.35 KN

Ft = 0.00 Ft = 0.07TV ≤ 0.25V, When T > 0.70 Sec


Ft = 0, When T ≤ 0.70 Sec

( V- Ft ) wx hx ( V- Ft ) wx hx
Design Force, Fx = =
∑ wi hi (w1h1+w2h2+w3h3+w4h4+w5h5+w6h6)
( 545.46 - 0.00 ) 2897.35 x hx
=
2897.35 x 3.05 ( 1+2+……+5+6)

= 8.520 hx

Lateral Load Page 42


Load Distribution on each story level

Height, hx ( V- Ft ) wx hx
Floor Design Force, Fx (KN) =
(m) ∑ wi hi

GF 2.13 Fx = 8.520 hx = 8.52 x 2.13 = 18.15

st
1 Floor 3.05 Fx = 8.520 hx = 8.52 x 3.05 = 25.97

2nd Floor 6.10 Fx = 8.520 hx = 8.52 x 6.10 = 51.95

rd
3 Floor 9.15 Fx = 8.520 hx = 8.52 x 9.15 = 77.92

4th Floor 12.20 Fx = 8.520 hx = 8.52 x 12.20 = 103.90

5th Floor 15.24 Fx = 8.520 hx = 8.52 x 15.24 = 129.87

RF 18.29 Fx = 8.520 hx + Ft = 8.52 x 18.29 + 0.0 = 155.85

Lateral Load Page 43


5

( Grid Layout Plan )


3

A B C D E

Lateral Load Page 44


(1) Considering Earthquake Load form WEST to EAST

155.85 RF

129.87 5th F

103.90 4th F

77.92 3rd F

51.95 2nd F

25.97 1st F

18.15 GF

A C E

Fig : Joint Load (KN)

Table : Load Distribution on Frame (West-East) 4.448 KN = 1kip

Total Load Frame Load (kips)


Story Level
(KN) AE1 AE2 AE3 AE4 AE5

GF 18.15 0.51 1.02 1.02 1.02 0.51

1st F 25.97 0.73 1.46 1.46 1.46 0.73

2nd F 51.95 1.46 2.92 2.92 2.92 1.46

3rd F 77.92 2.19 4.38 4.38 4.38 2.19


th
4 F 103.90 2.92 5.84 5.84 5.84 2.92

5th F 129.87 3.65 7.30 7.30 7.30 3.65

RF 155.85 4.38 8.76 8.76 8.76 4.38

Lateral Load Page 45


(2) Considering Earthquake Load form SOUTH to NORTH

155.85 RF

129.87 5th F

103.90 4th F

77.92 3rd F

51.95 2nd F

25.97 1st F

18.15 GF

1 2 3 4 5

Fig : Joint Load (KN)

Table : Load Distribution on Frame (South-North)

Total Load Frame Load (kips)


Story Level
(KN) A(1-5) B(4-5) C(1-3) D(4-5) E(1-5)

GF 18.15 1.02 - 2.04 - 1.02


st
1 F 25.97 1.46 - 2.92 - 1.46

2nd F 51.95 2.92 - 5.84 - 2.92

3rd F 77.92 4.38 - 8.76 - 4.38

4th F 103.90 5.84 - 11.68 - 5.84

5th F 129.87 7.30 - 14.60 - 7.30

RF 155.85 8.76 - 17.52 - 8.76

Lateral Load Page 46


(b) Wind Load
Detail Calculation for 1st Floor :

Sustained Wind Pressure, qz = Cc CI Cz Vb2

Where,
qz → Sustained wind pressure at height z, KN/m2
Cc → Velocity to pressure conversion co-efficient = 47.20 x 10 -6
CI → Structural importance co-efficient
Cz → Combined height and exposure co-efficient
Vb → Basic wind speed, km/h

Conversion co-efficient, Cc = 47.20 x 10-6

Structural importance co-efficient, CI = 1.00


Table-6.2.9 (BNBC)
CI (Structural Importance)
Essential Facilities 1.25
Hazardous Facilities 1.25
Special Occupancy Structures 1.00
Standard Occupancy Structures 1.00
Low-risk Structures 0.80

Combined height and exposure co-efficient, Cz = 0.368


Table-6.2.10 (BNBC)
Cz (Combined height and exposure co-efficient)
Height above ground level = 0-4.5m, Exposure A = 0.368
Height above ground level = 6.0m, Exposure A = 0.415
Height above ground level = 9.0m, Exposure A = 0.497
Height above ground level = 12.0m, Exposure A = 0.565
Height above ground level = 15.0m, Exposure A = 0.624
Height above ground level = 18.0m, Exposure A = 0.677
Height above ground level = 21.0m, Exposure A = 0.725
Height above ground level = 24.0m, Exposure A = 0.769

Basic wind speed, Vb = 210 km/h


Table-6.2.8 (BNBC)
Vb (Basic wind speed for selected location in BD)
Chittagong = 260 km/h
Comilla= 196 km/h
Dhaka = 210 km/h
Gazipur = 215 km/h
Khulna = 238 km/h
Kurigram = 210 km/h
Sylhet = 195 km/h

-6 2
Sustained Wind Pressure, qz = 47.20 x 10 x 1.00 x 0.368 x 210
2
= 0.766 KN/m

Lateral Load Page 47


(a) Windward :

Design Wind Pressure, Pz = CG Cp qz

Where,
Pz → Design wind pressure, KN/m2
CG → Gust co-efficient
Cpe → External Pressure co-efficient
qz → Sustained wind pressure

Gust co-efficient, CG = 1.654


Table-6.2.11 (BNBC)
CG (Gust co-efficient)
Height above ground level = 0-4.5m, Exposure A = 1.654
Height above ground level = 6.0m, Exposure A = 1.592
Height above ground level = 9.0m, Exposure A = 1.511
Height above ground level = 12.0m, Exposure A = 1.457
Height above ground level = 15.0m, Exposure A = 1.418
Height above ground level = 18.0m, Exposure A = 1.388
Height above ground level = 21.0m, Exposure A = 1.363
Height above ground level = 24.0m, Exposure A = 1.342

External Pressure co-efficient, Cpe = 0.80


Section-2.4.6.7 (BNBC)
Cpe (External Pressure co-efficient)
Windward wall for all value of L/B = 0.80

Design Wind Pressure, Pz = 1.65 x 0.80 x 0.77


2
= 1.014 KN/m

(b) Leeward :

Design Wind Pressure, Pz = CG Cp qz

Where,
Pz → Design wind pressure, KN/m2
CG → Gust co-efficient
Cpe → External Pressure co-efficient
qz → Sustained wind pressure

Gust co-efficient, CG = 1.654

Lateral Load Page 48


External Pressure co-efficient, Cpe = -0.30
Section-2.4.6.7 (BNBC)
Cpe (External Pressure co-efficient)
Leeward wall for L/B(≤0.10) = - 0.50
Leeward wall for L/B( 0.65 ) = - 0.60
Leeward wall for L/B( 1.00 ) = - 0.50
Leeward wall for L/B( 2.00 ) = - 0.30
Leeward wall for L/B(≥4.00) = - 0.20

Design Wind Pressure, Pz = 1.65 x -0.30 x 0.77


2
= -0.380 KN/m

Design Wind Load, Fx = Pz Az

Where,
Pz → Design wind pressure, KN/m2
Az → Area, m2

Lateral Load Page 49


(1) Considering Wind Load form WEST to EAST

Height Cz CG Design
qz Dimension Az Total
Story above (Value (Value Colum
2
Pz (m) Load
Level ground from (kn/m ) from n ID (m2) (KN)
level (m) BNBC) BNBC) B x H
1 2 3 4 5 6 7 8 9 10
C1 2.72 x 3.05 8.30 8.41
C3 5.54 x 3.05 16.90 17.13
1st F 3.05 0.368 0.766 1.654 1.014 C5 4.41 x 3.05 13.45 13.63
C7 4.09 x 3.05 12.47 12.64
C9 2.50 x 3.05 7.63 7.73
C1 2.72 x 3.05 8.30 9.15
C3 5.54 x 3.05 16.90 18.64
2nd F 6.10 0.417 0.868 1.589 1.103 C5 4.41 x 3.05 13.45 14.84
C7 4.09 x 3.05 12.47 13.76
C9 2.50 x 3.05 7.63 8.41
C1 2.72 x 3.05 8.30 10.42
C3 5.54 x 3.05 16.90 21.22
3rd F 9.15 0.500 1.041 1.508 1.256 C5 4.41 x 3.05 13.45 16.89
C7 4.09 x 3.05 12.47 15.66
C9 2.50 x 3.05 7.63 9.57
C1 2.72 x 3.05 8.30 11.41
C3 5.54 x 3.05 16.90 23.24
4th F 12.20 0.568 1.182 1.454 1.375 C5 4.41 x 3.05 13.45 18.50
C7 4.09 x 3.05 12.47 17.16
C9 2.50 x 3.05 7.63 10.49
C1 2.72 x 3.05 8.30 12.28
C3 5.54 x 3.05 16.90 25.00
5th F 15.24 0.628 1.307 1.415 1.480 C5 4.41 x 3.05 13.45 19.90
C7 4.09 x 3.05 12.47 18.46
C9 2.50 x 3.05 7.63 11.28
C1 2.72 x 1.53 4.16 6.54
C3 5.54 x 1.53 8.48 13.31
RF 18.29 0.681 1.418 1.385 1.571 C5 4.41 x 1.53 6.75 10.60
C7 4.09 x 1.53 6.26 9.83
C9 2.50 x 1.53 3.83 6.01

Lateral Load Page 50


Table : Load Distribution on Frame (West-East)

Frame Load (kips)


Story
Pz
Level
AE1 AE2 AE3 AE4 AE5

1st F 1.014 1.89 3.85 3.06 2.84 1.74

2nd F 1.103 2.06 4.19 3.34 3.09 1.89

3rd F 1.256 2.34 4.77 3.80 3.52 2.15

4th F 1.375 2.56 5.22 4.16 3.86 2.36

5th F 1.480 2.76 5.62 4.47 4.15 2.54

RF 1.571 1.47 2.99 2.38 2.21 1.35

(2) Considering Wind Load form SOUTH to NORTH

Height Cz CG Design
qz Dimension Az Total
Story above (Value (Value Colum
2
Pz (m) Load
Level ground from (kn/m ) from n ID (m2) (KN)
level (m) BNBC) BNBC) B x H
1 2 3 4 5 6 7 8 9 10
C1 3.52 x 3.05 10.74 10.88
1st F 3.05 0.368 0.766 1.654 1.014
C2 5.20 x 3.05 15.86 16.08
C1 3.52 x 3.05 10.74 11.85
2nd F 6.10 0.417 0.868 1.589 1.103
C2 5.20 x 3.05 15.86 17.50
C1 3.52 x 3.05 10.74 13.48
3rd F 9.15 0.500 1.041 1.508 1.256
C2 5.20 x 3.05 15.86 19.91
th C1 3.52 x 3.05 10.74 14.76
4 F 12.20 0.568 1.182 1.454 1.375
C2 5.20 x 3.05 15.86 21.81
C1 3.52 x 3.05 10.74 15.89
5th F 15.24 0.628 1.307 1.415 1.480
C2 5.20 x 3.05 15.86 23.47
C1 3.52 x 1.53 5.39 8.46
RF 18.29 0.681 1.418 1.385 1.571
C2 5.20 x 1.53 7.96 12.50

Lateral Load Page 51


Table : Load Distribution on Frame (South-North)

Frame Load (kips)


Story
Pz
Level
A(1-5) B(4-5) C(1-3) D(4-5) E(1-5)

1st F 1.014 2.45 - 3.61 - 2.45

2nd F 1.103 2.66 - 3.93 - 2.66

3rd F 1.256 3.03 - 4.48 - 3.03

4th F 1.375 3.32 - 4.90 - 3.32

5th F 1.480 3.57 - 5.28 - 3.57

RF 1.571 1.90 - 2.81 - 1.90

Lateral Load Page 52