Professional Documents
Culture Documents
FOR
Chapter 12
Membrane Filtration
Note: If any errors are noted in this solution manual or in the textbook, please notify
Kerry Howe at howe@unm.edu
PROBLEM 12-1
Problem Statement - Discuss the differences between MF and UF membranes. What
impact do these differences have on their use in water treatment?
Solution
1. Differences between MF and UF membranes include the following:
Microfiltration membranes have a larger retention rating (retain smaller particles)
than UF membranes. Microfiltraion membranes have a homogeneous structure
and UF membranes have an asymmetric structure. Different rating systems are
used for each type of membrane. Microfiltration membranes are rated by pore
size and typically have a rating between 0.1 µm and 1 µm. Ultrafiltration
membranes are rated by MWCO and typically have a rating roughly between
1,000 and 500,000 Daltons, which means particle retention capabilities are
between 1 and 30 nm.
2. The difference in retention rating has an impact on the objectives that each
membrane can achieve in water treatment. Microfiltration membranes cannot
reliably remove viruses, but UF membranes with a low enough retention rating can
achieve absolute virus removal.
PROBLEM 12-2
Problem Statement - Discuss the similarities, differences, advantages, and
disadvantages between membrane filtration and rapid granular filtration. This is an
essay question.
Solution
Rapid granular filtration and membrane filtration are both used for the removal of
particles from water. Both can reliably provide safe drinking water when operated
correctly. Both are typically able to achieve product water recovery above 95 percent.
Some of the differences between rapid granular filtration and membrane filtration are
listed in Table 12-4. The filtration rate for rapid granular filtration is about 100 times
greater than the filtration rate typical in membrane filtration. Rapid granular filtration can
operate at a lower pressure and has longer filter run times than membrane filtration, but
Membrane filtration has several advantages over rapid granular filtration. The
coagulation/filtration process of rapid granular filtration is impacted by changes in water
quality and operator error, both of which can adversely impact the water quality of the
filter effluent. Membrane filtration plants require less pre-treatment steps and are less
likely to release improperly treated water to the distribution system when operator errors
occur. The effluent particle concentration from membrane filtration plants is
independent of raw water quality, which is not the case for rapid granular filtration
plants. The lack of coagulation and flocculation facilities can make membrane filtration
easier to operate than rapid granular filtration. The density of filter area, along with the
lack of pretreatment processes often results in a membrane filtration plant that is more
compact than a rapid granular filtration plant would be for treating the same water
source.
The primary advantage of rapid granular filtration over membrane filtration is that rapid
granular filtration has a long and rich operating history, whereas membrane filtration is a
relatively new technology. Because of the long operating history of rapid granular
filtration the process is well understood, and it is possible to design and construct an
efficient rapid granular filtration plant without having to conduct pilot studies. Pilot
studies are necessary for membrane filtration plants to determine flux, backwashing
requirements, and cleaning requirements. Permitting of rapid granular filtration plants is
easier currently than membrane filtration plants, although this situation will likely change
the longer membrane plants are operated successfully and as regulators become more
familiar and comfortable with membrane technology.
PROBLEM 12-4
Problem Statement - Calculate rejection and log removal value for the following
filtration process (to be selected by instructor). Use the number of significant figures
necessary to correctly illustrate the removal being obtained.
A B C D E
Influent concentration (#/mL) 106 6.85 × 105 7.1 × 105 1.65 × 107 2.8 × 106
Effluent concentration (#/mL) 10 136 0.16 65 96
Solution
1. Calculate removal using Eq. 12-3:
Cp 136 mL−1
R =−
1 =−
1 =0.999801
Cf 6.85 × 105 mL−1
2. Calculate the log removal value using Eq. 12-4:
Cf 6.85 × 105 mL−1
= =
LRV log log = −1 3.70
Cp 136 mL
Answers to all problems:
A B C D E
Rejection 0.99999 0.999801 0.99999977 0.99999606 0.9999657
Log rejection value 5.00 3.70 6.65 5.40 4.46
PROBLEM 12-5
Problem Statement - An inside-out hollow-fiber membrane system is operated with a
cross-flow configuration. Each module contains 10,200 fibers that have an inside
diameter of 0.9 mm and a length of 1.75 m. Calculate the following for one module:
a. Feed flow necessary to achieve a cross-flow velocity of 1 m/s at the entrance to
the module.
b. Permeate flow rate if the system maintains an average permeate flux of 80
L/m2 · h.
c. Cross-flow velocity at the exit to the module.
d. Ratio of the cross-flow velocity at the entrance of the module to the flow velocity
toward the membrane surface. Given the magnitude of this ratio, what effect would
you expect cross-flow velocity to have on fouling in cross-flow versus dead-end
filtration?
Solution: Part a
1. Calculate the cross-sectional area of one fiber lumen.
π 2 π
( )
2
a XC = d =0.9 × 10 −3 m 6.362 × 10 −7 m2
=
4 4
2. Calculate feed flow to 1 fiber.
QF,1 =
va XC = (
(1 m/s ) 6.362 × 10−7 m2 = )
6.362 × 10 −7 m3 /s
3. Determine the total flow by multiplying QF,1, the result of the step 2, by the number
of fibers in the module.
QF = (10,200 fibers ) ( 6.362 × 10 −7 m3 /s ) ( 3,600 s/h ) = 23.4 m3 /h
Solution: Part b
1. Calculate the inside surface area of one fiber.
aS = π ( 0.9 × 10 −3 m ) (1.75 m ) =
πdL = 4.948 × 10 −3 m2
3. Determine the total flow by multiplying QF,1, the result of the step 2, by the number
of fibers in the module.
QP 10,200 fibers )( 0.3958 L/h ) (10-3 m3 /L )
(= 4.04 m3 /h
Solution: Part c
1. Calculate the retentate flow by mass balance.
Q=
F QP + QR
PROBLEM 12-6
Instructors Note: The procedures for the solution of this problem are demonstrated in
Examples 12-3, 12-4, and 12-5. The complete solution for Problem A is worked out in
this solution, and the solution to the remaining problems is shown in a table at the end
of the solution.
Problem Statement - Hollow fiber membranes with a membrane area of 23.3 cm2 were
tested in a laboratory and found to have the clean water flow shown in the table
below, at the given temperature and pressure.
Temperature (°C) 16 22 23 25 22
Solution
1. Calculate the flux at a standard temperature of 20°C using Eq. 12-8. Since flow =
4.47 mL/min or 0.268 L/h, J=Q/α or 115 L/m2•h:
Q 4.47 mL/min ( 60 min/h ) (L/1000 mL)
J= = =115.1 L/m2 ×h
A 23.3 cm2 (1 × 10 −4 )
(T )
(115.1 L/m h) (1.03 )( ) 20 C −16 C
M (1.03 )
−T
=JS J= S M
=
2
129.6 L/m2 h
JSP,20=
JS
=
(129.6 L/m =
h)
2
∆P (1 bar ) (105 )
kg/s2 mbar ( 3,600 s/h ) 103 L/m3 ( )=
κM= = 1.89 × 1012 m-1
µJ (1.00 × 10 -3
)(
kg/ms 193.4 L/m h 2
)
4. The membrane resistance coefficient can be calculated using either the actual flow
and pressure (115.1 L/m2·h at 16 °C and 0.67 bar) or the standard flow and
pressure (193.4 L/m2·h at 20 °C and 1 bar) and the results are the same (within the
Flux correction Eq. 12-7 L/m2∙h 127.4 103.6 68.8 138.5 29.9
Specific flux at std temp L/m2∙h∙bar 190.2 129.4 96.9 110.8 142.6
PROBLEM 12-7
Problem Statement - The 0.2-µm polyethersulfone microfiltration membrane shown on
Fig. 12-3 was tested in the laboratory and found to have a clean-water flux of 6500
L/m2 · h at 23º C and 0.69 bar. Assume that the flow through a microfiltration
membrane can be modeled using the Kozeny equation for flow through porous
media (Eq. 11-11 in Chap. 11).
a. Calculate the specific surface area of the membrane assuming a porosity of 0.6,
thickness of 0.10 mm, and Kozeny coefficient of 5.0.
b. What would the theoretical grain diameter be if the membrane were composed of
spherical granular media with the same specific surface area (see Eq. 11-6)?
c. How does the theoretical grain diameter compare to the retention rating for the
membrane? Using concepts of particle retention through granular media from
Chap. 11, what does this comparison suggest about the mechanisms for particle
removal in microfiltration?
d. Using the theoretical grain diameter as the characteristic dimension, calculate the
Reynolds number for flow through a microfiltration membrane. Is the flow laminar
or turbulent?
( ) ( )
0.5
( 0.69 bar ) 105 kg/s2 mbar ( 0.6 )3 103 mm/m
S
= = 4.21× 106 m-1
( −4
)(
( 5 ) 9.326 × 10 kg/ms 1.805 × 10 m/s ( 0.1 mm )
−3
)
Solution: Part b
Rearrange Eq. 11-6 and calculate the theoretical grain diameter, assuming the
membrane is constructed of spherical grains.
6 (1 − ε ) 6 (1 − 0.6 )
d= = 5.70 × 10 −7 m =
= 0.570 µm
S 4.21× 106 m-1
Solution: Part c
The nominal retention rating is given as 0.2 µm and the calculated theoretical grain
diameter is 0.57 µm (see Part b). Theoretically, granular media can strain particles
larger than about 0.15 times the grain diameter (see Fig. 11-8). Thus, a media
composed of spherical grains with a diameter of 0.57 µm would be able to strain
particles 0.086 µm and larger. The similarities between the size of the particles retained
by a granular media (using the calculated theoretical grain size) and the corresponding
nominal retention rating of the microfiltration membrane, means there are similarities
between the flow-pressure relationship in granular media and membrane filters.
Solution: Part d
Homework Solution Manual Page 10 of 29
MWH’s Water Treatment: Principles and Design, 3rd ed. Version 1
Chapter 12 - Membrane Filtration
1. Calculate the Reynolds number.
=
ρvd
Re =
( 997.5 kg/m )(1.805 × 10
3 −3
)(
m/s 5.70 × 10 −7 m )
= 1.10 × 10 −3
−4
µ 9.326 × 10 kg/ms
2. A Reynolds number of 1.10 x 10-3 in porous media corresponds to laminar flow.
Laminar flow means that the head loss through the media varies linearly with flow
velocity, which is commonly observed for membrane filters (if flow were turbulent,
head loss would vary by the square of the velocity). In addition, the Kozeny
equation (which applies to laminar flow) would be an appropriate way to calculate
flow through porous media, assuming the parameters in the equation could be
measured with some degree of accuracy.
PROBLEM 12-8
M (1.03 )
(T )
( 75 L/m h) (1.03 )( )
−T 20 C −17 C
=JS J= S M 2
= 82 L/m2 h
JSP,20=
JS
=
( 82 L/m =
h)
2
96 L/m2 hbar
C
∆P 0.85 bar
PROBLEM 12-9
Problem Statement – Feed water pressure and temperature and permeate flux at a
membrane filtration plant are reported on two dates below. For the plant selected by
your instructor, calculate the specific flux on each date, and indicate whether fouling has
occurred between the first and second dates.
A B C D E
Day 1
Instructors Notes: This problem is similar to Example 12-4. The solution is solved
completely for Problem A and the solution to the remaining problems are shown in a
table at the end of this solution.
Solution
1. Calculate the flux at a standard temperature of 20 °C using Eq. 12-8 for Day 1.
(T )
( 72 L/m h) (1.03 )( ) 20 C − 21 C
M (1.03 )
−T
=JS J= S M 2
= 69.9 L/m2 h
JSP,20=
JS
=
( 69.9 L/m =
h)2
JSP,20=
JS
=
(89.9 L/m =
h) 2
PROBLEM 12-10
Instructors Note: Q = Ja, so Eq. 12-9 can be used to calculate the standard flow rate
the same way standard flux would be calculated.
Problem Statement - A new membrane plant is being designed. Pilot testing indicates
that the membrane will be able to operate at a specific flux of 120 L/m2·h·bar at
20ºC. Water demand projections predict a summer peak-day demand of 90,000
m3/d and a winter peak-day demand of 60,000 m3/d. Historical records indicate
that the source water has a minimum temperature of 3º C in winter and 18º C in
summer.
b. What is the required membrane area, assuming the plant will operate at 0.8
bar, the online production factor is 95 percent, and the recovery is 97
percent?
Solution
1. Flux at standard temperature, JS = 120 L/m2•h•bar x 0.8 bar = 96 L/m2
a. Calculate the flux in summer at a standard temperature of 20°C using Eq.12-8.
=
Jm, Summer =
JS
=
(
96 L/m2 h ) 90.5 L/m2 h
(
1.03 )
( TS − TM ) 1.03(
20
C −18
C )
b. Calculate the flux in winter at a standard temperature of 20°C using Eq. 12-8.
=
Jm, W int er =
JS
=
(
96 L/m2 h ) 58.1 L/m2 h
(
1.03 ( TS −TM )
) 1.03(
20
C − 3
C )
2. Calculate the membrane area for summer conditions using Eq. 12-29.
45,000 m2
Jη (90.5 L/m h) ( 24 h/d)(0.95 )
2
Calculate the membrane area for winter conditions using Eq. 12-29.
=
Qf
a =
( 60,000 m 0.97 )(10 L/m=)
3 3 3
46,700 m2
Jη (58.1 L/m h) ( 24 h/d)(0.95 )
2
PROBLEM 12-11
Problem Statement - An ultrafiltration membrane with a membrane resistance
coefficient of 2.7 × 1012 m–1 is used to filter a 150 mg/L suspension of 0.5-µm latex
particles in a laboratory unstirred dead-end filtration cell. The experiment is
operated at a constant flux of 120 L/m2 · h and temperature of 20º C, and the
membrane has an area of 28.2 cm2. Assume that fouling is due to cake formation,
the particle density is 1050 kg/m3, the cake porosity is 0.38, and the Kozeny
coefficient is 5. Neglecting the backmigration of particles due to diffusion, calculate
and plot the transmembrane pressure and specific flux over the first 90 min of the
filter run.
Solution
The basic solution strategy is to create a spreadsheet with columns for (1) time, (2)
volume of water filtered, (3) cake thickness, (4) cake resistance coefficient, (5) pressure,
and (6) specific flux, and then plot pressure and specific flux as a function of time. The
solution shown below uses time steps of 5 minutes. The calculation steps are shown
for the first time step, and the remaining values are shown in the following table.
1. Convert the given values to SI units.
120 L/m2 h
Flux: =J = 3.33 × 10 −5 m/s
( )
10 L/m ( 3,600 s/h )
3 3
=
Concentration:
150 mg/L 103 L/m3
C = 0.15 kg/m3
( )
106 mg/kg
0.5 µm
Particle diameter: dP= = 5 × 10 −7 m
106 µm/m
2. Calculate the volume of water filtered at 5 minutes.
V = Jat
( )(
3.33 × 10 −5 m/s 2.28 × 10 −3 m2 ( 5 min )( 60 s/min ) =
V= )
2.28 × 10 −5 m3
δ=
CV
=
( 0.15 kg/m )( 2.28 × 10 m ) =
3 −5 3
2.30 × 10 −6 m
C
ρPa (1 − ε ) (1050 kg/m )( 2.28 × 10 m ) (1 − 0.38 )
3 −3 2
κ=
36 κK (1 − ε ) δC 36 ( 5 )(1 − 0.38 ) 2.30 × 10 m
2
=
−6 2
(
= 1.16 × 1010 m-1
)
ε3 dP2 ( 0.38 ) 5 × 10 m ( )
C 3 2
−7
5. Calculate the pressure using Eq. 12-11, noting the κA = 0. The viscosity at 20 °C is
1.0 x 10-3 kg/m·s (see Appendix C-1).
∆P = Jµ ( κM + κC )
= ( 3.33 × 10 −5
)( )(
m/s 1.0 × 10 −3 kg/ms 2.7 × 1012 m-1 + 1.16 × 1010 m-1 )
= 9.04 × 10 4 kg/ms2
= 0.904 bar
6. Calculate the specific flux using Eq. 12-9.
J 120 L/m2 h
J= = = 132.76 L/m2 hbar
∆P 0.904 bar
SP
7. Repeat steps 2 through 6 for the remaining time steps, and plot pressure and
specific flux as a function of time. The results are shown in the following table and
graphs.
0.98
0.96
0.94
Pressure (bar)
0.92
0.90
0.88
0.86
0.84
0.82
0.80
0 10 20 30 40 50 60 70 80 90 100
Time (min)
140
135
130
Specifc flux (L/m2•h•bar)
125
120
115
110
105
100
0 10 20 30 40 50 60 70 80 90 100
Time (min)
∆P = Jµ ( κM + κC ) = JµκM + JµκC
c. The pressure drop through the membrane and cake layer consists of two pressure
terms, one for the membrane and one for the cake layer. The pressure drop
through just the cake layer can be written as follows:
∆PC = JµκC
d. The Kozeny equation (Eq. 11-11) is written as follows:
hL κK µS2 v
=
L ρ W gε 3
e. To eliminate the specific area term in the Kozeny equation, substitute Eq. 11-6 into
Eq. 11-11.
hL κK µ6 (1 − ε ) v
2 2
=
L ρW gε3 dP2
f. Rearrange the equation in step 1e to solve for velocity.
ρW ghL ε3 dP2
v=
36 κK µ (1 − ε ) L
2
g. Substitute the following equalities into the equation developed in step 1f.
1. ∆PC =
ρW ghL (converting pressure to head)
2. v = J (flux is the same as superficial velocity)
3. δC = L (cake thickness is equal to the granular bed depth)
36 κK (1 − ε )2 δC
∆PC = Jµ
ε3 dP2
i. Combining the equations developed in steps 1c and 1h yields the cake resistance
coefficient, which is Eq. 12-12.
36 κ (1 − ε ) δC
2
κC = K 3 2
ε dP
PROBLEM 12-13
Problem Statement - A membrane plant containing 1200 m2 of membrane area
operates at a constant permeate flux of 45 L/m2 · h at a temperature of 15º C and
pressure of 0.25 bar immediately after backwash. The feed water contains 12 mg/L
of suspended solids. After 40 min of operation, the pressure rises to 0.30 bar.
a. Assuming that pressure rise between backwashes is due to formation of a cake
layer, calculate the specific cake resistance.
b. If permeate flux is increased to 50 L/m2 · h, calculate the pressure immediately
after backwash and the pressure after 40 min of operation.
Solution: Part a
1. Convert the flux given in the problem statement to SI units.
45 L/m2 h
=J = 1.25 × 10 −5 m/s
( )
10 L/m ( 3,600 s/h )
3 3
2. Calculate the membrane resistance using Eq. 12-7, assuming that no cake exists
immediately after backwash. From Appendix C-1, µ = 1.14 x 10-3 kg/m·s and ∆P =
0.25 bar = 0.25 x 105 kg/m·s2.
∆P 0.25 × 105 kg/ms2
κM= = = 1.75 × 1012 m-1
µJ ( −3
)( −5
1.14 × 10 kg/ms 1.25 × 10 m/s )
Homework Solution Manual Page 19 of 29
MWH’s Water Treatment: Principles and Design, 3rd ed. Version 1
Chapter 12 - Membrane Filtration
3. Calculate the cake resistance using Eq. 12-11 with only two resistances
(membrane and cake) after 40 minutes of operation.
∆P
J=
µ ( κM + κ C )
V
(
45 L/m2 h 1,200 m2 ( 40 min )
= 36,000 L
)
60 min/h
5. Calculate the specific cake resistance using Eq. 12-14.
α=
κCa
=
( 3.51× 10 11
)(
m-1 1,200 m2 103 mg/g )( )
= 9.75 × 1011 m/g
C
CV (12 mg/L )( 36,000 L )
Solution: Part b
1. Convert the new flux given in the problem statement to SI units.
50 L/m2 h
=J = 1.39 × 10 −5 m/s
( )
10 L/m ( 3,600 s/h )
3 3
2. Calculate the new pressure immediately after backwash, using Eq. 12-6 and the
membrane resistance calculated in Part a step 2.
∆P = JµκM = (1.39 × 10 −5
)( )(
m/s 1.14 × 10 −3 kg/ms 1.75 × 1012 m-1 )
= 2.77 × 10 4 kg/ms2
= 0.277 bar
3. Calculate the volume of water filtered in 40 minutes at the higher flux.
V
(
50 L/m2 h 1,200 m2 ( 40 min )
= 40,000 L
)
60 min/h
4. Calculate the cake resistance coefficient after 40 minutes using Eq. 12-14.
κ= αC
CV
= 9.75 × 1011 m/g
(12 mg/L )( 40,000 L=
) 3.90 × 1011 m-1
C
a 2 3
1,200 m 10 mg/g ( )( )
5. Calculate the pressure after 40 minutes of operation by re-arranging the equation
used in step a3 (Eq. 12-11 with only two resistances; membrane and cake.)
Homework Solution Manual Page 20 of 29
MWH’s Water Treatment: Principles and Design, 3rd ed. Version 1
Chapter 12 - Membrane Filtration
∆P = Jµ ( κM + κC )
= (1.39 × 10 −5
)( )(
m/s 1.14 × 10 −3 kg/ms 1.75 × 1012 + 3.90 × 1011 m-1 )
= 3.40 × 10 4 kg/ms2
= 0.34 bar
PROBLEM 12-14
Instructor’s Notes: The solution is worked out for Problem A and the answers for the
remaining problems are shown at the end of the solution.
Problem Statement - Calculate the membrane fouling index for the following data, for
the data set specified by your instructor.
A. Experimental flat-sheet laboratory filter, membrane area = 30 cm2, initial flux = 3,560
L/m2·h·bar, test pressure = 0.69 bar, test temperature = 23.9 °C.
Permeate Permeate
Time, Volume, Time, Volume,
min mL min mL
0 0 6 458.3
1 108.8 7 506.8
2 199.8 8 552.1
3 277.4 9 594.1
4 345.0 10 634.1
5 404.2 11 670.8
B. Full scale plant operating at constant permeate flow of 15,000 m3/day, temperature
= 20 °C, 5800 m2 of membrane area, pressure each day as shown below. Use Day
0 as the initial flux.
Transmemb. Transmemb. Transmemb.
Time, Pressure, Time, Pressure, Time, Pressure,
Day Bar Day Bar Day Bar
0 0.704
2 0.712 12 0.747 22 0.786
4 0.721 14 0.754 24 0.794
6 0.726 16 0.765 26 0.801
8 0.735 18 0.770 28 0.812
C. Data from a 30-minute filter run in the middle of a day of laboratory testing of
coagulated feed water, membrane area = 23 cm2, initial flux = 238 L/m2·h·bar, test
pressure = 2.07 bar, test temperature = 21.5 °C.
Permeate Permeate Permeate
Time, Volume, Time, Volume, Time, Volume,
min mL min mL min mL
0 2276.64
2 2292.62 12 2370.17 22 2444.76
4 2308.41 14 2385.31 24 2459.35
6 2324.05 16 2400.33 26 2473.88
8 2339.53 18 2415.24 28 2488.26
10 2354.92 20 2430.04
(199.8 mL ) (104
cm 2 /m 2 )
Vsp = 66.6 L/m 2
( 30.0 cm )(10 mL/L )
2 3
2. Calculate the volume filtered in each time increment by subtracting the previous
volume. Results are in the fourth column in the table. For the third row:
=
∆V 199.8 mL − 108.8
= mL 91 mL
3. Divide the volume filtered in each increment by membrane area and time to
determine flux. Then correct for temperature and pressure using Eqs. 12-8 and 12-9
to determine specific flux. Results are in the fifth column in the table. For the third
row,
( 91 mL ) (104 cm 2 /m 2 ) ( 60 min/h )
Jm = 1820 L/m 2 h
( 30 cm2 ) (1 min ) (103 mL/L )
J m (1.03) s m 1820 L/m 2 h (1.03)
T −T 20 − 23.9
6. The results of the above calculations are shown in the table below for all rows of
data.
7. Plot the inverse of the normalized specific flux (1/ J ´sp) as a function of the specific
throughput (Vsp), as shown in the following figure:
3.50
3.00
y = 0.013x + 0.607
2.50 R² = 0.987
1/Jsp
2.00
1.50
1.00
0.50
0.00
0 50 100 150 200 250
Specific throughput (L/m2)
The slope of the line is the membrane fouling index for the filter run is 0.013 L/m2 = 13
m-1.
1.18
1.16
1.14
1.12
R² = 9.98E-01
1.08
1.06
1.04
1.02
1.00
0 10000 20000 30000 40000 50000 60000 70000 80000 90000
Specific throughput (L/m2)
The slope of the line is the membrane fouling index is 2.05 × 10-6 L/m2 = 2.05 × 10-3 m-1.
The slope of the line is the membrane fouling index is 3.102 × 10-3 L/m2 = 3.102 m-1.
Pilot results
Flux (L/m2·h) 80 125 40 80 110
Backwash frequency (min) 30 25 25 22 30
Backwash duration (min) 1.5 0.5 1 2 1
Backwash volume (L) 270 100 200 240 240
Cleaning frequency (day) 45 30 60 30 30
Solution
1. Determine the fraction of time the system is producing permeate using Eq. 12-27:
1440 min/d
tbw (=
1.5 min ) 72 min/d
30 min
tdit = 15 min/d
=tcip
(=
4 h )( 60 min/h )
8 min/d
30 d
= =
V f JAt
(80 L/m h )( 45.0 m ) ( 28.5 min
2 2
=
)
1710 L
f
60 min/h
270 L
=Vbw = 135 L
2 modules
V f − Vbw 1710 L − 135 L
=r = = 0.921
Vf 1710 L
=
Qf
A =
( 60,804 m /d )(10 L/m =
3 3
) 3
34, 385 m 2
J η (80 L/m h ) ( 24 h/d )( 0.921)
2
764
N MOD /=
Rack = 77
10
The system will have 10 skids that each have 80 modules.