Professional Documents
Culture Documents
Transmission Lines
1. Where the earth resistivity is low, no special measures may be re-
quired to obtain tower footing surge impedances of 10 ohms or less;
the tower foundation structures provide the necessary surface "leak-
ance."
2. Where the earth has fairly low resistance, the normal tower
surge impedance may be reduced economically by the use of driven
Counterpoises are recommended (or pro- grounds.
tecting electric power transmission lines 3. Where the resistivity of the earth is high, driven grounds have
against damage from lightning surges where been found to be inadequate and sometimes impractical. For such
cases the remedy now is indicated to be the use of counterpoises.
other methods do not reduce the tower
.4. Counterpoises have been analyzed and classified as follows:
footing surge impedance to the desired (a) those consisting of wires at right angles to the direction of the
level. In this paper a physical explana- line which have the effect only of lowering the surge impedance of
the tower footings; (b) those consisting of wires parallel to the di-
tion of the theory of counterpoises is given rection of the line which have the effect of not only reducing the surge
impedance of the tower footings, but also reducing by mutual
together with an analytical solution of par- coupling the difference of potential between line conductors and the
allel counterpoise problems. O f the 2 tower top. The parallel counterpoise is, therefore, the most effec-
tive type, and methods of calculation are presented for the first
types studied, the parallel counterpoise time that allow analysis of this type of problem.
is shown to be the more effective. 5. Where a cross-wire counterpoise is used in combination with a
parallel counterpoise, its surge impedance should be considered inde-
pendently of the parallel counterpoise and in parallel with the nor-
mal tower footing surge impedance ; their resultant surge impedance
then should be used in the calculations in place of the normal tower
C H A R L E S L. G . FORTESCUE footing surge impedance.
F E L L O W A.I.E.E. E. Pittsbursh, Pa.
6. To obtain the optimum effect with a given length of wire, where
the earth resistivity is not very high, but too high to be taken care of
by driven grounds, it may be advantageous to extend the counter-
C
lONSTANT PROGRESS in an
art can be made only by the development of a work-
poise for only a portion of the distance between towers. Where
the resistivity is very high, however, the counterpoise should be ex-
tended for the whole distance.
7. For a projected line tests may be required to predetermine what
ing theory. It is not necessary that such a theory method of auxiliary grounding will be necessary. For practical
be presented in full perfection. This statement ap- estimating purposes, where a line is to be erected on ground with
plies with particular force to an art such as the pro- high resistivity a parallel counterpoise consisting of 2 or more wires
tection of electric power transmission lines against extending from tower to tower may be considered to make the line
equivalent to one having tower footing surge impedances of 10 ohms,
lightning where confirmation by statistical data on
and the clearances and insulation can be calculated on that basis.
experimental lines takes many years. One of the This value of 10 ohms has yet to receive confirmation, but to the
major problems of protecting transmission lines author's best knowledge it is a fair value to use at present in pro-
against direct strokes of lightning is related inti- jecting a line.
mately to the earth conditions of the right-of-way
over which the line passes. REVIEW OF PAST DEVELOPMENTS
After the direct stroke theory was announced in
1929, many engineers found that poor performance Since this paper is a further extension of the
on many existing lines was attributable mainly to theory of protection of transmission lines against di-
high tower footing resistance. In many cases it was rect lightning strokes and necessarily depends on
found almost impossible to effect sufficient reduction much of the theory already established, a brief re-
of this resistance by means available at that time. view of past developments of this theory seems in
The counterpoise, consisting of cables connected to order.
the line towers and buried in the ground offers a solu- The paper by Fortescue, Atherton, and Cox en-
tion to this difficulty. Counterpoises in general titled "Theoretical and Field Investigations of
are of 2 types: the "crow's foot" consisting of Lightning," presented at the A.I.E.E. winter con-
cables extending radially from the corners of the vention in 1929 (see A.I.E.E. TRANS., V. 48, 1929,
towers; and the parallel type consisting of cables p. 449-68) was among the first papers relating to the
extending from the towers parallel to the line. intensive field investigation of lightning with the
In this paper both the crow's foot and parallel cathode-ray oscillograph started in the summer of
types of counterpoises are analyzed from a theoretical 1928. It presented for the first time before the In-
standpoint, and a mathematical analysis of parallel stitute the conception of the lightning channel as a
counterpoise problems is given. An example illus- highly conducting path, after it had become estab-
trating the method of calculating the protection lished, having a surge impedance of decreasing value
level of a line equipped with a parallel counterpoise in the direction of the point of stroke. In that paper
Full text of a paper recommended for publication by the A.I.E.E. committee on
the theory of the direct stroke as the cause of outages
power transmission and distribution, and scheduled for discussion at the A . I . E . E . on high voltage transmission lines first was advanced,
winter convention, New York, Ν . Y . , Jan. 23-26, 1934. Manuscript submitted
Oct. 23, 1933; released for publication N o v . 13, 1933. Not published in pam-
which theory now has become generally accepted.
phlet form. Based on the ideas presented in that paper, by the
surge impedances given is assumed to be asymtotic portion of the line over High Knob equipped with the
to the effective surge impedance of the tower footing buried longitudinal counterpoise, has not had one
with a very long counterpoise, this would indicate a insulator assembly flashed by lightning. The 2 2 / 1
2
surge impedance of approximately 32 ohms for a buried miles of the line equipped with crow's feet have had
cable extending in both directions from a tower a substantial reduction of flashed insulators, com-
footing, which value seems very low. pared with previous experience. Table I brings out
this comparative performance in more detail.
PRACTICAL EXPERIENCE WITH LINES
INDICATING COUNTERPOISE EFFECTS
Table I—Flashed Insulator Assemblies on a 25-Mile Section
Some 66-kv lines with overhead ground wires of the Wallenpaupack-Siegfried 220-Kv Line
built along the right-of-way of railroads have shown
exceptionally good performance. With the usual Station
Protective
insulation and clearance for such lines, their per- Year Parallel Crow's Foot Gaps
formance cannot be accounted for by the low tower
footing surge impedance alone and must, therefore, 0 2
0 1
be credited to the counterpoise effect due to parallel- 0 2
ing rails. A notable example illustrating this corre- 0 0
usual severity experienced in that region. to draw any definite conclusion from, even though it
During the first 3 lightning seasons of operation, shows a perfect record over 5 lightning seasons, the
that is 1926 to 1928, inclusive, of the Wallenpaupack- performance of this portion of the line when com-
Siegfried 220-kv line of the Pennsylvania Power & pared with the 22V2-niile portion equipped with
Light Company, a considerable number of lightning crow's foot counterpoises is quite significant; and
flashovers was experienced with a disproportionately when considered in the light of experience with other
high percentage of this total concentrated at High existing lines, which appear to owe their high record
Knob, a terrain prominence and the point of highest to parallel counterpoise effects, the result is quite
elevation of the line about 12 miles from Wallen- convincing. Doubtless the performance of the
paupack. High Knob is a hill of solid rock, with a 22V2-mile portion still could be improved by using
thin layer of soil where not entirely exposed. Realiz- more wire in the counterpoises, but from theoretical
ing the necessity of augmenting the protection af- considerations the possible improvement does not
forded by the overhead ground wires, after weighing appear to be sufficient to bring it to a par with the
such experience as they could gather from operating portion of the line over High Knob equipped with
companies and results from lightning research in the parallel counterpoise.
high voltage laboratories and in the field, Mr.
Nicholas Stahl, chief engineer of the Pennsylvania PHYSICAL EXPLANATION OF
Power & Light Company, and Mr. A. E. Silver, THEORY OF PARALLEL COUNTERPOISE
consulting electrical engineer of Electric Bond &
Share Company, recommended the installation of a Theory of counterpoises has been a matter of
buried counterpoise over a distance of 2 / miles at
1
2 speculation for the last 3 or 4 years. The surge
High Knob. This counterpoise, consisting of 2 impedance of the counterpoise in which is included
continuous No. 2/0 B.&S. gauge copper wires, was the effect of distributed inductance, capacitance, and
installed in the spring of 1929, being completed leakance has been recognized as playing an impor-
during May. tant part in its effectiveness. Corona formation
Being encouraged by the initial results from the undoubtedly also plays a large part by increasing
buried counterpoise at High Knob and desirous of the capacitance and leakage and probably reducing
improved performance in the remaining 2 2 / miles 1
2 the inductance. It has been shown that in respect
of the 25 miles total of overhead ground wire sec- of surge admittance a parallel counterpoise with 2
tions of the Wallenpaupack line, the Pennsylvania wires 40 ft apart extending parallel from the towers
Power & Light Company, after further discussions a given distance in both directions is not materially
between their engineers and those of the Westing- different from a crow's foot counterpoise of 4 wires
house company, installed crow's feet at each tower extending radially the same distance at an angle of
throughout the 2 2 / miles. Over 17 / miles of this
l
2
l
2 45° with the direction of the line. To explain the
installation was made early in 1930, and the remain- theory of the parallel counterpoise effect, the over-
ing 5 miles early in 1931. These crow's feet consist head ground wires and the buried counterpoise wires
of buried cables in 4 directions, each extending 50 ft running parallel to the line should be considered as
out from the tower. The portions of the line in effect a transmission system of comparatively
equipped with these 2 types of artificial grounds low surge impedance, the tower being merely the
probably embrace the worst localized exposure to cross connection between the parallel wires of the
lightning on the Wallenpaupack line. system. The conductors must be considered as a
Results to date since the completion of these re- second parallel system insulated from the first sys-
PROSPECTIVE TESTS
χ ι + mVK
+ VK X VK + + VK χ ο
+ VK m Since so much depends on the mutual surge im-
This is equal to pedance between the counterpoise and overhead
lines, tests are under way on a line built near the
(s + i) VK - s ι Trafford laboratory of the Westinghouse company
m + VK ' VK for the purpose of measuring some of these values.
If the surge impedance due to the section of line and It is hoped that by the time this paper is presented
counterpoise on one side of the tower be considered, some data will be available that will be of help in
then to determine ra, 2Z , where Z is the normal deterfllînïng the proper constants to use in applying
the analytical solution to practical problems.
G 0
so that
Zi
Appendix I—The Parallel Counterpoise
m =
2Za
The value of Z is supposed to be known and, un- Θ Π £ of the difficulties of problems of this kind is to provide ade
0
quate nomenclature for all the quantities involved. Since there
less a cross counterpoise is used, is dependent only will be a change of value of all surge currents and electromotive
on the normal tower footing surge impedance ; Z\ is forces every half-period, it will be necessary to distinguish between
the surge impedance of the parallel counterpoise the values of a given current during the intervals. The currents
considering the medium to be homogeneous and air. in the ground wires and counterpoises all will be traveling positively;
in the tower will be both positively and negatively traveling surges
The Κ used in the preceding discussion should be that must be taken into account; while in the lightning channel
the true specific inductive capacity of the soil. This both kinds exist, but only the positively traveling waves need be
will vary over a wide range. The value for pure taken into account. Currents and electromotive forces will be
distilled water is about 70 ; therefore Κ would be ex- designated by giving them a subscript 6" for the lightning channel,
pected to be high for deep alluvial or marshy soil, A and Β for the ground wiie and counterpoise, C for the line, and
Τ for the transmission tower. The half-period is designated by the
possibly 9 or more. For light dry sandy soil, Κ Greek letter Tau ( τ ) and the values occurring during the rth half-
may be low, but moisture is always present in alka- period will be designated by adding the letter r to the subscript,
line earths and salts so that Κ is not expected to be thus ÈAT> È , Ès f Err* etc.
Tr T A positively traveling wave wiö
less than 4. In general, the value of the apparent be designated by placing the sign " -" over the symbol, thus
s
surge impedance is affected not only by Κ but also and a negatively traveling wave by placing the sign in reverse as
" ' " example 2?τγ. A positive traveling wave resulting from re-
by the leakance. Fortunately, where leakance is flection at the beginning of the rth period would be designated îj^
high Κ also is high and one tends to offset the other. I Br, etc., similarly negative traveling waves will be designated
However, for short steep waves resistance and leak- Irr, hr, etc.
ance affect the surge impedance very little, so that There are 3 general terminal conditions to be accounted for.
the proper value of Κ may be obtained by tests 1. Junction of lightning channel, tower, and ground wires.
made on buried counterpoises using a surge generator 2. Junction of tower footing and counterpoise.
3. Junction of tower, channel, and ground wire for negatively traveling waves
giving a steep front wave. Resistance has a ten- in the tower only.
dency to increase the surge impedance while leakance At the beginning of the first half-period no electromotive force is
has a tendency to decrease it, so that they offset each impressed at the junction of the tower footing and counterpoise so
DECEMBER 1 9 3 3 913
that for the potential of the transmitted surge on the ground wire (Ζτ , Z B ß \ f„
and tower in multiple
Zs ( ZsZt ,Z b
-(
Es = — IsiZs A γ,,
Zs + Ζτ 2(Z S + Z ) r ^ 2 J A2 + -7Γ 1
-(
Ès + És = Ès — IsiZs Zs y _ ( ZsZt
Zs + 2 ( Z + Z )
= Ès + î s i Z s — IaiZs — ÎtiZs
S T
(S)
Zab f
= 2Ès — IaiZs — ItiZs En =
Therefore,
Since there are no induced potentials in the tower structure nor
2Èsi — î a\Zs — Ït\Zs = ZaaÎai + ZabÎbi in the channel, at the junction of the tower channel and ground wire
transmitted potential is
or
Ετι + Èt2 = (Ιτ2 — ίτι)Ζτ
ü ~ ( Z S
A . Z A
\ Î
A
Λ . Ζ Α Β
Τ J _ Z S
T
\ 2~ ~2~ )
1
2~ 1
"2 By the principle of continuity of current at a junction point, the
current flowing toward this point — ( ί τ ι + Ιτ2) must be equal to
— Ïa\Zs — ItiZs = Ζτίτι the current flowing from it (1a2 — /s2) or
Èsi — ΤΓ Îai +
(î+î) but since there are no induced potentials in the channel, the poten-
tial at the junction
Therefore
or
( Ζτ
ύ +
, Ζββ\
- ^ - ) Ι β
t
ι ÎTÎ =
Ζ s +
^ S
Ζ τ
(Ia2 + ίτΐ) + Zs-7} +
Γ~7Γ
Ζτ
ίτΐ
Therefore
By eliminating In, these are reduced to
(8)
Ετι — Ζτίτι Zab ψ , (Z , Z \ ^
T
(2)
ß j B
Êt2
Ετι — —Ζτίτι — —ΖχΙ Bl
At the beginning of the second half-period there are 2 sets of equa- Its - (/V2 + ÎAZ) +
Zs +
tions to solve in which portions of Î 2 designated by 1'A2 and I" ai A
and portions of Ib2 designated by ί' B2 and Î"b2 are involved inde- Its = (7T2 — Ibz)
pendently. They are
ZsZt f , f , Z •2
Etz
f λ T
ZxZt -ζ7ϊτγ ( Ι Τ 2 + Ι Α 3 )
^ Z s T Z t
-G
1
, Z \ f Ζ AB f, τ
0
A A
2{Zs + Ζτ)
Étz - ΙτζΖτ — (It2 — Ibz)Zt
(3)
The equations after the first may be expressed in the general form
(10)
Ετι = ^/" È (r-l)
T = ^ΙΓ-Îat + ( Ζτ
2
, Zbb\
-t- 2
f
JiBr
\2(Z S + Z) ^ 2 ) \ 2 ^ 2 ) \ 2 )
To obtain the value of m
T
Ζ AB
2 Z 0 = 400 ohms
Y a b = - •
ZsZt
I
K 2(Z S + Z) T •)(f+¥)-(¥)" Z = 6 0 1og |g = 298
1 e
549
2£ s Z s (13)
Iai =
Zs + Z r Zs + Z r Zs ~h Z r Therefore
/ n = ^ßi ZX 298 q 7 _
W
^ 2 Z ^ =
2 T 7 = L 3 7 5
£ri =
Zr^n
£ri = —
Ζτίτι — ~~ ZtIbx
Taking S = 1
(i + s) VK - s ι _ 3 ι = 0 4 4 4
Zs
ÎA2 — FA A £n + YabEti m + VK ' VK 3.375 · 2 · ·
Zs + £ r
Zs Zn = 60 l o g e g = 312
7ß2 = FAB Ετι + YbbEti
Z S + Z T
400
Z = 30 loge = 149
2 2
2.87
/r2 =
Zs^Tt { Î T l + / a 2 ) +
Z s ^ Z r / n (14)
498
Z = 0.444 Χ 60 loge ^ = 0.444 X 94.4 = 42
/Γ2
1 2
= —
(^Γ1 - Ibi)
Zr 2
559
ÈT* = - ^ f f ^ tfn + Iai) + ^ + Z y
Ιτι Zu = 0.60 loge = 149
46.9
£T2 = —
ΖτΪτι — Ζτ{Ιτι — Ib2) 461
Z3 2 — 0.444 X 60 l o g e ^ = 0.444 X 114.5 = 5 0 . 9
I Ar = YaA-
v
Zs+
É {r-l) + Y AB ÈT(r-l)
Ζτ' T
From these the following are obtained:
74.5 X 108.5
/ Γ
' =
- Zs^VZt { 1 t
^
+
H R ) +
ZTVZt Î T { r
~ l )
I (15) Zbb —
183.0
44.2
Ζ ab —
21
Ζ AC =
74.5
Ιττ — — (^Γ(γ-Ι) — I Br)
Zbc =
25.45
Zaa
Zs 2
78 Zs •+- Z r 3
Εττ == — Ζτίττ — Zr(/r(r-l) —
^ßr) 2
Z = 1
(16) ^ = 22.1
T
915
DECEMBER 1 9 3 3
Zs = 200 ohms
Zs — Ζτ _ 1 Zs I Ai = -195 - 22.4 = -217.4
Zs + Ζ τ 2 Ζ s + Ζτ =
IBA = + 2 8 . 6 + 237.5 +266.1
ZT(ZS — ΖΤ)
Z = 100 ohms = 33.33 ohms
T
Zs + Ζτ In = - | (161.2 - 217.4) = 37.5
Ζτ _|_ Zßfl
72.1 ohms I AS = - 5 9 . 3 - 5.0 = 64.3
2 ^ 2
let = + 8 . 7 + 52.8 = +61.5
^~ = 10.5 ohms
ITS = - f- (488 - 64.3) = 10.35
Product of first 2 of above 3 quantities is 111 .33 X 72.1 = 8,025.0
Square of last = 110.2 / Γ 6 = -(37.5 - 61.5) = 24.0
Ε τ& = 1,035
Difference 7,914.8
Ε TB -2,400
79 1
YAA = 7914.8
J£h. = 0.0091
-1,600
Zs + Ζτ
111.33
Ybb = = 0.0141
7914.8
I At = - 1 4 . 5 - 1.4 = -15.9
10.5
= -0.00133
Y a b
7914.8 Î* B = + 2 . 1 + 14.6 = 16.7
For the calculations an arbitrary value È = 1,000,000 volts will
3
Ire = - f (12 - 15.9) 2.6
2E S
ÉT7
I M = - 3 9 . 4 + 6,560 = +6,520.6
Zs £ τ
= -108
ÎT2 = - Ξ ( - 2 2 2 - 349.5) = 381 Zs + Ζτ
3
/ Γ 2 = -(4,647 - 6,520.6) = 1,873.6 IAI = -0.98 - 0.081 -1.07
IM -16 ΪΒ6 17
Ι = -(381 - 703.3) = 322.3
η
Iai = -4 HR = 4
ETZ = 16,850
I AS -1.0 Ibs 1.0
ETZ = -32,230
The tabulated results of carrying out the additions to obtain
ZS £ I A, I b , È , È , È , and È — È are given in Table II. It may be
= -21,480
A B C A C
Table II
Values Obtained A r e Per 1,000 Kv of Stroke Potential
Amperes Kilovolts
*C A-E
E C
0 0 0 0 0 0 0
0.1 303 -44 46 4 21 25
0.2 571 563 101 36 57 44
0.3 720 1,241 139 70 85 54
0.4 847 1,946 173 104 113 60
0.5 969 2,557 207 138 140 67
0.6 1,088 3,369 241 172 167 74
0.7 1,207 4,082 274 206 194 80
0.8 1,326 4,750 307 238 220 87
0.9 1,445 5,463 340 272 246 94
1.0 1,566 6,225 375 308 275 100 10 12 14 16
NUMBER OF INSULATOR UNITS
1.1 1,349 7,087 359 341 281 79
1.2
1.3
1,174
1,130
7,025
6,987
332
323
336
332
266
262
65
61
Fig. 2. Characteristics of standard 10-in. diam. in-
1.4 1,100 6,929 317 330 258 59 sulator units with 5 A in. spacing; IV2 X 40-Msec
3
1.5
1.6
1,097
1,084
6,866
6,791
315
312
327
323
257
254
59
58
positive wave
1.7 1,072 6,720 308 319 251 57
Corrected to the following atmospheric conditions: absolute
1.8 1,068 6.649 306 316 249 57
humidity, 6.5 grains per cu ft; relative density, 1.0
Among the many points in and near New York City which may be visited by those attending the winter convention of the
Institute, January 23-26, 1934, is the Roseland switching station of the Public Service Electric and Gas Company of New
Jersey. The 220-kv section is shown above on the left, and 132-kv section on the right