Switchgear Interlocks in Substation For Different Bus
Switchgear Interlocks in Substation For Different Bus
GOPALA KRISHNA
ADE/400KV/APTRANSCO
INTERLOCKS
WHY
INTERLOCKS
ARE
REQUIRED
1. PREVENTS HUMAN MISTAKES
EARTH SWITCH
1. OPERATED ONLY IF THE ISOLATORS ON BOTH THE SIDES ARE OPEN.
2. EARTH SWITCHES WHICH CAN EARTH AN INCOMING LINE DIRECTLY OR
THROUGH A CB CAN BE OPERATED IF AND ONLY IF THE LINE IS DEAD.
INTERLOCKS
INTERLOCKS
SINGLE BUS & TRANSFER BUS SYSTEM
T/F-1 T/F-2
TRANSFER BUS
FEEDER1 FEEDER2
INTERLOCKS LINE BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 89-A/BAY ISOLATOR OPERATION:
1. 52 CB/BAY IN OPEN CONDITION.
89-AE
2. 89AE/BAY EARTH SWITCH OPEN CONDITION.
52-CB 3. 89LE1/BAY EARTH SWITCH OPEN CONDITION.
4. BB189E BUSEARTH SWITCH OPEN CONDITION.
89-LE1
OPEN
BB189E
89-L OPEN
52 CB/BAY
OPERATION
89-AE/BAY
OPEN & 89A/BAY
OPEN
52 CB
89-L OPEN
89-AE OPERATION
89-LE1
OPEN & 89L
89-LE1
OPEN
89-L 89-A
OPERATION
OPEN
& 89-AE
89-LE2 89-L
FEEDER OR
ICT OR
REACTOR
89-A 89-L 89-AE
89-LE1
OPEN
89-L 89-A
OPERATION
OPEN
& 89-LE1
89-LE2 89-L
FEEDER OR
ICT OR
REACTOR
89-A 89-L 89-LE1
OPTD
U/V RELAY
89-L
OPEN
OPERATION
89-C
& 89-LE2
89-LE1
RESET
86-GA
89-L
RESET
REMOTE
86-GB
& OPERATION
52-CB
OPEN
89-A
89-L OPEN
89-L
LOCAL
89-AE CLOSE & OPERATION
52-CB
89-AE
89-CE 89-AE
52-CB
89-LE1
TRANSFER BUS COUPLER
FOR 89-C ISOLATOR OPERATION:
89-L 1. NO OTHER ISOLATOR IS CLOSED TO TRANSFER BUS C
2. BB389E EARTH SWITCH OPEN CONDITION.
3. 89LE2 EARTH SWITCH OPEN CONDITION.
FEEDER OR 89-LE2 4. 52 TBC CB IN OPEN CONDITION.
ICT OR OR
REACTOR 1. 52 CB IN CLOSED POSITION.
2. 89-A ISOLATOR CLOSED CONDITION.
3. 89-L ISOLATOR CLOSED POSITION.
4. 89-A/TBC BAY BUS-A ISOLATOR CLOSED POSITION.
5. 89-C/TBC BAY BUS-C ISOLATOR CLOSED POSITION.
6. NO OTHER ISOLATOR IS CLOSED TO TRANSFER BUS C
7. ADDITIONAL INTERLOCK PROTECTION TRANSFERRED
MAY ALSO PUT THROUGH PROTECTION TRANSFER
SWITCH.
INTERLOCKS LINE BAY
89-C/ LINE-1 89-C/ LINE-2 89-C/ ICT-1 89-C/ ICT-2
FUTURE BAYS
+ VE
NO OTHER
52CB/TBC 89LE2 BB389E ISOLATOR
89-C/BAY
CLOSED TO
BUSBAR-C
NO OTHER
TTS ISOLATOR
N T CLOSED TO
.
89-A/TBC 89C/TBC 52CB/BAY 89A/BAY 89L/BAY BUSBAR-C
OPEN
89-CE / TBC
OPEN
89-CE / TBC
89-C/TBC
89-C/TBC
RESET
REMOTE
86-GB/TBC
& OPERATION
52-CB/TBC
RESET
96-BB/TBC
CLOSE
89-CE / TBC
89-AE
89-CE 89-AE
52-CB
89-LE1
TRANSFER BUS COUPLER
FOR BB189E EARTH SWITCH OPERATION:
89-L 1. ALL BAYS BUS-A ISOLATORS OPEN CONDITION
OPEN
89-A/BAY1
FEEDER OR 89-LE2 OPEN
89-A/BAY2
OPERATION
ICT OR & BB189E
UP TO NO OF BAYS
REACTOR
OPEN
89-A/BAYn
UP TO NO OF BAYS
OPEN OPEN OPEN INTER
LOCK
CONTACTOR
INTERLOCKS BUS BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C
89-C 89-A
89-A
52-CB
89-AE
89-CE 89-AE
52-CB
89-LE1
TRANSFER BUS COUPLER
FOR BB389E EARTH SWITCH OPERATION:
89-L 1. ALL BAYS BUS-C ISOLATORS OPEN CONDITION
OPEN
89-C/BAY1
FEEDER OR 89-LE2 OPEN
89-C/BAY2
OPERATION
ICT OR & BB389E
UP TO NO OF BAYS
REACTOR
OPEN
89-C/BAYn
UP TO NO OF BAYS
OPEN OPEN OPEN INTER
LOCK
CONTACTOR
INTERLOCKS
INTERLOCKS
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
T/F-1 T/F-2
BUS-1
BUS COUPLER
BUS-2
TRANSFER BUS
COUPLER
BAY3 BAY4 BAY5
BAY1 BAY2 TRANSFER BUS BAY6 BAY7 BAY8
CLOSE
52-CB 89-B/BAY
CLOSE
52CB/BAY OPERATION
CLOSE OR BB189E & 89-A/BAY
89-LE1
89-A/BC
& OPEN
CLOSE
89-B/BC
89-L CLOSE
52CB/TBC
FEEDER OR
OPEN OPEN OPEN OPEN OPEN INTER
ICT OR LOCK
REACTOR 89-B/BAY 52CB/BAY 89-B/BC 52 CB/BC 89-A/BC
CONTACTOR
OF BAY
CLOSE CLOSE CLOSE CLOSE CLOSE
INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A) FOR 89-B/BAY ISOLATOR OPERATION:
OPEN
BB289E 52CB/BAY
MAIN BUS-2(B) OPEN
89-LE1/BAY
BB389E &
OPEN
TRANSFER BUS( C ) 89-AE/BAY
OPEN
89-AE 89-A 89-B 89-C 89-A/BAY
CLOSE
52-CB 89-A/BAY
CLOSE
52CB/BAY OPERATION
CLOSE OR BB289E & 89-B/BAY
89-LE1
89-A/BC
& OPEN
CLOSE
89-B/BC
89-L CLOSE
52CB/TBC
FEEDER OR
OPEN OPEN OPEN OPEN OPEN INTER
ICT OR LOCK
REACTOR 89-A/BC 52CB/BAY 89-B/BC 52 CB/BC 89-A/BAY
CONTACTOR
OF BAY
CLOSE CLOSE CLOSE CLOSE CLOSE
INTERLOCKS FEEDER BAY
OPEN OPERATION
52CB/TBC 89-C/BAY
OPEN TTS
TRANSFER OR
89-LE2/BAY
CLOSE
BB389E
OPEN & 89-C/TBC
CLOSE
52CB/BAY
CLOSE
NO OTHER CLOSE
ISOLATOR
89L/BAY &
CLOSED TO
BUSBAR-C NO OTHER CLOSE
CLOSE ISOLATOR
89-B/TBC
89-B/BAY
CLOSE & CLOSED TO
BUSBAR-C
OR
CLOSE
89-A/TBC FOR 89-C/BAY ISOLATOR OPERATION:
89-A/BAY
CLOSE &
NO OTHER
52CB/TBC 89LE2 BB389E ISOLATOR
89-C/BAY
CLOSED TO
BUSBAR-C
.
89-A/TBC 89A/BAY 89C/TBC 52CB/BAY 89L/BAY BUSBAR-C
FEEDER OR
ICT OR
REACTOR 52 CB/BAY ICT HV TE 89-AE/BAY 89-LE1/BAY 89-LE2/BAY 89-L
OF BAY
OPEN OPEN OPEN OPEN OPEN INTER
(FOR ICT ONLY) LOCK
CONTACTOR
INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
52-CB
OPEN
89-L/BAY
89-LE1 OPEN
89-A/BAY & OPERATION 89-AE/BAY
89-LE2
52-CB
OPEN
89-L/BAY
89-LE1 OPEN
89-A/BAY & OPERATION 89-LE1/BAY
89-LE2
52-CB
89-L/BAY OPEN
89-C/BAY OPEN
89-LE1 & OPERATION 1-89LE2
OPTD
LINE U/V
(FOR LINE)
89-L OPEN
LV-89T (FOR ICT)
89-LE2
89-LE1
RESET
86-GA
89-L
RESET
REMOTE
86-GB
& OPERATION
52-CB/BAY
89-LE2
RESET
96-BB
FEEDER OR
ICT OR
REACTOR 86-GA 86-GB 96-BB 52-CB/BAY
OF BAY
RESET RESET RESET INTER
LOCK
CONTACTOR
INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
FOR 52 CB /BAYCIRCUIT BREAKER FOR LOCAL OPERATION:
1. 89-A ISOLATOR OPEN CONDITION.
2. 89-L ISOLATOR OPEN CONDITION.
52-CB 3. 89-AE TBC EARTH SWITCH CLOSED CONDITION.
4. 89-LE1 EARTH SWITCH CLOSED CONDITION.
89-LE1 OPEN
89-A
89-L OPEN
89-L
LOCAL
89-AE CLOSE & OPERATION
52-CB/BAY
89-LE2
CLOSE
89-LE1
FEEDER OR
ICT OR
REACTOR 89A 89L 89-AE 89-LE1 52-CB/BAY
OF BAY
OPEN OPEN CLOSE CLOSE INTER
LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
FOR 89-A / TBC ISOLATOR OPERATION:
1. 52 CB / TBC IN OPEN CONDITION.
2. 89AE / TBC EARTH SWITCH OPEN CONDITION.
52-CB
3. 89CE / TBC EARTH SWITCH OPEN CONDITION.
4. BB189E BUSEARTH SWITCH OPEN CONDITION.
5. 89-B/TBC ISOLATOR OPEN CONDITION
89-CE OPEN
BB189E
TRANSFER OPEN
52 CB / TBC
BUS
OPEN OPERATION
COUPLER 89-AE / TBC
OPEN
& 89A / TBC
89-CE / TBC
89-B / TBC OPEN
89-CE / TBC
89-A / TBC OPEN
OPEN
89-CE BB389E
OPEN
TRANSFER 52 CB / TBC
OPERATION
BUS 89-AE / TBC
OPEN & 89C / TBC
COUPLER OPEN
89-CE / TBC
89-CE
OPEN
TRANSFER 89-A / TBC
BUS OPEN OPERATION
COUPLER
89-B / TBC
OPEN
& 89-AE / TBC
89-C/TBC
89-CE
OPEN
TRANSFER 89-A / TBC
BUS OPEN OPERATION
COUPLER
89-B / TBC
OPEN
& 89-CE / TBC
89-C/TBC
RESET
89-CE 86-GA/TBC
TRANSFER RESET REMOTE
BUS 86-GB/TBC
& OPERATION
52-CB/TBC
COUPLER RESET
96-BB/TBC
OPEN
89-BE / BC
OPEN
89-BE / BC
BUS COUPLER
OPEN
89-A / TBC
OPERATION
OPEN
& 89-AE / BC
89-B/TBC
BUS COUPLER
OPEN
89-A / BC
OPERATION
OPEN
& 89-BE / BC
89-B/BC
RESET
86-GA/BC
RESET REMOTE
86-GB/BC
& OPERATION
52-CB/BC
RESET
96-BB/BC
BUS COUPLER
OPEN
89-A/BC
OPEN
89-B/BC LOCAL
89-AE/BC CLOSE
& OPERATION
52-CB / BC
CLOSE
89-BE/BC
89-AE 89-A 89-B 89-C 89-AE 89-A 89-B 89-C 89-A 89-B
FEEDER OR
ICT OR
REACTOR
OF BAY
INTERLOCKS BUS EARTH SWITCH
BB189E BB289E BB389E
OPEN OPEN OPEN
89-A/BAY1 89-B/BAY1 89-C/BAY1
OPEN OPEN OPEN
89-A/BAY2 89-B/BAY2 89-C/BAY2
OPERATION OPERATION OPERATION
UP TO NO OF BAYS
& BB189E UP TO NO OF BAYS
& BB289E UP TO NO OF BAYS
& BB389E
OPEN OPEN OPEN
89-A/BAYn 89-B/BAYn 89-C/BAYn
UP TO NO OF BAYS
OPEN OPEN OPEN INTER
LOCK
CONTACTOR
89-B /BAY1 89-B/BAY2 89-B / BAY n BB289E FOR BUS EARTH SWITCH
OPERATION, ALL ISOLATORS
OPEN OPEN
UP TO NO OF BAYS
OPEN INTER
CONNECTED TO CONCERNED
LOCK BUS ARE TO BE OPENED.
CONTACTOR
89-C /BAY1 89-C/BAY2 89-C / BAY n BB389E
UP TO NO OF BAYS
OPEN OPEN OPEN INTER
LOCK
CONTACTOR
INTERLOCKS
INTERLOCKS
I-CONFIGUARATION
FEEDER1 FEEDER3 FEEDER5 FEEDER7 FEEDER9 FEEDER11
BAY10
BAY13
BAY16
BAY4
BAY7
BAY1
BAY11
BAY14
BAY17
BAY8
BAY2
BAY5
BAY12
BAY18
BAY15
BAY9
BAY3
BAY6
BUS-2
BAY15
BAY13
BAY3
BAY9
BAY1
BAY7
DIA1 DIA3 DIA5
BUS-1
BUS-2
BAY18
BAY10
BAY12
BAY6
BAY16
BAY4
1-89 3-89
1-89E 3-89E
1-52CB 3-52CB
1-89AE 3-89AE
1-89A 3-89A
1-89RE 1-89R 2-89A 2-89B
SHUNT
REACTOR
. 1-89LE 3-89TE
1-PH NEUTRAL
UUU
GROUNDING
REACTOR
LINE 1
T/F-1
INTERLOCKS BAY 1
BB1-89E BUS-1
1-89
1-89E
1-52CB
FOR 1-89 ISOLATOR OPERATION:
OPEN
1-89AE BB189E
OPEN
1-89AE
1-89A OPEN & OPERATION 1-89
1-89E
1-89RE 1-89R OPEN
1-52CB
LINE SHUNT REACTOR
1-89L
UUU
. 1-89LE
OPEN OPEN OPEN OPEN INTER
UUU
LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1
1-89
1-89E
1-52CB
FOR 1-89E ISOLATOR OPERATION:
OPEN
1-89AE 1-89A
1-89A
& OPERATION1-89E
OPEN
1-89RE 1-89R 1-89
LINE SHUNT REACTOR
1-89L
UUU
. 1-89LE
OPEN OPEN INTER
UUU
LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1
1-89
1-89E
1-52CB
FOR 1-89A ISOLATOR OPERATION:
OPEN
1-89AE
1-89AE
1-89A
1-89E
OPEN
& OPERATION1-89A
1-89RE 1-89R OPEN
1-52CB
LINE SHUNT REACTOR
1-89L
UUU
. 1-89LE
OPEN OPEN OPEN INTER
UUU
LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1
1-89
1-89E
1-52CB
FOR 1-89AE EARTH SWITCH OPERATION:
OPEN
1-89AE 1-89A
1-89A
& OPERATION 1-89AE
OPEN
1-89RE 1-89R 1-89
LINE SHUNT REACTOR
1-89L
UUU
. 1-89LE
OPEN OPEN INTER
UUU
LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1
FOR 1-89L ISOLATOR OPERATION:
IL
1-52CB CLOSE
1-89R
PUSH OR
DC
INTERLOCK OPEN
2-52CB
1-89AE BYPASS
OPEN & OPERATION 1-89L
PB 1-89LE
OPEN
1-89A 1-52CB
1-89RE 1-89R DC INTERLOCK
BYPASS PB
IL
LINE SHUNT REACTOR
1-89L
UUU
PUSH
1-89R 2-52 CB 1-89LE 1-52 CB 1-89L
. 1-89LE
CLOSE OPEN OPEN OPEN INTER
UUU
LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1
1-89
1-89E
1-52CB
FOR 1-89LE EARTH SWITCH OPERATION:
OPEN
1-89AE 1-89L
1-89A
& OPERATION 1-89LE
LINE U/V RELAY OPTD
1-89RE 1-89R
LINE SHUNT REACTOR
1-89L
UUU
LINE U/V
RELAY 1-89L 1-89LE
. 1-89LE
OPTD OPEN INTER
UUU
LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1
1-89
1-89E
FOR 1-89R ISOLATOR OPERATION:
1-52CB
OPEN
1-89RE
OPEN
2-52CB
1-89AE OPEN & OPERATION 1-89L
1-89L
OPEN
1-89A 1-52CB
1-89RE 1-89R
IL
LINE SHUNT REACTOR
1-89L
UUU
. 1-89LE
OPEN OPEN OPEN OPEN INTER
UUU
LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1
1-89
1-89E
1-52CB
FOR 1-89RE EARTH SWITCH OPERATION:
1-89AE
OPEN OPERATION
1-89R 1-89RE
1-89A
1-89RE 1-89R
LINE SHUNT REACTOR
1-89L
UUU
1-89R 1-89RE
. 1-89LE
OPEN INTER
UUU
LOCK
CONTACTOR
LINE 1
INTERLOCKS 1-52 CB BAY1
BB1-89E BUS-1
LOCAL
1-89E
1-89 CLOSE
1-89E LOCAL
& OPERATION
1-52 CB
CLOSE
1-89AE
1-52CB
RESET
REMOTE
1-89L 86-GB/BAY1
& OPERATION
1-52 CB
UUU
RESET
96-BB/BAY1
. 1-89LE
UUU
2-89A 2-89B
OPEN
2-52 CB
OPEN OPERATION
289-AE & 2-89A
OPEN
289-BE
2-89A 2-89B
OPEN
2-52 CB
OPEN OPERATION
289-AE & 2-89B
OPEN
289-BE
2-89A 2-89B
OPEN
289-A
OPERATION
289-B
OPEN & 2-89AE
2-89A 2-89B
OPEN
289-A
OPERATION
289-B
OPEN & 2-89BE
CLOSE
2-89AE
REMOTE
LOCK
RESET CONTACTOR
86-GA/BAY2
RESET
REMOTE
86-GB/BAY2
& OPERATION
2-52 CB
RESET
96-BB/BAY2
FOR HALF DIA ONLY
3-89
3-89E
3-52CB
3-89
3-89E
3-52CB
& OPERATION3-89E
OPEN
3-89
3-89T
3-89
3-89E
3-52CB
3-89A OPEN
3-89AE
OPEN OPERATION
3-89E
OPEN
& 3-89A
3-52CB
3-89T
3-89
3-89E
3-52CB
& OPERATION3-89AE
OPEN
3-89
3-89T
3-89
3-89E
3-52CB
3-89
3-89E
3-52CB
& OPERATION3-89TE
OPEN
LV89T
3-89T
CLOSE
3-89AE
3-52CB
REMOTE
LOCK
RESET CONTACTOR
86-GA/BAY3
RESET
3-89T REMOTE
86-GB/BAY3
& OPERATION
3-52 CB
RESET
96-BB/BAY3
3-89TE
7-89/ DIA3
OPEN
&
OPERATION
BB189E
9-89/ DIA3
OPEN
& BB289E
UP TO NO OF DIAS
UP TO NO OF DIAS
OPEN
OPEN DIA N
DIA N
UP TO NO OF DIAS
OPEN OPEN OPEN OPEN INTER
LOCK
CONTACTOR
UP TO NO OF BAYS
OPEN OPEN OPEN OPEN INTER
LOCK
CONTACTOR
ISOLATOR S.NO
ISOLATOR EQUIPMENT-1 EQUIPMENT-2 EQUIPMENT-3 EQUIPMENT-4
INTERLOCKS OPEN/CLOSE INTERLOCKS REQUIRED FOR CONCERNED ISOLATOR / EARTH SWITCH OPEN OR CLOSE
BAY - 1
1 1 - 89 ISO BB189 E O 189 AE O 189 E O 152 CB O
2 1 – 89 E ES 189 A O 189 O -- - -- -
3 1 – 89 A ISO 189 AE O 189 E O 152 CB O -- -
4 1 – 89 AE ES 189 A O 189 O -- - -- -
5 1 – 89 L ISO 189 LE O 152 CB O 252 CB O -- -
6 1 – 89 LE ES 189 L O UV RELAY A -- - -- -
BAY - 2
NOTE: All Earth Switches in
the Bay are towards Circuit 7 2 – 89 A ISO 289 BE O 289 AE O 252 CB O -- -
Breaker side only. The Line 8 2 – 89 AE ES 289 B O 289 A O -- - -- -
and Transformer
9 2 – 89 B ISO 289 BE O 289 AE O 252 CB O -- -
Earth Switches are towards
Line & Transformer. 10 2 – 89 BE ES 289 B O 289 A O -- - -- -
O: OPEN BAY - 3
C: CLOSE 11 3 – 89 ISO BB289 E O 389 AE O 389 E O 352 CB O
A: ACTED
12 3 – 89 E ES 389 A O 389 O -- - -- -
BB189E : BUSBAR-1 EARTH SWITCH .
13 3 – 89 A ISO 389 AE O 389 E O 352 CB O -- -
BB289E : BUSBAR-2EARTH SWITCH .
UV RELAY: UNDER VOLTAGE RELAY. 14 3 – 89 AE ES 389 A O 389 O -- - -- -
15 3 – 89 T ISO LV89 E2 O 389 TE O 252 CB O 352 CB O
16 3 – 89 TE ES 389 T O LV89 T O -- - -- -
BB189E
OPEN ISOLATOR & CB INTERLOCKS OPEN
BB289E
OPEN OPEN
1-89AE
OPEN & OPERATION 1-89 1-89E
CLOSE LOCAL
CLOSE 3-89
OPERATION
& OPEN
3-89AE
1-89E
OPEN 1-89AE
CLOSE & 1-52CB OPEN
3-89E
1-52CB 3-52CB
CLOSE LOCAL
1-52CB OPEN 2-89AE CLOSE OPEN 3-52CB
OPEN 2-89BE
CLOSE & 2-52CB OPEN
1-89AE & OPERATION 1-89A 3-89A
OPERATION
& 3-89AE
OPEN CLOSE OPEN
1-89E 3-89E
LOCAL 3-89E
CLOSE
3-89AE
CLOSE & 3-52CB
OPEN OPEN
1-52CB 3-52CB
RESET OPEN
OPEN 86GR-A
1-89LE & OPERATION 1-89L RESET
REMOTE
CLOSE
OPERATION 3-89TE
OPEN 86GR-B & 1-52CB 3-89T & OPEN
2-52CB
2-52CB RESET
96BB OPEN
LV89E2
OPEN
1-89 OPERATION RESET OPEN
3-89
OPEN & 1-89E 86GR-A
REMOTE
CLOSE
3-89E
OPERATION
& OPEN
1-89A
86GR-B
RESET & 2-52CB 3-89A
OPEN
1-89 OPERATION OPEN
3-89
1-89A
OPEN & 1-89AE
86GR-A
RESET
REMOTE 3-89AE
OPERATION
& OPEN
RESET CLOSE 3-89A
1-89L
OPEN 86GR-B & OPEN
OPERATION RESET 3-52CB 3-89T
U/V RLY
ACTED & 1-89LE 96BB 3-89TE
OPERATION
& OPEN
LV89T
OPEN
2-89A
OPEN 2-89B
OPEN & OPERATION
2-89AE
OPEN
2-52CB 2-52CB
OPEN OPEN
2-89AE & OPERATION 2-89A
OPEN 2-89AE & OPERATION
2-89A 2-89B
2-89BE
OPEN
2-89B
OPEN & OPERATION
2-89BE 2-89BE
OPEN