Prof. P. K. Das
Professor
Mechanical Engineering Department
IIT Kharagpur
Feed water
Riser Water + chemical
Boiler Drum as
Water, steam,
an Input-
foam, sludge, Output System
floating
impurities
Schematic of a boiler
drum – relative positions
of different components
Priming is the sudden gust of liquid slugs in the steam flow due to rapid
change in steaming rate, increase in liquid level, improper circulation etc.
It not only makes the steam dirty but can also create problems like flow
fluctuation, water hammer, thermal stress.
Foamnig occurs due to the saponification in presence of oil, grease,
floating impurities. It restricts the release of the bubbles as the liquid has
a high surface tension. During bubble rapture droplets are formed which
are also carried away by steam
Apart from mechanical cleaning of steam chemical correction is also
applied.
Tri-sodium phosphate or tannin is injected to induce precipitation of the
dissolved salts in the form of sludge.
Liquid excursion by
vapor drag
3. Low cost
Test Facility
Scheme for
automatic surface
blow down
Possibility of
heat recovery
from surface
blow down
stream
Example
Boiler specifications:-
367.7 kW(500 bhp), 7840.9 kg/h (17,250 PPH)
Operating pressure 1.55 Mpa (225 PSIG)
Boiler Water temperature 476K (397 F)
Boiler is operated with 75% firing rate with 80% efficiency i.e. 5863.6 kg/h
(12,900 PPH) with 4 597.3 kWh (1,56,86,720 Btu) heat input.
Using ON/OFF feed water system (recovery volume of 3% low water capacity
(235 kg) + 2% over capacity(157 kg) = 5% water recovery capacity (392 kg) )
Feed water cycle = 392/5863 hr = 4.01 min
Feed water is supplied at 355.2 K with 261.4 kg/min.
Resultant impact
Total feed water delivery time = 392/ 261.4=1.5 min, temperature rise= 120 K
1.Sub-cooling of water occurs due to mixing of drum water with feed water.
2.Steaming pressure falls from 1.55 Mpa (@ 476 K) to 1.34 Mpa (@ 469.7 K) i.e.
13% drop in steaming pressure
On-off control
Modulating Control
Conductivity
probe for level
measurement
Possible actions:
•Start or stop a valve
•Open or close a valve Two point
•Sound an alarm conductivit
•Open or close a relay y probe
Capacitance method of
level measurement
Can be conveniently
used for on-off control
•Manual control
•Single element control
•Two element control
•Three element control
• Can not adjust pressure or load disturbance of the feed water flow
• Can not eliminate the phasing interaction between the feed water
flow and drum level as only a slow process of drum level is
controlled
• The second issue can lead to a high subcooling of the drum water
on a large increase of steam demand due to excessive feed water
entry