RW1
Soil data
SELECTED GRANULAR MATERIAL
Ø= 30
g s= 20 gw= 10 kN / m3
g
C= 0 ss
= 10.00
gc= 25 kN / m3
Ø 0.52 radians
delta = 20.00
tan(delt 0.364
Allowable soil pressure, q a = 450 kN/m2
k a= 0.33
k p = ( 1+sinØ )/( 1- sinØ ) = 3.00
A = 0 .5 bd c − c −
2
s
{ √1 1
bd c
4M
2
2
}= 637.14 mm 2
gc= 25 kN / m3
Ø 0.52 radians
delta = 20.00
tan(delt 0.364
k a= 0.33
k p = ( 1+sinØ )/( 1- sinØ ) = 3.00
2
}= 967.04 mm 2
967 mm 2
p *f / 4 * b /As,prov.=
2
Using f 14 c/c 159.184 mm
Use f 14 c/c 150 mm, for vertical reinforcements in both sides.
- The area of horizontal reinforcement shall not be less than one-half of that of the vertical reinforcement
Article 7.2.5.3.1
A s horz = 483.52
p *f / 4 * b /As,prov.=
2
Using f 10 c/c 162.433 mm
Use f 10 c/c 160.00 mm
Design of concrete retaining wall
RW1
Soil data
SELECTED GRANULAR MATERIAL
Ø= 30
g s= 20 g w= 10 kN / m3
C= 0 g ss = 10.00
gc= 25 kN / m3
Ø 0.52 radians
delta = 20.00
tan(delt 0.364
Allowable soil pressure, q a = 300 kN/m2
k a= 0.33
k p = ( 1+sinØ )/( 1- sinØ ) = 3.00
A =0 .5 bd c − c −
2
s
{ √ 1 1
858
2
}= 857.60 mm 2
mm 2
p *f / 4 * b /As,prov.=
2
Using f 12 c/c 131.876 mm
Use f 12 c/c 130 mm, for vertical reinforcements in both sides.
- The area of horizontal reinforcement shall not be less than one-half of that of the vertical reinforcement
Article 7.2.5.3.1
A s horz = 428.80