Professional Documents
Culture Documents
net/publication/225674995
CITATIONS READS
4 664
4 authors, including:
Hyung-Suk Han
Defense agency for technology and quslity
65 PUBLICATIONS 260 CITATIONS
SEE PROFILE
All content following this page was uploaded by Hyung-Suk Han on 06 February 2015.
(Manuscript Received August 16, 2006; Revised April 25, 2007; Accepted April 26, 2007)
--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Abstract
The main sources of the refrigerant-induced noise can be classified 2 types according to its characteristics. One is
due to the cyclic characteristics such as quality, velocity of the refrigerant, pressure drop and mass flow rate. The other
is due to the structural characteristics such as distributed path pipe layout, distributor and expansion device. In this
paper, the effects of cycle characteristics on the noise of multi-type system air-conditioner are investigated
experimentally. In the indoor unit of multi-type air-conditioner, the variation of noise is examined when the in-flowing
and out-flowing refrigerant to the indoor unit are 2-phase state according to its cycle control. And several factors are
recommended in order to reduce the refrigerant-induced noise of the air-conditioner.
Keywords: Refrigerant-induced noise; Quality; Mass flow rate; Electric Expansion Valve (EEV)
--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
In this paper, the mechanism of refrigerant-induced The flow pattern of 2-phase flow is generally
noise is discussed. And refrigerant-induced noise is dependent on the mass flux of the gas and liquid.
investigated experimentally according to the cyclic Baker(1954) suggested the flow pattern map related
characteristics of system air-conditioner. Since the to mass flux for the horizontal flow and Hewitt and
refrigerant-induced noise depends on its velocity at Roberts(1969) suggested for the vertical flow. In this
cooling mode, the variation of refrigerant-induced paper, Baker map and Hewitt map will be used for
noise with different quality is also discussed at expectation of flow pattern in a pipe. Figure 2 shows
cooling mode. Since the phase of the refrigerant at those maps for the variation of flow pattern with
condenser-outlet will be 2-phase as mass flow rate of quality at the evaporator inlet where the pressure is
the refrigerant, the variation of noise with mass flow 0.68 Mpa, inner diameter of pipe is 4.95mm, and
rate is discussed at heating mode. mass flow rate is 60~120 kg/hr.
In Fig. 2, m’ is mass flow rate of the refrigerant, x
2. Mechanism of refrigerant-induced noise is quality, A is cross sectional area of the tube, Gg is
mass flux of the gas, Gl is mass flux of the liquid, g ,
Figure 1 shows the Molier diagram (p-h) of general
l , water are the density of the gas, liquid and water, μg,
refrigeration cycle. The refrigerant flowing out from
μl, μwater are the viscosity of the gas, liquid and water,
the condenser is sub-cooled liquid, and its phase
and water, are the surface tension of the water and
changes from liquid to 2-phase when passing through
liquid. The relations between parameters are as
the expansion device. In addition, as shown in Fig. 1,
follows;
the pressure drop of “ⱁP” occurs and the vapor
fraction in the refrigerant grows up while this 1000.0
refrigerant is passing through the pipe between x=0.99 x=0.9 x=0.8 x=0.7
x=0.6
expansion valve and evaporator. Because of these x=0.5
x=0.4
100.0 x=0.3
reasons, the refrigerant flowing into the evaporator x=0.2
x=0.1
becomes 2-phase state with high velocity. The energy
Gg /(kg/m 2 s)
Annular
Wavy
loss occurs at these positions because of high velocity 10.0
1000.0 "Wispy"
x=0.1
Gg2 / g (kg/s 2 m)
Annular annular
100.0
G l 2 / l (kg/s 2 m)
Fig. 1. Molier diagram (p-h diagram) for general air- Fig. 2. Flow pattern map for horizontal and vertical flow at
conditioner. evaporator inlet.
1114 Weui Bong Jeong et al. / Journal of Mechanical Science and Technology 21(2007) 1112~1119
m'x
Gg =
A
m '(1 − x)
Gl =
A
1
§ ρ ρl · 2
λ =¨ g ¸
© ρ air ρ water ¹
1
σ § μ ρ water 2 · 3
ψ = water ¨¨ l ¸
σ © μ water ρl 2 ¸¹
Heating Cooling
Indoor Outdoor Indoor Outdoor Indoor Outdoor Indoor Outdoor Indoor Outdoor
DB(Ⳅ) 20.0 7.0 27.0 24.0 27.0 35.0 21.0 21.0 32.0 43.0
RH(%) 58.4 86.7 25.1 55.3 46.0 24.4 52.8 52.8 45.5 24.4
G
(a) Cooling (b) Heating
Fig. 4. Schematic diagram of the test setup with multi-type air-conditioner (TC: Thermocouple).
quality is 0.14 at cooling low temperature, 0.16 at the low pressure line and discharge valve in the
cooling standard and 0.19 at cooling overload compressor will be closed, which makes the mass
condition. Figure 5 represents the sound pressure flow rate in a pipe decrease suddenly. And the
level measured at these different temperature con- refrigerant is compressed and discharge valve is
ditions for the indoor unit “2” for multi type air opened when the PWM valve is off, which causes the
conditioner. In Fig. 5, it can be known that the noise increasing of mass flow rate. Because of this cycle
increased at high frequency over 1000 Hz when the variation, the control of open-step for EEV(Electric
quality increases. And over-all sound pressure level Expansion Valve) is very important in order to control
also grows up according to the increasing of the mass flow rate approximately. Figure 7 shows the
quality. As referred to previous section, it can be Molier(p-h) diagram of this cycle at heating mode,
verified that the variation of noise with quality is and Table 2 shows the temperature of the heat
dependent on the velocity of refrigerant when the exchanger for the indoor unit while the PWM valve is
flow pattern of the refrigerant is not slug or churn on and off . At the heating mode, indoor unit becomes
flow. Because the mass flow rate of the indoor unit is condenser and the refrigerant at condenser outlet
at least 60 kg/hr and the quality at evaporator inlet is becomes sub-cooled liquid. Monitoring its state with
over 0.14 for the cooling mode, the flow pattern at the sight-glass and cycle temperature, it is observed that
evaporator inlet should be annular as shown in Fig. 2. the state of refrigerant becomes 2-phase according to
EEV open-step and control of PWM valve. It means
3.2 Cycle characteristics at heating mode that the sub-cooled temperature becomes 0 degree.
Therefore, the point “A” in Fig. 7 moved to right and
A digital scroll compressor manufactured by left direction according to EEV open step. And point
Corperland Co. is installed for 5 HP system air- “A” in Fig. 7 moved from “1” to “3” during on-off
conditioner and it controls the cycle with on-off control of PWM valve. It is monitored that the
control of PWM valve. The on-off control of PWM refrigerant-induced noise grows up when EEV open-
valve is shown in Fig. 6. When the PWM valve is on, step is 300step and PWM valve becomes on, at which
the refrigerant in the compressed room bypasses to point “A” is moving through “1” in Fig. 7(b).
1116 Weui Bong Jeong et al. / Journal of Mechanical Science and Technology 21(2007) 1112~1119
45 Loading
Cooling Standard
35 Cooling Overload
30
Unloading
25
20 0 10 20 30 40 50 60 70
15
10 Time[sec]
5
0 Fig. 6. PWM valve control logic(Loading : PWM valve = On,
0 2000 4000 6000 8000 10000 Unloading : PWM valve = Off).
Frequency[Hz]
45 Cooling Standard
40 Cooling Low
Sound Pressure Level[dBA]
35 Cooling Overload
30
25
20
15 (a) EEV open step = 200step (b) EEV open step = 300step
10
5 Fig. 7. Molier diagram of 5HP system air conditioner at
0
heating mode.
0 2000 4000 6000 8000 10000
Frequency[Hz]
3.3 Mass flow rate at heating mode
(b) 1/3 octave noise at unloading condition
Figure 8 shows the refrigerant-induced noise as
different EEV open-step and PWM valve control.
47.0
When the EEV step is over 300 steps, the level of the
46.5
sound pressure increases as shown in Fig. 8(a), and
Sound Pressure Level[dBA]
46.0
45.5
45.0
45.6 the difference of sound level is dominant at high
45.0
44.5
frequency range from 1 kHz to 4 kHz, at which the
44.0 43.9 human ear is very sensitive. Figure 8(b) shows the
43.5 sound pressure variation as time while the PWM
43.0
42.5
valve is on and off. It can be found that the sound
42.0 pressure level increases suddenly when the PWM
0.13 0.15 0.17 0.19 0.21
valve is off (loading condition). For different EEV
Frequency[Hz]
open-step and PWM valve control, the refrigerant
(c) Over-all noise level at loading condition as different state is monitored by sight-glass. When the EEV open
quality step is 300steps, the refrigerant state which goes out
Fig. 5. Sound pressure level of 4 way cassette at cooling from the condenser is not sub-cooled liquid during the
mode as different temperature conditions. PWM valve is closed (loading condition). It can be
Weui Bong Jeong et al. / Journal of Mechanical Science and Technology 21(2007) 1112~1119 1117
200 step
45.0 226 step
40.0 306 step
35.0 348 step
20.0
15.0
10.0
5.0
0.0
-5.0
0 2000 4000 6000 8000 10000 12000
Frequency[Hz]
Fig. 8. Sound pressure as different EEV step and PWM valve control.
180
induced noise at this time. The variation of the mass
160 flow rate as EEV open-step was calculated by Jang
140 and Kim(2005), which is given in Fig. 9. In Fig 9, the
Mass Flow Rate [kg/hr]
100.0 x=0.99
ditioner with lower noise, the following factors are
x=0.9 x=0.8
x=0.7 recommended.
x=0.6
x=0.5
x=0.4 (1) Quality at the evaporator inlet should be mi-
x=0.3
Wavy
Annular
x=0.2
nimized.
10.0 (2) Sub-cooling should be maximized at all of the
x=0.1
operating conditions.
Gg /(kg/m s)
2
Stratified
(3) Velocity at evaporator inlet should be
Slug
minimized and the flow pattern must not be slug-flow.
1.0
x=0.01 (4) EEV open-step should be controlled approxi-
Bubbly mately not to be 2-phase for the refrigerant at
m' = 60kg/hr Plug
m' = 90kg/hr condenser outlet.
m' = 120kg/hr
0.1
10.0 100.0 1000.0 10000.0
2
References
G l (kg/m s)
(a) Horizontal flow Arora, C. P., 2000, “Refrigeration and Air Condi-
tioning,” McGraw-Hill.
Cjoi, J. M. and Kim, Y. C., 2005, “Performance of
10000.0
x=0.9
x=0.8 Short Tube Orifices Using R-410A Near the Critical
x=0.7
x=0.6
x=0.5
Region,” Korean Journal of Air-conditioning and Refri-
1000.0 "Wispy"
x=0.4
annular geration Engineers, Vol. 17, No. 12, pp. 1106~1112.
x=0.3
Annular
x=0.2
Gian Piero Celata, 1997, “Experimental Evaluation of
100.0 the Onset of Subcooled Flow Boiling at High Liquid
G g2 / g (kg/s2 m)
Internal Fluid Flow,” 2003 Spring Conference Journal Whalley, P. B., 1999, “Two Phase Flow and Heat
of KSNVE, pp. 911~916. Transfer,” Oxford University Press.
Tatsumi KANNON, 1997, “Study on Noise Caused Willam S. Janna, 1993, “Design of Fluid Thermal
by Slug Flow through a Capillary Tube,” JSME, Vol. 63, Systems,” PWS-Kent Publishing Company.
No. 611, pp. 2392~2397. Yang, C. Y., 2001, “Flow Pattern of Air-Water and
Tomomi UMEDA, 1993, “Reduction of Noise Caused Two-phase R-134a in Small Circular Tubes,” Interna-
by Gas-Liquid Two-Phase Refrigerant Flow through an tional Journal of Multiphase Flow, Vol. 27, pp. 1163~
Expansion Valve,” JSME, Vol. 59, No. 557, pp. 243~248. 1177.