ATLANTA ELECTRICALS PVT. LTD.

TRANSFORMER TEST REPORT Page : 1 OF 5


Customer : ABP Induction System Pvt. Ltd W.O.No. : AET 929 Sr.No. : 929/4570

Customer :- ABP Induction System Pvt. Ltd


P.O.No. :- 12-13/PO/000614 DT: 31-10-12
Rating :- 3600 KVA, 33.00/ (0.660 x 2 ) kV
Vector Group :- Dy11d0
Current :- H.V. Current :-62.98 Amp L.V. Current :- 3149.20 Amp (660V x 2 LV) (1574.60 Amp. X 2 LV)
Connection :- H.V. Side :- Delta L.V. Side :- Delta & Star
W.O.No. :- AET 929
Sr. No. :- 929/4570
Cooling :- ONAN
0 0
Temp Rise :- Oil :- 50 C Winding :- 55 C
Tappings :- + 10 % to - 10% In Step Of 5 % On HV for HV Variation - OCTC.
Date Of Testing : 29.12.2012
Ref. Standard :- IS : 2026 / 1977

ROUTINE TEST

Sr. No. ROUTINE TEST Page No.


1 Ratio Test. 2
2 Magnetic Balance Test. 2
3 Vector Group Test. 3
4 Winding Resistance Test. 3
5 Insulation Resistance Test. 3
6 Saperate Source (High Voltage) Withstand Test. 3
7 Induced Over Voltage test. 4
8 No Load Loss And Magnetizing Current Measurement. 4
9 Dielectric Strength Test On Transformer Oil. 4
10 Load Loss & Impedance Voltage Measurement. 4
11 Results & Calculation Sheet. 5
12 %Imp for individual L.V. w.r.t. H.V. 5

Total Pages : 5

Tested By : Witnessed By :

Chirag Makavana, Mr. Kinjal Patel,


Engr., (Testing), Engineer - Design & Quality,
AEPL, V.U. Nagar. ABP I. S. P. L.