You are on page 1of 7

SCHEDULE

SYMBOL DESCRIPTION QUANTITY

FLUORESCENT LAMP FITTING (2x36)


31
OR LED (1 X 18W)
FL-29 FL-30
W1 W1 W1 W1 FLUORESCENT LAMP FITTING (1x36)
10
OR LED (1 X12W)

LOP SAFETY EYE


LAMP FITTING WITH 18W, CFL LAMP 00
WASH &
SC-02 (CEILING MOUNTED)
SHOWER
STORAGE FL-31 WALL BRACKET LAMP (IP-65 FOR OUTDOOR) 00
FOR PACL

CHEMICAL ELE.PANEL
400 WIDE DRAIN
SC-03 20W EMERGENCY FLUORESCENT WITH
E 02
FL-01 FL-04 FL-08 FL-12 FL-16 FL-20 FL-24 2 2 3 BUILT IN BATTERIES
STORAGE D1 E
FOR PACL CEILING FAN 00

FL-32 FL-33 FL-34 FL-35


13A SOCKET OUTLET WITH SWITCH (TWIN) 07
+178.000
SC-05
FL-05 FL-09 FL-13 FL-17 FL-21 FL-25 R FAN REGULATOR 00
STORAGE
FOR LIME AS
"n" GANG SWITCH REQUIRED
SD E
SC-06
FL-36 FL-37

NEUTRALIZATION POND
DISTRIBUTION BOARD 01

CABLE DUCT-300 X 300


FL-06 FL-10 FL-14 FL-18 FL-22 FL-26 CHLORINE
STORAGE AREA FL-38
DB
STORAGE CHEMICAL BUILDING
FL-39 FL-40
FOR LIME 40A, 2P MCB
(10kA)
4 2
SC-07
FL-02 FL-07 FL-11 FL-15 FL-19 FL-23 FL-27
RCCB
EXHAUST FAN 40A, 2P
SC-04 FL-41 30mA
HARD STANDING
UNLOADING BAY DB RAMP Lighting circuit
SC-01 10A (2C+E)1.5 sq.mm PVC
D2
3 4 4 4 1 4 4 4 FL-1 TO FL-15
LOP
Lighting circuit
10A (2C+E)1.5 sq.mm PVC
FL-03 W1 FL-28 D2 FL-16 TO FL-28
FD1 Lighting circuit
6A (2C+E)1.5 sq.mm PVC
RAMP
FL-29 TO FL-35
Lighting circuit
6A (2C+E)1.5 sq.mm PVC
FL-36 TO FL-41
GROUND FLOOR PLAN
10A Spare

13A, Sockets in ring cct.


20A (2C+1) 2.5 sq.mm PVC
SC-1 TO SC-4
13A, Sockets in ring cct.
20A (2C+1) 2.5 sq.mm PVC
SC-5 TO SC-7
20A Spare

FOR INFORMATION ONLY


CLIENT NATIONAL WATER SUPPLY AND DRAINAGE BOARD REV DESCRIPTION DATE SIGN DESIGNED ENG. DHANUSHKA APPROVED IN PRINCIPLE SUBJECT TO THE REV NO DATE
GALLE ROAD, RATHMALANA, SRI LANKA.
WILGAMUWA WATER SUPPLY PROJECT DRAWN JAYASUNDARA
CONDITION THAT THE DESIGN & BUILD -3 2018-06-18
CONTRACTOR IS RESPONSIBLE FOR THE
DESIGN DRAWING TITLE CHECKED ENG. WANW CONFORMITY OF THE DESIGN WITH SHEET SIZE SCALE
YUNICA ENGINEERS & CONSULTANT FUNCTIONAL & STRUCTURAL REQUIREMENTS. A3
NO:157/2, MUIBUN TOWERS DHARMAPALA MAWATHA ,COLOMBO - 07 1:75

CONTRACTOR DRG NO
CML-MTD CONSTRUCTION LTD
NO:155, DHARMAPALA MAWATHA,COLOMBO - 07
CHEMICAL BUILDING
NWS&DB/CP/WIL/103/ME/14
CONTRACT NO
P&P/D&B/LBF/WILGAMUWA/2014 SMALL POWER PROJECT MANAGER PROJECT DIRECTOR
CML - MTD CONSTRUCTION NWS&DB
UP
400 WIDE DRAIN
+68 level
Ø32-NRV
10 OVER FLOW
EXTEND BACK TO
TANK
Ø32-PVC
+68 level A +150 level 11

Ø32
Ø50-PVC
UP

8
DUTY
LOP
STANDBY DUTY +68 level
PRE-LIME
DOSING UNIT
OVER FLOW
4 9
EXTEND BACK
over flow line is TO TANK
beneath 3 B 12
LINE TO BE
2450 1500 SLOPED DOWN
PT
2900
EMF 2
Ø50-
PVC EMF
STANDBY 7
2150 15 13
6

UP
+68 level PT +68 level
Ø32-
PVC
A 3 2 15 10
+150 level 5 Ø32-PVC

1
Ø50-PVC Ø32
4 1
1 Ø32-NRV
DUTY
OVER FLOW
14
5 EXTEND BACK TO
TANK
OVER FLOW DRAIN DRAIN
STANDBY
EXTEND BACK B
PACL-STANDBY
TO TANK Ø32-PVC
8
POST-LIME
DOSING UNIT 10 11
6 Ø32-PVC +68 level
PACL-DUTY
7 14 POST-LIME-STANDBY

9 12 13 Ø32-NRV POST-LIME-DUTY
EMF UP 32Ø SERVICE
WATER
+68 level PT Ø32-PVC

CABLE DUCT-300 X 300


UP
CHEMICAL ELE.PANEL

LOP

FOR INFORMATION ONLY


CLIENT NATIONAL WATER SUPPLY AND DRAINAGE BOARD REV DESCRIPTION DATE SIGN DESIGNED ENG. DHANUSHKA APPROVED IN PRINCIPLE SUBJECT TO THE REV NO DATE
GALLE ROAD, RATHMALANA, SRI LANKA.
WILGAMUWA WATER SUPPLY PROJECT 0 1st SUBMISSION 2017-11-02 DRAWN JAYASUNDARA
CONDITION THAT THE DESIGN & BUILD -2 2018-06-18
CONTRACTOR IS RESPONSIBLE FOR THE
DESIGN DRAWING TITLE -1 REVISED AS PER NWS&DB COMMENTS 2017-11-30 CHECKED ENG. WANW CONFORMITY OF THE DESIGN WITH SHEET SIZE SCALE
YUNICA ENGINEERS & CONSULTANT FUNCTIONAL & STRUCTURAL REQUIREMENTS.
NO:157/2, MUIBUN TOWERS DHARMAPALA MAWATHA ,COLOMBO - 07 -2 REVISED AS PER NWS&DB COMMENTS 2018-06-18 A3 1:30
CONTRACTOR CHEMICAL HOUSE BUILDING DRG NO
CML-MTD CONSTRUCTION LTD
NO:155, DHARMAPALA MAWATHA,COLOMBO - 07 CHEMICAL DOSING PUMPING SYSTEM ...................................................... ..............................................
NWS & DB /CP/WIL/103/ME/15
CONTRACT NO
P&P/D&B/LBF/WILGAMUWA/2014 Sheet-1 PROJECT MANAGER
CML - MTD CONSTRUCTION
PROJECT DIRECTOR
NWS&DB
CHEMICAL DOSING SYSTEM
AIR RELEASE
561 QUANTITY QUANTITY
POSITION DESCRIPTION -LIME -PACL
PG

1 Ø50 TRUE UNION PVC BALL VALVE 8 6

2 Ø50 PVC UNION COUPLING 2 2


PULSATION
DAMPER 3 5 LITER CAPACITY INLINE CALIBRATION PIPE 2 1

PS
4 Ø50 X 20 -PVC CLAMP SADDLE OR REDUCED FAUCETS TEE 4 2
PRESSURE

700
FOR FIXING SUCTION PRESSURE SWITCH
LOADING

468
VALVE 5 DIAPHRAGM DOSING PUMP 4 2

300

68
FLOOR
150

LEVEL 6 Ø32 PVC UNION COUPLING 8 4


780 7 DELIVERY SIDE PULSATION DAMPER 4 2
1916

VIEW ON A - A 8
Ø32 X 20 -PVC CLAMP SADDLE OR REDUCED FAUCETS TEE FOR
FIXING DELIVERY PRESSURE GAUGE-FOR USE IN ADJUSTING PLV
4 2

9 PRESSURE LOADING VALVE (PLV) 4 2

10 Ø32TRUE UNION PVC BALL VALVE 12 7

11 PRESSURE RELIEF VALVE (OVER FLOW VALVE) 4 2


Ø32 X 20 -PVC CLAMP SADDLE OR REDUCED FAUCETS TEE FOR
12 2 1
FIXING PRESSURE TRANSMITTER-COMMON DELIVERY
13 ELECTRO-MAGNETIC FLOW METER-Ø25 2 1
PG+PS
14 NRV-Ø32 4 2

15 Y-STRAINER Ø50 2 2

PS
700

OVERFLOW VALVE
300

FLOOR
150

150

LEVEL NOTE:

1175 1. DIAPHRAGM PUMPS HAVE INBUILT NON -RETURN VALVES

VIEW ON B - B 2. OVER FLOW VALVE, PRESSURE LOADING VALVE AND PULSATION DAMPER SHALL BE SELECTED TO SUIT
MANUFACTURER RECOMMENDATIONS AND FIXING SHALL BE DONE WITH NECESSARY FITTINGS
3. EMF CONNECTION DETAILS ARE TO BE OBTAINED FROM MANUFACTURER.
4. ALL THE PIPES TO BE SUPPORTED WITH CONCRETE COLUMNS ENCASED IN PVC PIPES
5. DRAIN PIPE WAS DN100 AND OVER FLOW PIPE WAS DN40 IN P&ID, BUT DUE TO THE COMMERCIAL
UN-AVAILABILITY OF SUCH SIZES WITH THE TANKS, THEY WERE CHANGED TO DN50 & DN32 RESPECTIVELY.
NOTE:
6. PUMP SHAPE MAY BE CHANGED WITH THE MANUFACTURER
1. SPACES BETWEEN FITTINGS CAN BE CHANGED TO SUIT THE 7. IN P&ID FOR ALUM ONLY ONE PULSATION DAMPER WAS GIVEN. BUT BY FOLLOWING MANUFACTURER
CONDITIONS AT SITE. RECOMMENDATIONS TWO PD WERE INTRODUCED.
2. SUPPORTS HAS NOT BEEN SHOWN FOR CLARITY.
3. INSTRUMENTATION-REFER P&ID

FOR INFORMATION ONLY


CLIENT NATIONAL WATER SUPPLY AND DRAINAGE BOARD REV DESCRIPTION DATE SIGN DESIGNED ENG. DHANUSHKA APPROVED IN PRINCIPLE SUBJECT TO THE REV NO DATE
GALLE ROAD, RATHMALANA, SRI LANKA.
WILGAMUWA WATER SUPPLY PROJECT DRAWN JAYASUNDARA
CONDITION THAT THE DESIGN & BUILD -2 2018-06-18
CONTRACTOR IS RESPONSIBLE FOR THE
DESIGN DRAWING TITLE CHECKED ENG. WANW CONFORMITY OF THE DESIGN WITH SHEET SIZE SCALE
YUNICA ENGINEERS & CONSULTANT FUNCTIONAL & STRUCTURAL REQUIREMENTS.
NO:157/2, MUIBUN TOWERS DHARMAPALA MAWATHA ,COLOMBO - 07
A3 1:25
CONTRACTOR CHEMICAL HOUSE BUILDING DRG NO
CML-MTD CONSTRUCTION LTD
NO:155, DHARMAPALA MAWATHA,COLOMBO - 07 CHEMICAL DOSING PUMPING SYSTEM NWS & DB /CP/WIL/103/ME/16
CONTRACT NO
P&P/D&B/LBF/WILGAMUWA/2014 Sheet-2 PROJECT MANAGER
CML - MTD CONSTRUCTION
PROJECT DIRECTOR
NWS&DB
LEVEL SENSOR

1505
1900

AGITATOR

570
SS304 PLATE
10mm THICK

SS304 C-CHANNEL
100x50x6
Ø12 HOLES FOR
M10 BOLTS

- PACL TANKS -

A LIME TANKS A

SCALE

PLAN
SCALE 1:25
FOR INFORMATION ONLY
CLIENT NATIONAL WATER SUPPLY AND DRAINAGE BOARD REV DESCRIPTION DATE SIGN DESIGNED ENG. DHANUSHKA APPROVED IN PRINCIPLE SUBJECT TO THE REV NO DATE
GALLE ROAD, RATHMALANA, SRI LANKA.
WILGAMUWA WATER SUPPLY PROJECT 0 1ST SUBMISSION 2017-11-16 DRAWN JAYASUNDARA
CONDITION THAT THE DESIGN & BUILD -2 2018-06-18
CONTRACTOR IS RESPONSIBLE FOR THE
DESIGN DRAWING TITLE -1 REVISED AS PER NWS&DB COMMENTS 2017-11-30 CHECKED ENG. WANW CONFORMITY OF THE DESIGN WITH SHEET SIZE SCALE
YUNICA ENGINEERS & CONSULTANT FUNCTIONAL & STRUCTURAL REQUIREMENTS.
NO:157/2, MUIBUN TOWERS DHARMAPALA MAWATHA ,COLOMBO - 07 -2 REVISED AS PER NWS&DB COMMENTS 2018-06-18 A3 AS SHOWN
CONTRACTOR CHEMICAL HOUSE BUILDING DRG NO
CML-MTD CONSTRUCTION LTD
NO:155, DHARMAPALA MAWATHA,COLOMBO - 07 DUST EXTRACTION HOPPER & ...................................................... ..............................................
NWS & DB /CP/WIL/103/ME/17
CONTRACT NO
P&P/D&B/LBF/WILGAMUWA/2014 DISSOLVING BASKET Sheet - 3 PROJECT MANAGER
CML - MTD CONSTRUCTION
PROJECT DIRECTOR
NWS&DB
1 2 3 4 5

10475
2015 2010 3725 2725

Ø140 PVC-YPE250

PIPE TO SUPPORTED
TO ROOF

Ø140 PVC-YPE250
20 Ø STOP TAP 20 Ø STOP TAP
AXIAL FAN SERVICE WATER
SERVICE WATER
SPRAY NOZLE PACL DISSOLVING
BASCKET
LEVEL SENSOR AGITATOR
1962 1567

SS304 C-CHANNEL
100x50x6
2550

2550
LIME PACL
TANKS TANKS

SECTION A-A NOTE: JOINTS TO BE WELDED

FOR INFORMATION ONLY


CLIENT NATIONAL WATER SUPPLY AND DRAINAGE BOARD REV DESCRIPTION DATE SIGN DESIGNED ENG. DHANUSHKA APPROVED IN PRINCIPLE SUBJECT TO THE REV NO DATE
GALLE ROAD, RATHMALANA, SRI LANKA.
WILGAMUWA WATER SUPPLY PROJECT DRAWN JAYASUNDARA
CONDITION THAT THE DESIGN & BUILD -2 2018-06-18
CONTRACTOR IS RESPONSIBLE FOR THE
DESIGN DRAWING TITLE CHECKED ENG. WANW CONFORMITY OF THE DESIGN WITH SHEET SIZE SCALE
YUNICA ENGINEERS & CONSULTANT FUNCTIONAL & STRUCTURAL REQUIREMENTS.
NO:157/2, MUIBUN TOWERS DHARMAPALA MAWATHA ,COLOMBO - 07
A3 AS SHOWN
CONTRACTOR CHEMICAL HOUSE BUILDING DRG NO
CML-MTD CONSTRUCTION LTD
NO:155, DHARMAPALA MAWATHA,COLOMBO - 07 DUST EXTRACTION HOPPER & NWS & DB /CP/WIL/103/ME/18
CONTRACT NO
P&P/D&B/LBF/WILGAMUWA/2014 DISSOLVING BASKET Sheet - 4 PROJECT MANAGER
CML - MTD CONSTRUCTION
PROJECT DIRECTOR
NWS&DB
FLANGE FABRICATED WITH FLANGE FABRICATED WITHFABRICATED WITH
FLANGE
SS304 PLATE 6mm THICK SS304 PLATE 6mmSS304
THICKPLATE 6mm THICK
673

250
250
140
FABRICATED WITH SS304 FABRICATED WITH SS304
PLATE 3mm THICK PLATE 3mm THICK

150

150
1200
1200
90°
SS CHAIN
LOCK FABRICATED
HOLES Ø15 CENTER TO HOLES Ø15 CENTER TO 25 WITH SS304

550
CENTER 60mm CENTER 60mm 3mm PLATE
35

DOOR

150
500 500

FRONT FRONT ELEVATION

70
FLANGE FABRICATED
WITH SS304 PLATE 6mm
THICK
FRONT

125
70
70

Ø 12 HOLES FOR M10

40
Ø1
500
125

640
640

Ø44 640
0
25

673
640
640 Ø 12 HOLES FOR M10

PLAN PLAN
673
DISSOLVING BASKET FOR DISSOLVING BASKET FOR
PACL - 2 NOS LIME - 2 NOS PLAN
SCALE 1:25 SCALE 1:25

DUST EXTRACTION HOPPER


ARRANGEMENT
QTY. 4NOS
SCALE 1:25

FOR INFORMATION ONLY


CLIENT NATIONAL WATER SUPPLY AND DRAINAGE BOARD REV DESCRIPTION DATE SIGN DESIGNED ENG. DHANUSHKA APPROVED IN PRINCIPLE SUBJECT TO THE REV NO DATE
GALLE ROAD, RATHMALANA, SRI LANKA.
WILGAMUWA WATER SUPPLY PROJECT 0 1ST SUBMISSION 2017-11-16 DRAWN JAYASUNDARA
CONDITION THAT THE DESIGN & BUILD -2 2018-06-18
CONTRACTOR IS RESPONSIBLE FOR THE
DESIGN DRAWING TITLE -1 REVISED AS PER NWS&DB COMMENTS 2017-11-30 CHECKED ENG. WANW CONFORMITY OF THE DESIGN WITH SHEET SIZE SCALE
YUNICA ENGINEERS & CONSULTANT FUNCTIONAL & STRUCTURAL REQUIREMENTS.
NO:157/2, MUIBUN TOWERS DHARMAPALA MAWATHA ,COLOMBO - 07 -2 REVISED AS PER NWS&DB COMMENTS 2018-06-18 A3 AS SHOWN
CONTRACTOR CHEMICAL HOUSE BUILDING DRG NO
CML-MTD CONSTRUCTION LTD
NO:155, DHARMAPALA MAWATHA,COLOMBO - 07 DUST EXTRACTION HOPPER & ...................................................... ..............................................
NWS & DB /CP/WIL/103/ME/19
CONTRACT NO
P&P/D&B/LBF/WILGAMUWA/2014 DISSOLVING BASKET Sheet - 5 PROJECT MANAGER
CML - MTD CONSTRUCTION
PROJECT DIRECTOR
NWS&DB
5 6
11
4
3 9
10
PS

PRE CL2-DUTY PG

Ø32 PVC Ø50 PVC

300 300 300


2 7 PRE CL2-STANDBY

2098
1932
POST CL2-DUTY

175
8
Ø32 PVC
1 POST CL2-STANDBY 1931

489
175
CHLORING BOOSTER PUMP CONNECTION DETAILS
SCALE 1:25

VIEW ON A - A VIEW ON B - B
SCALE 1:50 SCALE 1:50

WARNING LIGHTS
& HORNE

CHLORINE DOSING SYSTEM


PUM-4 POSITION DESCRIPTION QUANTITY
Ø32 BY PASS
SERVICE WATER 1 CYLINDER WEIGHING MACHINE 2
B B
Ø32 STRAINER PUM-3
Ø50 PVC 2 68kg CHLORINE CYLINDER 4

PUM-2 3 SCALE 2
Ø32 BY PASS 2m-TIN PLATED FLEXIBLE COPPER PIPES WITH
PANEL 4 4
CONNECTION VALVES
PUM-1
Ø50 PVC
5 COMMON HEADER 2

TO DOSING POINT 6 VACUUM REGULATOR 2


VACUUM CHANGE OVER NOTE:
7 1
UNIT
1. WARNING SYSTEM CONSISTS OF HORNE AND FLASH LIGHTS, GAS DETECTOR
A A 8 CHLORINE GAS SENSOR 2
AND GAS SENSORS.
CHLORINE 9
DIAPHRAGM TYPE PRESSURE
2 2. BODY & EYE SHOWER SHALL BE INSTALLED IN A LOCATION SHOWN BY THE
STORAGE AREA GAUGE
ENGINEER.
10 CL₂ INJECTOR 4
3. PRV SHOWN SEPARATELY IN P&ID IS INBUILT WITH THE VACUUM REGULATOR
11 DOING REGULATOR 4
4. VACUUM CONNECTING LINES ARE PE10/14

PLAN - CHLORINE BUILDING


SCALE 1:50
FOR INFORMATION ONLY
CLIENT NATIONAL WATER SUPPLY AND DRAINAGE BOARD REV DESCRIPTION DATE SIGN DESIGNED ENG. DHANUSHKA APPROVED IN PRINCIPLE SUBJECT TO THE REV NO DATE
GALLE ROAD, RATHMALANA, SRI LANKA.
WILGAMUWA WATER SUPPLY PROJECT 0 1ST SUBMISSION 2017-11-16 DRAWN JAYASUNDARA
CONDITION THAT THE DESIGN & BUILD -2 2018-06-18
CONTRACTOR IS RESPONSIBLE FOR THE
DESIGN DRAWING TITLE -1 REVISED AS PER NWS&DB COMMENTS 2017-11-30 CHECKED ENG. WANW CONFORMITY OF THE DESIGN WITH SHEET SIZE SCALE
YUNICA ENGINEERS & CONSULTANT FUNCTIONAL & STRUCTURAL REQUIREMENTS.
NO:157/2, MUIBUN TOWERS DHARMAPALA MAWATHA ,COLOMBO - 07 -2 REVISED AS PER NWS&DB COMMENTS 2018-06-18 A3 AS SHOWN
CONTRACTOR CHEMICAL HOUSE BUILDING DRG NO
CML-MTD CONSTRUCTION LTD
NO:155, DHARMAPALA MAWATHA,COLOMBO - 07 CHLORINATION SYSTEM ...................................................... ..............................................
NWS & DB /CP/WIL/103/ME/20
CONTRACT NO PROJECT MANAGER PROJECT DIRECTOR
P&P/D&B/LBF/WILGAMUWA/2014 CML - MTD CONSTRUCTION NWS&DB

You might also like