Professional Documents
Culture Documents
FT450
Model Í FT 450 (Replaces FT 32) 2 3 9 1
The trap contains a
Steam Traps
by a separate internal 11
Float &
Pressure (psig)
0 145 290 435 464 580 725 PMA 535 psig/650°F 37 barg/342°C
Max. allowable pressure
Operating Range
Temperature °F
300 572
TMA 750˚F/0-505 psig 400˚C/0-34 barg
200 392 Max. allowable temperature
* The limiting operating and design conditions for ANSI 150 flanged units
100 Steam saturation curve 212
will be limited by the Flange Rating.
0 32
0 10 20 30 32 40 50
Pressure bar g
Typical Applications
The product must not be used in this region.
All process equipment, particularly when controlled by modulat-
ing temperature control valves; unit heaters, air heating coils, heat
The product must not be used in this region
as damage to internals may occur. exchangers and steam main drip stations.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-2-304-US 03.12
2:190
Cast Steel Float & Thermostatic Steam Trap
FT450
D Sample Specification
G
Steam Traps
withdrawal
bimetal air vent. Internals of the trap shall be com-
Dimensions pletely servicable without disturbing the piping.
(nominal) in inches and millimeters
Size-DN A A1 B C D E F G H NPT/SW Flg
3/4” 6.1 10.1 3.0 3.1 6.4 4.7 7.4 4.0 — 18.0 lb 23.8 lb
20 155 255 76 79 163 120 189 102 8.2 kg 10.8 kg
Thermostatic
Float &
1” 6.5 10.4 5.0 3.8 8.2 6.3 9.2 5.8 — 28.0 lb 33 lb
25 165 264 127 97 208 160 234 147 12.7 kg 15 kg
1-1/2” 9.8 14.0 5.6 3.6 9.8 7.7 11.1 6.4 4.7 55.1 lb 64.0 lb
40 250 356 142 92 250 195 282 163 119 25.0 kg 29.0 kg Installation
2” 11.8 16.0* 6.0 4.0 10.0 7.7 11.6 6.5 6.0 68.0 lb 82.0 lb A pipeline strainer should be installed ahead of
50 300 406* 152 102 255 195 295 165 152 31.0 kg 37.3 kg
any steam trap. Full port isolating valves should
*ANSI 600 16.5” 419 mm be placed to permit servicing. The trap should be
installed below the drainage point of the equip-
ment with a collecting leg before the trap, in a
Maintenance
This product can be maintained without disturbing the piping connections. Complete position so that the float arm is in a horizontal
isolation from both supply and return line is required before any servicing is performed. plane and the float rises and falls vertically, with
The trap should be disassembled periodically for inspection and cleaning of the valve head the flow direction as indicated on the body. Refer
and seat, operating mechanism and air vent. to IMI 2.300 for complete instructions.
Worn or damaged parts should be replaced using a complete valve mechanism assembly
and/or air vent assembly.
Complete installation and maintenance instructions are given in IMI 2.300, which accom-
panies the product.
Air Bim
Ve eta
nt A lA
K sse spe ir Ve
cia n
N
J
mb
ly l op t Ass
tion em
Spare Parts
M K al bly
H
L H Valve Mechanism Kit
U w/ Float ( 3/4” & 1”) A,B,C,D,E,F,G
Gasket Kit
T
B G AEF D C (3 of each) B,K,T
© Spirax Sarco, Inc. 2012
TI-2-304-US 03.12
Spirax Sarco, Inc., 1150 Northpoint Blvd, Blythewood, SC 29016 Telephone: (803) 714-2000 FAX (803) 714-2222
2:191