Job

Name: MSX-P112-H12-MF Cut Sheet


Tag: MK-1
Quantity: 1
Printed Date: October 7, 2021

Model: MSX-P112-H12-MF
Design Conditions

Summer
Elevation (ft.) Winter (F) Supply (CFM)
DB (F) WB (F)
3,150 77.3 74.3 63.1 1,200

Unit Specification

Weight (lbs.) Cooling Type Heating Type Unit Installation Unit ETL Listing
1,103 Chilled Water Hot Water Indoor UL / cUL 1995

Configuration

Outdoor Air
Discharge Position Supply Air Filters Outdoor Air Damper
RightSide None Inlet Damper

Cooling Specifications

Performance (DB/WB) Capacity (MBH) Fluid Conditions


Type Flow Rate (GPM) Fluid PD (ft wg)
EAT (F) LAT (F) Total Sensible EWT (F) LWT (F)
Chilled Water 77.3/74.3 59.5/59.5 62.7 21.2 44 56 10 0.7

Heating Specifications

Performance Fluid Conditions


Type Capacity (MBH) Flow Rate (GPM) Fluid PD (ft wg)
EAT (F) LAT (F) EWT (F) LWT (F)
Hot Water 63.1 118.7 64.4 180 160 6.6 0.1

Air Performance

Fan
Type Total Volume (CFM) External SP (in wg) Total SP (in wg) RPM Operating Power (hp)
QTY Type Size Drive-Type
Supply 1,200 0.5 1.006 1,736 0.37 1 MixedFlow 12 Direct

Sound Performance

Sound Power by Octave Band


Lwa dBA Sones
62.5 125 250 500 1000 2000 4000 8000
71.1 70.9 65.1 62.8 70.6 70.4 66.6 66.5 75.6 64.6 13.2

Motor Specifications

Motor Qty Size (hp) Enclosure Efficiency RPM


Supply Fan Motor 1 1/2 ODP NEMA Premium 1,725

Electrical Specifications

Power Supply Rating (V/C/P) MCA (Amps) MOP (Amps)


Unit 460/60/3 1.6 15

Page 1 of 3 Version 3.0.0, September 2021


Job Name: MSX-P112-H12-MF Cut Sheet
Tag: MK-1
Quantity: 1
Printed Date: October 7, 2021

Supply Fan
1.2 0.4
1 ,7 3 6 F
RPM

Brake Horsepower (BHP)


Static Pressure (in. wg)

0.9 0.3

0.6 a 0.2
re
a
d ed
s ha
in
0.3 e 0.1
rat
pe
no t o
Do
0 0
0 3 6 9 12 15 18 21 24 27
Volume (CFM) x 100

Fan curve
Brake horsepower curve
Max system curve
System curve

Controls Sequence
General Operation: Unit will operate through a contact closure on R & G. This actuates the dampers (if equipped) and supply fan to
operate. The fan will operate at a constant volume, unless the unit is selected with variable air volume; Through various available controls,
the unit will have the ability to modulate between design and 50% of design performance.

Heating Operation: Unit heating will operate through a contact closure between R & W1, when outdoor air temperature is below the
heating inlet air temperature sensor setpoint (If equipped). Modulation of valves is provided by others.

Cooling Operation: Unit cooling will operate through a contact closure between R & Y1, when outdoor air temperature is above the
cooling inlet air temperature sensor setpoint (If equipped).

Page 2 of 3 Version 3.0.0, September 2021


Job Name: MSX-P112-H12-MF Cut Sheet
Tag: MK-1
Quantity: 1
Printed Date: October 7, 2021

Dimensions and Weights

Label Value Description


- 1103 Weight w/o accessories (lbs)
- 32.8 Supply Duct Width (in)
- 26.1 Supply Duct Height (in)
A 39 Overall Height (in)
B 34 Overall Width (in)
C 155 Overall Length (in)
W 36 Outdoor Air Intake (in)
X 36 Non-Access Side (in)
Y 36 Control Center Access (in)
Z 33 Access Side (in)

Page 3 of 3 Version 3.0.0, September 2021