You are on page 1of 2

DIN 4705 Engelsk udskrift

Draft Calculation according to DIN4705

Project: Stack H=50 biodrying boxes

Stack:
Effective height 45 m

Cross-sectional area Ø 2,2 m 3,801 m2


Cross-sectional area reduction Ø 2,2 m 3,801 m2

Hydraulic diameter 2,2 m

Operation temperature 40 °C 313 °K

Outdoor temperature 25 °C 298 °K

Flue gas mass 165750 m3/h (IN) 190036 m3/h =


52,788 m3/s

Flue gas velocity 13,9 m/s


Outlet velocity (Düse) 13,9 m/s

Density - air ( 101300 N/m2 ) 1,184 kg/m3

Density - flue gas 1,156 kg/m3

Surface roughness 0,0005 m


Roughness value 0,012872

Single resistance 0,8

Flow technical security factor SE = 1

Frictional resistance 29,3 N/m2

Single resistance 89,2 N/m2

Acceleration loss 111,4 N/m2


Acceleration loss, reduction 0,0 N/m2

Static draft -12,6 N/m2


2
Pressure at inlet 217 N/m

Side 1
DIN 4705 Engelsk udskrift

Draft Calculation according to DIN4705

Project: Stack H=50 biodrying boxes

Kanal:
Effective height 0m
Length of flue gas duct 1m

Cross-sectional area Ø 0,8 m 0,503 m2

Hydraulic diameter 0,8 m

Flue gas velocity 105,0 m/s

Surface roughness 0,0005 m


Roughness value 0,019293

Single resistance 1,6

Flow technical security factor SE = 1

Frictional resistance 153,7 N/m2

Single resistance 10198,2 N/m2

Static draft 0,0 N/m2


2
Pressure loss in flue gas duct 10352 N/m

Side 2

You might also like