You are on page 1of 8

Building and Environment, Vol. 29, No. 3, pp.

303-310, 1994
Copyright © 1994 Elsevier Science Ltd
~ ) Pergamon Printed in Great Britain. All rights reserved
0360-1323/94 $7.00+ 0.00

0360-1323(94)E0012-G

Evaluation of a Vertical Displacement


Ventilation System
BJARNE W. OLESEN*
MAKOTO KOGANEI*t
G. T H O M A S HOLBROOK*
JAMES E. WOODS*

The effectiveness of a vertical displacement ventilation system was evaluated when contaminants
including tobacco smoke were present. Air supply was through a perforatedfloor and carpet. System
performance was evaluated using AD PI (Air Diffusion Performance Index), percentage dissatisfied
due to draft, vertical temperature difference, and air change, and contaminant removal indices.
Gaseous contaminants were simulated with tracer gas. Cigarettes and occupants also generated
particulates, C02, CO, and TVOC (total volatile organic compounds). Several combinations of
supply airflow rate and thermal loads were evaluated. The risk of draft was found to be negligible.
The air change effectiveness for the room varied from 126 to 145% and the contaminant removal
effectiveness for the occupied zone variedfrom 80 to 700%.

INTRODUCTION to take into account how efficiently the air is distributed


within the occupied zone. In cases where stagnant air
THE cause for many cases of Sick Building Syndrome is
exists within occupied zones or short circuiting occurs
poor ventilation due to either inadequate flow of outdoor
between supply and return air streams, it may be necess-
air or poor distribution of the air in the system to the
ary to increase the amount of outdoor air and the total
occupied space. The distribution of the air influences both
supply air flow rate to values that exceed those based on
the thermal conditions and the indoor air quality in the
assumptions of complete mixing [1, 2]. The standards
space. The quality of the thermal environment is affected
and guidelines introduce the concept of ventilation effec-
by the air temperature uniformity in the occupied space,
tiveness, but without any detailed explanations on how
i.e. vertical air temperature differences, and risk for draft.
to measure it. To properly assess the ventilation in the
Draft sensation is the combined effect of air temperature,
breathing zone, one must determine :
mean air velocity, and turbulence intensity. Indoor air
quality is influenced by the quality of the air supplied to • the air renewal/air distribution process: how quickly
the occupied zone, the emission rates of sources within "old" air is replaced with "new" air in the occupied
the occupied and unoccupied zones, the degree of con- zone [3];
taminant dilution in the occupied zone, and the degree • the contaminant removal process : how effectively con-
of contaminant removal from the occupied zone. taminants generated within the occupied and unoc-
The objective of this study is to evaluate the per- cupied zones are removed and prevented from spread-
formance of a vertical displacement ventilation system ing in the occupied zone [4].
with air supplied through a perforated floor. Initial
results of this evaluation and a discussion of air change These two processes are related but not identical and
effectiveness and contaminant removal effectiveness therefore need to be considered separately. For both air
measurements are presented. Data were obtained for sev- renewal and contaminant removal it is important to dis-
eral contaminants, two different supply air flow rates, tinguish between results based on room average, occu-
and two thermal load conditions. pied zone average or local conditions. For example, the
air renewal/air distribution process is commonly evalu-
ated by ratioing the exhaust age-of-air to the age-of-air
BACKGROUND at a point or within a zone of interest. In the following
Outdoor air ventilation rates or outdoor air change background discussion, this ratio is denoted as the air
rates listed in existing standards and guidelines [1, 2] change effectiveness and is meant to be applied to the
assume complete mixing of the air in the ventilated space. room as a whole unless otherwise indicated. Similar
As complete mixing does not always occur, it is necessary remarks apply in the following background discussion in
which the contaminant removal process is evaluated
using the term contaminant removal effectiveness. Com-
plete mixing is referred to here as having an air change
*Indoor Environment Program, Virginia Polytechnic Institute
and State University, Blacksburg, VA 24061, U.S.A. effectiveness of 100% as compared to an air change
1"Research and Development Center, Asahi Kogyosha Co., efficiency of 50% as used in [4].
Ltd., 6-17-16 Higashi-Narashino, Narashino, Chiba 275, Japan. With displacement flow ventilation, the vertical tem-

eAE 29:3-e 303


304 B.W. O l e s e n et al.

perature difference between feet and head may cause ther- (ceiling supply and return) at various air change rates. In
mal discomfort. Thus a critical system performance cri- most of the tests, the effectiveness varied between 80 and
terion is the maximum cooling load that can be removed 116%.
from the occupied zone without causing thermal dis- Olufsen [27, 28] reported extensive age-of-air measure-
comfort. Based on laboratory studies [5] and rec- ments in both test and real rooms. The tested ventilation
ommendations in internationally recognized standards systems included both conventional systems (ceiling sup-
[6,7], the air temperature differences between head and ply and return) and displacement type systems (floor/
feet of sedentary or standing occupants should not exceed lower wall supply and ceiling return). The global air
3 C , to achieve a dissatisfaction criterion of not more change effectiveness, defined as the ratio of the exhaust
than 5%. If the supply air is too cold, the vertical tem- age-of-air to the room average age-of-air, varied between
perature gradient in the space may cause discomfort. The 58 and 104% for the conventional systems and between
gradient may be reduced by increasing the supply air flow 102 and 116% for the displacement type systems. The
but too much air flow can cause discomfort due to draft. local air change effectiveness, defined as the ratio of the
Discomfort due to draft results from the combined influ- exhaust age-of-air to the local age-of-air, varied sig-
ences of local air temperature, air velocity and turbulence nificantly more. Near the floor, values of up to 500%
[6-8]. Full scale experiments [9,10] suggested a maximum were obtained for the displacement systems. Near breath-
cooling load of 20-30 W/m 2 for displacement ventilation. ing level (1.1 m height), values of up to 200% were
More recent experiments [11] show that well designed obtained. For the conventional systems the local air
displacement diffusers can handle loads up to 40 W/m 2. change effectiveness at breathing level varied between 50
Svensson [12] suggests that with well selected supply ter- and 110%. Several internal load densities, air flow rates,
minal devices, 30 W/m 2 can be removed from occupied and supply temperatures were studied. No clear influence
zones with room ceiling heights of 2.7-2.8 m, and 40 of these parameters was reported. Cox et al. [29] reported
W/m 2 can be removed from occupied zones with ceilings on a study of a displacement ventilation system in an
at about 3.4 m. Sandberg [13] recommends a maximum office. Contaminant removal effectiveness was measured
cooling load of 25 W/m 2 based on a vertical air tem- using tracer gas dosed in the office to simulate a con-
perature gradient of less than Y'C/m. Similar limits for taminant source. At breathing level (1.1 m height), the
maximum cooling loads are recommended in references effectiveness was close to 100%--not significantly better
[14] and [15]. The reported studies do not distinguish than for a conventional system. For lower heights the
between loads in the occupied zone and above, i.e. lights. effectiveness had much higher values. A higher flow rate
This may influence the heat load which can be removed increased the contaminant removal effectiveness but
with displacement systems without causing comfort prob- people moving around in the room decreased the effec-
lems. tiveness. Qingyan et al. [30] studied the air flow patterns
Several field measurements [16-23] of air change effec- in a room with four different configurations of supply
tiveness have been performed using the age-of-air and return devices, including displacement type systems.
concept. All of these studies dealt with ceiling supply and All experiments were performed in a cooling mode. The
return systems operated during summer conditions, i.e. contaminant removal effectiveness for the displacement
cooling mode. Air change effectiveness for the occupied type systems reached values up to 170% while the con-
zone was found to be around 100%, implying perfect ventional, i.e. non-vertical displacement, system had an
mixing conditions. Bauman et al. [24] studied the air effectiveness of 60%. Higher flow rates increased both the
change effectiveness in a simulated, partitioned office contaminant removal effectiveness and the temperature
space having a ceiling supply and return ventilation effectiveness (the ratio of the temperature difference
system. They also concluded that under cooling con- between the exhaust and supply to the temperature
ditions (supply temperature lower than room tem- difference between the sample location and the supply),
perature), the air change effectiveness indicated complete but a higher heat load (from a simulated warm window)
mixing. Their [24] tests with heating (supply temperature reduced the effectiveness values.
higher than room temperature) showed air change effec- Nickel [31] studied the influence of different types of
tiveness values lower than 100% indicating some short ventilation systems on the air quality in a room with
circuiting. Offermann [25] reported measurement of air simulated tobacco smoking. Conventional systems using
change effectiveness values less than 100% on a forced ceiling supply and return were compared with a dis-
air heating system with ceiling supply. Seppanen [26] placement system using low wall supply and ceiling
reported on simultaneous measurements of air change return. The tests were clone in a conference test room
effectiveness and contaminant removal effectiveness in a with a thermal load simulation of 10 people and lights.
test room. In these measurements the contaminant Smoking was simulated with 12 burning cigarettes and
removal effectiveness was measured by simulating CO2 the emitted CO was used as representative of the cigarette
emissions from a seated person. The highest values (air pollution. Local contaminant removal effectiveness
change effectiveness of 92-144% and contaminant values were obtained by comparing concentrations at
removal effectiveness of 110-190%) were obtained for different locations and heights in the room with the con-
the displacement system. The difference between supply centration in the extract. For the conventional systems,
and room temperature varied between - 3 and +3°C. values between 84 and 90% were obtained at a breathing
No general relationships between air change effectiveness level of 1.2 m. For the displacement system, values in the
and contaminant removal effectiveness were found. In range of 500 1400% were measured. By changing the
the same study, the air change effectiveness was measured location of the exhaust in the ceiling, conventional system
in several offices with typical air distribution systems effectiveness values increased at some locations to greater
Vertical Displacement Ventilation System 305

4.4 m

~Return air grilles 7 [


Chair Lights Chair
©'
Measurement
2.5 m Lights
02 location

1.7 m
D~,r [--']T~

jL
Supply Supply
Chair Chair
I.Im
4.2 m
Chair Chair
IL O.l'~m 0.6 m
x__ Perforated floor/carpel

(a) Room plan with tobacco smoke dosing (b) Room section with measurement heights
at "T" and tracer gas dosing at "S". annotated (ceiling height is 3.2 m from floor)
Fig. 1. Schematic of test room.

than 100%. Also, the location of the exhaust in the ceiling All tests used 100% outside air, i.e. no return air was
had some influence on the measured local contaminant recirculated. Before the start of the tests the supply and
removal effectiveness values for the displacement system. exhaust air flows were balanced. Sensible thermal loads
The author also noted that persons moving around in the consisted of fluorescent lights (total of 240 W, wall-
room helped to mix the air and reduced the effectiveness mounted near the ceiling) and a simulated occupant load
of the displacement flow. of five persons. Electric blankets were folded so the sur-
This literature review indicates that a limiting factor face area was similar to that of a standard person and
for the use of displacement ventilation is that a heat load the output wattage for each blanket was set at 120 W
of only 30-40 W/m 2 can be removed from an occupied (determined from its electrical resistance at operating
zone without violating existing comfort criteria for ver- conditions) to approximate the heat load of a person and
tical air temperature difference between feet and head desk lamp. Latent loads were not included in this study.
and for draft at the floor, near supply terminal devices. Supply air flow rates were 142 and 472 l/s and thermal
In most of the reported experiments with displacement load levels were 13 W/m 2 (fluorescent lights only) and 44
type systems as well as in most existing displacement W/m 2 (fluorescent lights and all blankets on). Gaseous
systems, the air has been supplied through relatively large contaminants were simulated with tracer gas (SF6) dosed
air diffusers positioned at a wall and close to the floor. in the center of the room at a height of 0.9 m. Particulates,
The present study investigates a displacement system CO2, CO, and total volatile organic compounds (TVOC)
using a perforated carpet/floor as the supply diffuser. The were generated from the sidestream smoke of six ciga-
assumption is that with this type of system, higher flow rettes, continuously burning and mounted at a height of
rates are possible since the velocity is lowered by spread- 0.9 m. An occupant, seated in the center of the room
ing the flow over a larger outlet area and thus a higher (breathing level at 1.1 m), kept the cigarettes burning
heat load can be removed without causing comfort prob- continuously. The occupant was also assumed to have
lems. generated particulates, CO2, CO, and TVOC. When the
The literature also shows that both contaminant occupant was in the room, the thermal load output of
removal effectiveness and air change effectiveness are use- the blanket in the center of the room was reduced to 50
ful parameters in evaluating the performance of a system. W, i.e. simulating a desk lamp only.
Previously reported data show air change effectiveness The thermal environment was evaluated from measures
values up to 140% and local contaminant removal effec- of temperature and air velocity mean and standard devi-
tiveness values much higher (1400%). These values are ation at five heights (0.1, 0.6, 1.1, 1.7, and 2.5 m) and at
influenced not only by the location and type of supply four locations (Fig. 1). From these measurements vertical
and return terminal devices but also by flow rates, air temperature differences, and percentage dissatisfied
internal heat loads, the difference between supply and due to draft (PD) were calculated [6, 7, 32] for the occu-
room temperature, and the type of contaminant. No clear pied zone (height ~< 1.7 m) while the Air Diffusion Per-
relation between these factors and the effectiveness has formance Index (ADPI) was evaluated for both the occu-
been found in existing literature. pied zone and the room (all points). ADPI [32] was
calculated as the percentage of points meeting the criteria
METHOD - 1.7°C ~< 0 ~< 1.1°C;
Tests were performed in a test room with a floor size where 0 = ta--t~,a--8(Va--O.15), (1)
of 4.2 m by 4.4 m and a ceiling height of 3.2 m. The walls where 0 = effective draft temperature (°C); ta = cor-
and ceiling were approximately adiabatic. The test room rected time averaged air temperature at each measuring
was served by a vertical displacement ventilation system point (°C) ; ta,a = average test zone air temperature (°C)
supplying air through a perforated floor/carpet and (average of all ta values) ; v. = mean air velocity at each
returning air through l0 grilles in the ceiling (Fig. l). measuring point (m/s).
306 B . W . Olesen et al.

The percentage of dissatisfied due to draft (PD) was each point. In this way room average, occupied zone
calculated as [8]: average, and breathing level (1.1 m height, sedentary)
average contaminant removal effectiveness values could
e o = (34-t,,~,) (Va-0.05) T M (0.37SD,:+3.14), (2) be calculated. Only the occupied zone average, C R E , ,
where SD,, = standard deviation of the local mean air (average of all CRE r values measured at heights ~< 1.7
velocity. m), and 1.1 m breathing level average, CREj~,, (average
Air temperature differences between feet and head lev- of all CREp values measured at a height of 1.1 m), values
els for seated (0.1 and 1.1 m) and for standing (0.1 and 1.7 are reported here. Gaseous contaminants were measured
m) were calculated as the average of simple temperature with the photo-acoustic detection method, and par-
differences between these measurement heights at each of ticulates with the piezo-balance method.
the four measurement locations (Fig. 1).
The local air change effectiveness was determined [3] RESULTS
as the ratio of the local age-of-air calculated from con-
centrations measured at the return air grilles to the local Measured thermal comfort indices and air change
age-of-air calculated from location 1 concentrations mea- effectiveness data are presented in Table 1. Each par-
sured at a height of either 1.1 or 1.7 m. The age-of-air at ameter was evaluated for two or more heights or zones.
a point in the room is a measure of the time it takes the Similarly, contaminant removal effectiveness data are
supply air to reach that location in the room [3, 33]. The shown in Table 2 for the same air flow rate and thermal
age-of-air, r, at each measuring point was determined by load conditions.
using the step-up method in which tracer gas is dosed
into the supply duct, as described by Sutcliffe [3]. DISCUSSION
The thermal environment (air temperatures and vel-
Z=f: [1-~f)ldt, (3) ocities) was relatively uniform except for the test with
low supply air flow and high load (Table 1). Vertical
where C~ (t) is the time dependent concentration at the temperature differences were no more than 1.2°C between
measuring point, C~ is the concentration in the supply ankle (0.1 m) and head (1.1 m) for a sedentary person
air, and t is time. and no more than 1.5°C for a standing person (0.1 m and
The local age-of-air was determined at heights of 1.l 1.7 m), again except for the low supply air flow and high
and 1.7 m since these are the breathing levels of a sed- load where the corresponding values were 2.2 and 3.3°C.
entary and a standing person. The local air change effec- These values are within the recommended values in ISO
tiveness was computed at each point and the effectiveness 7730 [6], but the 3.3°C temperature difference for a stand-
values for repeated measurements at the same point were ing person measured in the low flow/high load condition
averaged together. The average of all effectiveness values is just above the recommended level in A S H R A E 55-92
obtained at 1.1 m height is reported here as ACEIim and [7]. Note, however, that the floor supply provides a very
at 1.7 m height as ACE:re. The room average age-of- low inlet velocity (typically 0.05 m/s or less), and thus
air, (z), was determined [33] from calculations using the supply flow rate can be increased (increased recir-
concentrations measured at the return air grilles. culation) as required by the heat load without sig-
nificantly altering the discomfort due to draft. Therefore,
the low supply rate condition [7.6 1/(s" m2)] was at an air
c~ J /jo flow rate much lower than could be used in practice, e.g.
as required by A S H R A E 62-89 [1] for a smoking lounge.
where Ce(t) is the time dependent concentration at the Even with a load of 44 W/m 2 there were no comfort
return air grilles. Room average air change effectiveness problems due to vertical air temperature differences.
values were determined as the ratio of the local age-of- Mean air velocities were always lower than 0.10 m/s in
air calculated from concentrations measured at the return the occupied zone and, for most locations, about 0.05
air grilles to the room average age-of-air. Effectiveness m/s. A S H R A E 113-90 [32] recommends that ADPI
values for repeated measurements of the same room con- should be more than 80%. In several of the tests the index
dition were averaged together and are reported here as dropped below 80%. Since the measured air velocity in
simply ACE. most cases was about 0.05 m/s, the corrected air tem-
Contaminant removal effectiveness, CRE e, is a measure perature due to air velocity, calculated as - 8 (v,-0.15
of how effectively contaminants generated in the room m/s), was +0.8°C. Since the limiting effective draft tem-
are removed from the room and prevented from spread- perature (0) is 1.1 °C, the maximum acceptable difference
ing into the measurement location p, calculated as in [4] : between the test point temperature and the average zone
temperature would then only be 0.3°C. Thus, the ADPI
CRE, = ( C ~ - C s ) / ( G - C O " 100%, (5)
calculation implies that the optimal air velocity is 0.15
where Ce = contaminant concentration at return air m/s ; but it has been demonstrated that at 0.15 m/s people
grilles; Cs = contaminant concentration in the supply may experience draft [7, 8]. Data for the percentage dis-
air; and Cp = contaminant concentration at the sample satisfied due to draft show that all points in the occupied
point p. zone were lower than the 15% recommended in ISO/DIS
Contaminant concentrations were measured at four 7730 [6] and A S H R A E 55-92 [7]. In this case, then, the
locations (Fig. 1) and five heights (0.1, 0.6, 1.1, 1.7, and criteria used for ADPI do not give a correct evaluation of
2.5 m) for each location and CRE r was computed for the impact that air velocity distribution has on comfort.
V e r t i c a l D i s p l a c e m e n t Ventilation S y s t e m 307

Table 1. Thermal environment and air change effectivenessdata

Vertical PD Air change


temperature PD <~ 15% average effectiveness
mean
Supply difference (m) ADPI ( _+standard deviation)
flow Load Height Height
rate (l/s) (W/m 2) 1.1-0.1 1.7-0.1 Height ~<1.7 m All points ~<1.7 m ~<1.7 m ACE11m ACE~7m ACE

142 13 0.6°C 1.2°C 69% 56% 100% 0.7% 115% 1 1 2 % 126%


(_+7%) (lpt)* (_+13%)
472 13 0.8°C 1.5°C 75% 80% 100% 3.2% 158% 97% 145%
(_+27%) (lpt)* (+_11%)
142 44 2.2°C 3.3°C 75% 60% 100% 0.5% 106% 1 0 2 % 135%
(lpt)* (lpt)* (lpt)
472 44 1.2°C 1.3°C 94% 75% 100% 3.6% 197% 162% 137%
(_+27%) (lpt)* (_+14%)

* Only one measurement obtained for this condition.

Table 2. Contaminant removal effectiveness for different contaminants and for two different supply rates and two thermal load
conditions

Supply Contaminant removal effectiveness(%)


flow CRE, Am CREo,
rate Load
(l/s) (W/m2) CO2 CO TVOC SF 6 Particulate CO: CO TVOC SF6 Particulate

142 13 358 169 217 168 299 404 201 181 205
472 13 239 107 77 397 -- 225 103 79 701
142 44 269 291 199 236 297 518 245 385 215
472 44 214 96 81 615 594 206 105 96 640

Vertical profiles of contaminant concentrations and air velocity are shown in Fig. 2. These values were obtained by averaging data
measured at locations one through four.

Thus, it is recommended that these criteria be modified load (162%). This indicates that the clean zone height is
for consistency with the ISO/DIS 7730 [6] and ASHRAE lower than 1.7 m with the low flow rate and that the
55-92 [7] standards. Based on these requirements, there supply air temperature is too close to the room air tem-
were no draft problems in the present study even with perature to establish displacement flow for the high flow/
the high supply flow rate of 25 l/(s" m2). low load condition. The room average air change effec-
The air change effectiveness data in Table 1 also include tiveness (Table 1) does not vary much (126-145%). This
the standard deviation as a measure of the repeatability. indicates that displacement flow is obtained only in a
For a few tests, a lack of supply air temperature control portion of the occupied zone, and above the "clean zone"
resulted in non-steady state conditions. The supply flow a mixing zone, including some stagnant area, develops.
rates in the repeated tests were however within 6%. The small region of displacement flow may have been
During these tests the test room was positively pressur- caused by control system forced cyclic oscillations in the
ized with respect to the surrounding space as indicated supply air temperature (up to 16°C peak-to-peak) during
by a plastic sheeting side wall which bowed outward from all test runs, however, the room temperature typically
the room. This was verified by the age-of-air data since held to within +_1.5°C. The data do however indicate
the room average age-of-air greatly exceeded the room piston flow with local air change effectiveness values up
nominal time constant (room volume/air supply rate) to 200% (local effectiveness values would be about 100%
for both flow rate conditions, thus indicating room air if complete mixing existed at the sample location). This
exfiltration. With no room exfiltration/infiltration, the is higher than reported in many studies with displacement
room average age-of-air should be between that of piston systems with low wall supply diffusers. However, it is
flow (one half the nominal time constant) and complete important to use a supply flow rate which will result in a
mixing (equal to the nominal time constant) [3]. Similar clean zone height higher than the occupied zone.
results can also be found throughout the test literature An even higher supply flow rate, or a larger tem-
[22, 23]. Since the use of age-of-air ratios for air dis- perature difference between supply and room air, would
tribution effectiveness/efficiency evaluations is based have been possible with this type of system without caus-
upon the assumption of no test room leakage [3], the ing comfort problems due to draft and vertical air tem-
value of field measurements of air change effectiveness perature differences. This means a significantly higher
parameters should be closely examined. heat load than the 44 W/m 2 used can be removed with a
The air change effectiveness based on the age-of-air at system supplying the air through a perforated floor.
a height of 1.1 m varied between 106 and 197%, showing The contaminant removal effectiveness data show no
higher values for higher supply flow rates (Table 1). Sig- clear indication of the effect of thermal loads and supply
nificantly lower values were measured at 1.7 m height flow rate. Large variations are present, but in most cases,
(97-112%) except for the case with high flow rate/high the values are significantly above 100%--up to 700%.
308 B . W . Olesen et al.

Different contaminants were supplied to the space with the space, i.e. initial velocity and the proximity to heat
significantly different methods which may have influ- plumes. Contaminant removal effectiveness as presently
enced the contaminant removal effectiveness values. CO2, defined is not suitable to characterize the performance of
generated by the person sitting in the room, was emitted a ventilation system, because the value is so dependent
with a lateral impulse as opposed to the other con- on type and location of the contaminants. Air change
taminants which had a negligible initial velocity. SF6 is a effectiveness is better for characterizing the air dis-
"cold" source--its density is greater than air causing the tribution system. Values obtained for contaminant
S F 6 to mix with the air below the dosing point. In this removal effectiveness can only be used under the assump-
study it was dosed above an electric blanket. For the low tion that all contaminants are evenly distributed in a
thermal condition, the blanket was turned off, no thermal space. Until a standard methodology is developed, the
flow was provided, and S F 6 spread in all directions, sample locations utilized to characterize the room or zone
resulting in low local concentrations. For the high ther- of interest and the source and its contaminants should be
mal condition, the blanket underneath the dosing point included when presenting contaminant removal effec-
was turned on, providing a thermal plume-flow upward, tiveness data.
taking the SF~ with it, and resulting in higher con-
centrations. The cigarettes are "warm" sources, and
although they do not significantly influence the heat load
in the room, they influence the local thermal conditions
CONCLUSION
because of their small heat plumes. These heat plumes
take the generated contaminants upwards, which affected Although the data reported here are limited and the
the way the produced contaminants, particles, CO and tests did not show a high degree of repeatability, it is
TVOC distributed in the test room. (See contaminant clear that the performance of a displacement ventilation
concentration profiles in Fig. 2.) system is dependent on factors such as the thermal load
The problem with obtaining meaningful contaminant condition, the total supply flow rate, and the type and
removal data is determining the proper sampling location of the contaminant generated in the room. Dis-
locations to arrive at a representative data set. The con- placement ventilation systems supplying air through a
taminant concentration can be measured at one height, perforated floor can remove higher heat loads than 44
e.g. breathing level, or averaged over a volume, e.g. the W/m 2 without causing any thermal comfort problems.
entire occupied zone. Also the distance from the source No thermal comfort problems existed under the tested
to sample locations should be taken into account as well conditions. Criteria used in determining the ADPI must
as the source temperature and type of contaminant. The be reviewed to reflect results on people's perception of
contaminants used in a measurement of contaminant draft. Air change effectiveness measurements indicated
removal effectiveness will behave very differently depend- displacement flow in the test room. Effectiveness values
ing on their density and the way they are emitted into seemed to increase with flow rate. Contaminant removal

(142 l/s) (472 l/s)


Contaminant Symbol (Ce-C~) (Ce'C s)
CO 2 o 38.7 ppm 20.3 ppm
co o 0.33 ppm 1.05 ppm
TVOC A 0.40 ppm 0.32 ppm
SF 6 0 4.66 ppm 1.83 ppm Open symbols for 142 I/s
Particulate + 0.68 mg/m 3 0.23 mg/m 3 Solid symbols for 472 I/s
142 I/s 472 l/s
3.2 3.2

2.4
std. dev.
i.\
Velocity

2.4

~eQ 1.6 / 1.6

0.8

0 0.5 1.0 1.5

(Cp'C.)/(Ce'C.)
2.0
I
2.5 0
I
0.5 1.0 1.5
,,
2.0
( C: C ~)l(C :C ,)
2.5 0.05
Velocity (m/s)
0.10
0.8

Fig. 2. Normalized profiles of local concentrations (Cp) and velocitiesaveraged over four locations in test
room at 44 W/m2and at two supply flow rates.
Vertical Displacement Ventilation System 309

data showed no clear influence of heat load and supply dard method must address the measurement locations in
flow rate. the test area and their proximity to the contaminant
There is a need for standardized methods to measure sources as well as the type of sources.
both ventilation effectiveness and thermal comfort. Wide
variations in contaminant removal effectiveness data Acknowledgements---We are pleased to acknowledge that this
study is being funded by Philip Morris U.S.A. We also gratefully
resulted from differing measurement techniques. The acknowledge the support from Asahi Kogyosha Co., Ltd. for
definition and measurement method for contaminant Dr. Koganei as a Visiting Scholar at the Virginia Tech Indoor
removal effectiveness needs to be further detailed. A stan- Environment Program.

REFERENCES

1. ASHRAE Std. 62-89, Ventilation for acceptable indoor air quality, Atlanta, GA (1989).
2. EEC Report No. 11, Guidelines for ventilation requirements in buildings. European Concerted Action
(COST-613), Commission of the European Communities, Luxembourg (1992).
3. H. Sutcliffe, Technical Note No. 28, A guide to air change efficiency, AIVC, U.K. (1990).
4. C. Brouns and B. Waters, Technical Note No. 28-2, A guide to contaminant removal effectiveness,
AIVC, U.K. (1991).
5. B.W. Olesen, M. Scholer and P. O. Fanger, Discomfort caused by vertical air temperature differences
and comfort, in Conf. Proc. Indoor Climate 1979, pp. 561-579, Danish Building Research Institute
(1979).
6. ISO 7730, Moderate thermal environments~etermination of the PMV and PPD indices and speci-
fication of the conditions for thermal comfort. International Standards Organization, Geneva (1984)
(revised 1993).
7. ASHRAE Std. 55-92, Thermal environmental conditions for human occupancy, Atlanta, GA (1992).
8. P.O. Fanger, A. K. Melikow, H. Hanzawa and J. Ring, Air turbulence and sensation of draught.
Energy and Buildings 12, 1 (1988).
9. H. Mathisen and E. Skaret, Displacement ventilation in small room. Sintef Report STF 15 A84047,
Norwegian Institute of Technology, Norway (1983).
10. H. Esdorn, H. Knabl and R. Kulpmann, Air conditioning, new horizon-new opportunities, in
Proceedings of the 4th International Conference on Indoor Air Quality and Climate, Volume 4, Institute
for Water, Soil, and Hygiene, Berlin (1987).
11. I. Palonen, A. Majonen and O. Seppanen, Performance of displacement air distribution system in
small office room, in Proceedings of Heahhy Buildings '88 (Edited by B. Berglund and T. Lindvall),
Swedish Council for Building Research, Stockholm, Sweden (1988).
12. A . G . L . Svensson, Nordic experiences of displacement ventilation systems. ASHRAE Transactions
95(2) (1989).
13. M. Sandberg and C. Blomqvist, Displacement ventilation in office rooms. ASHRAE Transactions
95(2) (1989).
14. H. Stymne, M. Sandberg and M. Mattsson, Dispersion pattern of contaminants in a displacement
ventilated room--implications for demand control. 21th AIVC Conference, Ottawa, Canada (1991).
15. D. P. Wyon and M. Sandberg, Thermal manikin prediction of discomfort due to displacement
ventilation. ASHRAE Transactions 96 (1990).
16. A.K. Persily, Ventilation effectiveness in mechanically ventilated office buildings. National Institute
of Standards and Technology, NBSIR 85-3208 (1985).
17. A.K. Persily, Ventilation effectiveness measurements in an office building. ASHRAE Proceedings of
IAQ 86, Managing Indoor Air for Health and Energy Conservation (1986).
18. A . K . Persily and W. S. Dols, Field measurements of ventilation and ventilation effectiveness in a
library building, in Proceedings of the l lth A1VC Conference, Ventilation System Performances,
Volume 2 (1990).
19. A.K. Persily and W. S. Dols, Field measurements of ventilation and ventilation effectiveness in an
office/library building. Indoor Air 1(3) (1991).
20. W.J. Fisk, R. J. Prill and O. Seppanen, Commercial building ventilation measurements using multiple
tracer gases. Proceedings of the 9th AIVC Conference, Effective Ventilation (1988).
21. W.J. Fisk, R. J. Prill and O. Seppanen, A multi-tracer technique for studying rates of ventilation, air
distribution patterns, and air exchange efficiencies. ASHRAE, Building Systems : Room Air and Air
Contaminant Distribution (1989).
22. W.J. Fisk, D. Faulkner and R. Prill, Air exchange effectiveness of conventional and task ventilation
offices. ASHRAE Proceedings of lAQ '91, Healthy Buildings (1991).
23. B.W. Olesen and J. Seelen, Field measurements of air change effectiveness using tracer gas techniques.
ASHRAE Proceedings of lAQ '92, Environmentsfor People (1992).
24. F.S. Bauman, D. Faulkner, E. A. Arens, W. J. Fisk, L. P. Johnston, P. J. McNeel, D. Pih and H.
Zhang, Air movement, ventilation, and comfort in a partitioned space. ASHRAE Transactions 98(1)
(1992).
25. F.J. Offermann, Ventilation effectiveness and ADPI measurements of a forced air heating system.
ASHRAE Transactions 94(1), 694-704 (1988).
26. O. Seppanen, Ventilation effectiveness in practice. IAQ '86, Atlanta, GA (1986).
27. P.L. Olufsen, Measurement of air distribution in mechanically ventilated rooms. SBl-report 216,
Horsholm, Denmark (1991) [in Danish].
28. P. L. Olufsen, Field studies on ventilation efficiency in mechanically ventilated rooms. ASHRAE
Transactions 97(2) (1991).
29. C . W . J . Cox, Ph. J. Ham, J. M. Koppers and L. L. M. van Schijndel, Displacement ventilation
systems in office rooms : a field study. Roomvent '90, Stockholm (1990).
310 B . W . Olesen e t al.

30. C. Qingyan, J. Van der Kovi and A. Myers, Measurements and computation of'ventilation efficiency
and temperature efficiency in a ventilated room. Enerqy and Buildings 12 (1988).
31. Nickel, Air quality in a conference room with tobacco smoking ventilated with mixed or displacement
ventilation. Roomvent '90, Oslo (1990).
32. ASHRAE Std. 113-90, Method of testing for room air diffusion, Atlanta, GA (1990).
33. M. Sandberg and M. Sjoberg, The use of moments for assessing air quality in ventilation r o o m s
Buildin# and Environment 18, 181 197 (1983).

You might also like