You are on page 1of 3

200000 LL Cap Sr - 16.

00 m Staging - M30
Design of roof slab - 100 mm thick
Using 10 mm dia. RTS
Effective depth = 100 - 45 - 5 = 50 mm
Roof slab projection = 0 mm
Diameter of roof slab = 9.0 m
According to IS 3370 - ( Part 2 ) : 2009 - Clause 5.3
If the tank is supported on walls or other similar supports, the floor slab shall be designed for bending moments due to
Max. panel size = Diameter of inscribed circle
= 4.0 m
Load calculation
Live load = = 1.5 KN / m2
Self weight = 0.1 x 25 = 2.5 KN / m2
Total 4 KN / m2

Moments taken from IS 456 : 2000 - Table 26


lx = 4 m
ly = 4 m
ly = 1 Two - way slab
lx
Negative moments at continuous edge a x = 0.032
a y = 0.032

Mx = 4.00 x 0.032 x 4 x 4 = 2.048 KNm


My = 4 x 0.032 x 4 x 4 = 2.048 KNm

Positive moments at mid - span a x = 0.024


a y = 0.024

Mx = 4 x 0.024 x 4 x 4 = 1.536 KNm


My = 4 x 0.024 x 4 x 4 = 1.536 KNm

Check for cracking stress


Actual cracking stress - f = 2.05 x 6 x 1000000 = 1.23 N/mm2 < 2 N/mm2
1000 x 100 x 100
Hence safe
Reinforcement at bottom

Ast = 2.048 x 1000000 = 366.36852 mm2


130 x 0.86 x 50

Minimum Ast = 0.24 x 1000 x 100 = 240 mm2


100
Min. Ast required per face = 120 mm2 183.18

3
Provide 10 mm RTS
Spacing = 1000 x 78.5398 = 214.4 say 200 mm c/c 392.699 mm2
366.37 Bothways

For Maximum sagging bending moment = 1.54 KNm

Area of steel required


1.536 x 1000000 = 274.776 mm2
130 x 0.86 x 50
Alternate bars are cranked at 0.25 l from the centre of the support be at 1220 mm. Bars are extended ypto 1500 mm
from the centre of support
Result :-
Thickness - 100 mm.
Bottom rod - 10 mm dia RTS @ 200 mm c/c on both direction.
Alternate bars are cranked at 0.25 l from the centre of the support be at 1220 mm. Bars are
extended ypto 1500 mm from the centre of support and extra rod of 10 mm dia RTS @ 400 mm c/c
at top in all supports.

Design of side wall


Assume the thickness of side wall as 150 mm
It is assumed that the side wall is fixed at bottom and free at top
Storage depth = 3.6 m
Scour depth = 0.15 m
Free board = 0.3 m
H - Height of water = 4.05 m
D - Inner dia. of tank = 8.5 m
t - Thickness.of side wall = 150 mm ( Assumed )

H2 = 4.05 x 4.05 = 12.8647


Dt 8.5 x 0.15

Refer IS 3370 - Part IV - Table 9 and 10

H2 Max. -ve B.M. Co - eff. Max. +ve B.M. Co - eff. Hoof tension Co. eff.
Dt at 1H at 0.6H at 0.5H
14 - 0.009 + 0.0008 + 0.539
12 - 0.0104 + 0.0013 + 0.543
12.86 - 0.0098 + 0.00108 + 0.54127

Max. -ve B.M. = 0.0098 x 1000 x 4.05 x 4.05 x 4.05 x 10 = 6506.64

Max. +ve B.M. = 0.0011 x 1000 x 4.05 x 4.05 x 4.05 x 10 = 719.985

Hoof tension Co. eff. = 0.5413 x 1000 x 4.05 x 4.25 x 10 = 93166.2

Min. depth required against cracking


D ( 6 x 6506.64 x 1000 ) 0.50

( 2 x 1000 )

= 139.71 mm

4
Thickness of side wall provided is 150 mm Hence safe
Using 10 mm dia. RTS
Effective depth = 150 - 45 - 5 = 100 mm
Vertical reinforcement for
Max. -ve B.M. = 6506.6 x 1000 = 581.98885 mm2
130 x 0.86 x 100

Max. +ve B.M. = 719.99 x 1000 = 64.399403 mm2


130 x 0.86 x 100

Min. area of steel required according to IS 3370


= 0.24 x 1000 x 150 = 360 mm2
100
in each of two direction at right angles within each surface zone

Provide 12 mm RTS Inner face ( Water face ) - Vertical rod 113


Spacing = 1000 x 113 = 194.162 mm say 180 mm c/c 628 mm2
582

Provide 10 mm RTS Outer face - Vertical rod


Spacing = 1000 x 78.54 = 1219.58 mm say 200 mm c/c 393 mm2
64.4
Steel area for hoop tension = 93166.2 = 716.7 mm2
130
Ast required for one face = 358.332 mm2

Provide 10 mm RTS Circumferentially


Spacing = 1000 x 78.54 = 219.182 mm say 180 mm c/c 436 mm2
358.3
Result:-
Thickness :- 150 mm
Vertical rod inner - Provide 12 mm RTS mm dia RTS @ 180 mm c/c.
Vertical rod outer - 10 mm dia RTS @ 200 mm c/c.
Hoop rod 10 mm dia RTS @ 180 mm c/c.
Haunch size : 180 X 180 mm.
Haunch rod 10 mm dia RTS @ 80 mm c/c.