You are on page 1of 3

DESIGN AND MANUFACTURE OF

480 VOLT VARIABLE FREQUENCY DRIVES


ELECTRICAL DEPARTMENT

DATA SHEET PAGE 1 OF 3

1 Facility Name/Location:      


2 Item Name:       Purchaser Project Number:      
3 Item Tag Number: LVVFD Purchase Order Number:      
4 Supplier:       Supplier Project Number:      
5 Applicable To: Proposal Purchase As Built
6 Supplier Data Legend: O = Optional Extra Cost (Provide Cost) NA = Not Available
7 One Line Diagram No.       Description of Load      
8 Remarks:
9 1. The site requirement section of application data shall be completed by Purchaser.
10 2. Site requirement shall supersede Purchaser standard.
11 3. If no site requirement is specified, standard requirement shall apply.
12 4. Supplier data section shall be completed by supplier and returned with bid. Quantitative
13 5.data shall be provided. Operational and performance data shall be based on input, output, environmental, and
14 load characteristics
specified and shall include effects of harmonic reducing equipment, such as line reactors.
15 GENERAL
16 Purchaser Requirements Supplier Data
17 Standard Site Standard O NA
18 1.UL Listed YES            
19
20 ENVIRONMENTAL CONDITIONS
21 Purchaser Requirements Supplier Data
22 Standard Site Standard O NA
23 2.Elevation, ft 3300            
24 3.Temperature Range, C 0 to 40            
25 4.Humidity (Non-Condens), % 0 to 90            
26 5.Max Vibration, G 0.5            
27
28 SUPPLY POWER CHARACTERISTICS
29 Purchaser Requirements Supplier Data
30 Standard Site Standard O NA
31 6.Nominal Line Voltage 480 VAC/3 Ph/60 Hz            
32 7.Power Configuration Wye W/High-Res Gnd            
33 8.Voltage Tolerance, +% 10            
34 9.Frequency Tolerance, +Hz 2            
35 10. Total 10            
36 Harmon.
11. Distortion, % Highest 5            
37 12.Single Harmonic, % Power 0.8            
38 13.Factor, Lagging Available                  
39 Short Circuit,
Current (Rms Sym), kA                  
40
41
42 No. Date Revision By Apvd
43                       
44                       
45                       
46                       

3/97 PAGE ____ OF ____


DESIGN AND MANUFACTURE OF
480 VOLT VARIABLE FREQUENCY DRIVES
ELECTRICAL DEPARTMENT

DATA SHEET PAGE 2 OF 3

1 MOTOR DATA
2 Purchaser Requirements Supplier Data
3 Standard Site Standard O NA
4 1.Motor Tag Number                  
5 2.Driven Equipment                  
6 3.Nameplate Horsepower                  
7 4.Utilization Voltage 460 VAC, 3 Ph            
8 5.Synchronous Speed, rpm                  
9 6.Full Load Amps (FLA)                  
10 7.Locked Rotor Amps (LRA)                  
11 8.NEMA Design B            
12 9.Temperature Rise, C 80            
13 10. Insulation F            
14 11.Class Service 1.15            
15 12.Factor Distance                  
16 From VFD to Motor
17 SYSTEM FEATURES
18 Purchaser Requirements Supplier Data
19 Standard Site Standard O NA
20 13. Adjust. 1-30            
21 14.Accel Rate, Hz/sec Adjust 1-30            
22 15.Decel Rate, Hz/sec Critical 3            
23 16.Frequency Lockout Slip Required            
24 17.Compensation Automatic Required            
25 18.Torque Boost Carrier 2 to 8            
26 19.Freq Range, kHz Adjustable Required            
27 Min/Max Speed
28 PERFORMANCE DATA
29 Purchaser Requirements Supplier Data
30 Standard Site Standard O NA
31 20. Acceptable None            
32 21.Line Notching Adjustable 3-12            
33 22.V/Hz Range V/Hz 2            
34 23.Regulation, +% Output 0-400            
35 25.Frequency Range, Hz Frequency 0.5            
36 26.Stability, +% Frequency 0.01            
37 27.Resolution, Hz Total Refer to Spec            
38 28.Harmonic Distortion Highest Refer to Spec            
39 29.Single Harmonic Eff at Full 95 Minimum            
40 30.Load/Full Speed, % Power 0.95 or Better            
41 31.Factor Total                  
42 System MTBF, hr
     
43      
44      
45      
46

3/97 PAGE ____ OF ____


DESIGN AND MANUFACTURE OF
480 VOLT VARIABLE FREQUENCY DRIVES
ELECTRICAL DEPARTMENT

DATA SHEET PAGE 3 OF 3

1 CUSTOMER INPUTS
2 Purchaser Requirements Supplier Data
3 Standard Site Standard O NA
4 1.Start Forward Dry Contact Input            
5 2.Start Reverse Dry Contact Input            
6 3.Stop Dry Contact Input            
7 4.Speed Control Signal, mA 4-20            
8 5.Fault Reset Not Required            
9 6.Run Indication Req (From C SPDT)            
10 7.Common Fault Alarm Req (From C SPDT)            
11 8.Common Failure Alarm Req (From C SPDT)            
12 9.Output Speed/Frequency, mA Required (4-20)            
13 10. Output Not Required            
14 Current PHYSICAL DATA
15 Purchaser Requirements Supplier Data
16 Standard Site Standard O NA
17 11. Outline                  
18 12.Dimens, H x W x D, in. Weight, lb                  
19 13. Heat                  
20 14.Dissipation, Btu NEMA 1            
21 15.Rating of Enclosure Mounting Wall Mount            
22 16.Configuration Cable                  
23 Entry (Top or Bottom) OPTIONAL METERING (SPECIFY ANALOG OR DIGITAL)
24 Purchaser Requirements Supplier Data
25 Standard Site Standard O NA
26 17. 3 PH Input                  
27 Current,
of Motor 0-150%
FLA
28 18. 3 PH Input                  
29 19.Volt, 0-600 VAC 3 PH                  
30 Output
of MotorCurrent,
FLA 0-150%
31 20. kW Meter, 1            
32 0-150%
kW Rating of Motor
33 21. kW-hr                  
34 22.Meter Elapsed                  
35 Time Meter OTHER OPTIONS
36 Purchaser Requirements Supplier Data
37 Standard Site Standard O NA
38 23. Input Circ Circuit Breaker            
39 24.Break or Fused Discon Full Not Required            
40 25.Voltage Bypass PID Not Required            
41 27.Controller P/I Not Required            
42 Transducer for Signal
Speed Control Pneumatic
43 28. Space Not Required            
44 29.Heaters Start-up                  
45 30.Assistance Serial                  
46 31.Comm (RS 232 etc. Integral Not Required            
A/C

3/97 PAGE ____ OF ____