PROVISION OF EPC SERVICE FOR FIELD

CONTROL CENTER FOR MAJNOON


OPERATION CENTER PROJECT

DETAIL DESIGN FOCP-FCC-CJI-EA-2015-0003 REV.: 004 PAGE 1 OF 5

DATA SHEET
FOR
AC UNINTERRUPTIBLE POWER SUPPLIES

004 ISSUED FOR AS-BUILT 24.07.2020 XU DD LI Q LIU XM WANG YT

003 ISSUED FOR CONSTRUCTION 25.03.2020 XU DD LI Q LIU XM WANG YT

002 ISSUED FOR CONSTRUCTION 09.12.2019 XU DD LI Q LIU XM WANG YT

001 ISSUED FOR APPROVAL 24.10.2019 XU DD LI Q LIU XM WANG YT

REV. DESCRIPTION DATE PREP'D CHK'D REV'D APP'D


STAGE DETAIL DESIGN
PROVISION OF EPC SERVICE FOR FIELD
PROJECT CONTROL CENTER FOR MAJNOON DOC.NO. FOCP-FCC-CJI-EA-2015-0003
OPERATION CENTER PROJECT
PAGE NO. 2 OF 5

DOCUMENT DATA SHEET FOR AC UNINTERRUPTIBLE POWER SUPPLIES REV.: 004

MANUFACTURER: SERVICE: EQUIPMENT NO.: QTY:

DESIGAN LIFE: SIZE:


1 INFORMATION
2 A APPLICABLE SPECIFICATION & STANDARD MAJ-0066-FOC-01-ELE-SPC-0003
3 SPECIFICATION FOR AC UNINTERRUPTIBLE POWER SUPPLIES
4 MAJ-0066-FOC-01-ELE-DWG-0001
5
6 B QUANTITY 1 SET
7
8 C CLIMATIC CONDITIONS
9 1 AMBIENT TEMPERATURE -4~54℃
10 2 ALTITUDE ( ABOVE MSL ) 4~10 Mtrs. AVERAGE SEA LEVEL
11 3 RELATIVE HUMIDITY 16.8 to 65.9 %
12 4 ATMOSPHERE DUST LADEN
13
14 D SYSTEM PARTICULARS
15 1 VOLTAGE 400 V ± 10 %
16 2 FREQUENCY 50 Hz ± 5 %
17 3 NO. OF PHASES / WIRE 3 PHASE / 4 WIRE
18 4 SYSTEM GROUNDING SOLID GROUND
19 5 FAULT LEVEL 50 kA, 3-Ph, SYMM.
20
21 E INPUT CHARACTERISTICS
22 1 NUMBERS OF SUPPLY 2 MAINS AND 1 BYPASS
23 2 MAIN INPUT RATED VOLTAGE 3PH / 400V±10%
24 3 BYPASS INPUT RATED VOLTAGE 3PH / 400V±10%
25 4 POWER FACTOR 0.8
26 5 INPUT POWER BY VENDOR
27 6 RATED FREQUENCY 50Hz±5%
28 7 FAULT LEVEL 25kA
29 8 METHOD OF SYSTEM EARTHING TN-S
30 9 SURGE ARRESTOR REQUIRED
31
32 F OUTPUT CHARACTERISTICS
33 1 RATED OUTPUT POWER 1 SET 60kVA
34 2 BACKUP TIME AT FULL LOAD GAS FIRE EXTINGGUISHING SYSTEM : 4 HOUR
35 OTHERS : 1 HOUR
36 3 OUTPUT VOLTAGE / NUNBER OF PHASES 380/400/415V±2%
37 4 FAULT CURRENT 25kA FOR 1S
38 5 RATED FREQUENCY 50Hz±1%
39 6 OUTPUT CURRENT BY VENDOR
40 7 CHANGEOVER TIME ≤5ms
41 8 METHOD OF SYSTEM EARTHING TN-S
42 9 OVERALL EFFICIENCY OF FULL LOAD BY VENDOR
43 10 COMMON ALARM (VOLT FREE CONTACT) REQUIRED
44
45 G DISTRIBUTION SYSTEM
46 1 TYPE OF INPUT SWITCH MCCB
47 2 TYPE OF OUTPUT SWITCH MCB
48 3 NUMBER OF POLES OF OUTPUT SWITCH 3P
49 4 RATED CURRENT PER CIRCUIT MAJ-0066-FOC-01-ELE-DWG-0001
50 5 LOAD TYPE EQUIPMENTS OF INSTRUMENT AND COMMUNICATION
51
52 H CHARGER - RECTIFIER
53 1 TYPE IGBT
54 2 RECTIFIER QUANTITY 2
55 3 RUNNING MODE PARALLEL
56 4 RECTIFIER 1 CHARGER
57 5 COOLING FORCED
58 6 RECTIFIER 2 CHARGER
59 7 RATED POWER (FLOATING MODE) BY VENDOR
60 8 INPUT PEAK CURRENT BY VENDOR
61 9 OUTPUT RATED DC CURRENT BY VENDOR
62 10 OUTPUT DC VOLTAGE BY VENDOR
63
STAGE DETAIL DESIGN
PROVISION OF EPC SERVICE FOR FIELD
PROJECT CONTROL CENTER FOR MAJNOON DOC.NO. FOCP-FCC-CJI-EA-2015-0003
OPERATION CENTER PROJECT
PAGE NO. 3 OF 5

DOCUMENT DATA SHEET FOR AC UNINTERRUPTIBLE POWER SUPPLIES REV.: 004

MANUFACTURER: SERVICE: EQUIPMENT NO.: QTY:

DESIGAN LIFE: SIZE:


1 INFORMATION
2 11 FLOATING VOLTAGE BY VENDOR
3 12 BOOSTING VOLTAGE BY VENDOR
4 13 EQUALIZING VOLTAGE BY VENDOR
5 14 RIPPLE VOLTAGE 1%
6 15 RECTIFIER EFFICIENCY BY VENDOR
7 16 RECTIFIER POWER FACTOR BY VENDOR
8 17 RECTIFIER ON/OFF SWITCH BY VENDOR
9 18 INPUT ON/OFF SWITCH BY VENDOR
10 19 MANU/AUTO SELECTOR BY VENDOR
11 (FLOATING/BOOSTING/EQUALIZING)
12 20 BOOST OPERATION DURATION TIMER REQUIRED
13 21 BATTERY ISOLATION SWITCH MCCB 2P
14 22 DC OUTPUT VOLTAGE ADJUSTMENT BY VENDOR
15 23 DC CURRENT LIMIT ADJUSTMENT BY VENDOR
16 24 AC INPUT VOLTAGE METER REQUIRED
17 25 DC OUTPUT V/A METER REQUIRED
18 26 BATTERY VOLTAGE/CURRENT METER REQUIRED
19 27 INDICATION
20 27.1 MAINS ON INDICATION REQUIRED
21 27.2 RECTIFIER RUNNING REQUIRED
22 27.3 OPERATION MODE REQUIRED
23 (FLOATING/EQUALIZING/BOOST)
24 27.4 OPERATION ON BATTERY REQUIRED
25 27.5 EQUALIZING/BOOST INHIBITION REQUIRED
26 27.6 IMMINENT DISCHARGED BATTERY REQUIRED
27 28 INDICATION AND ALARM
28 28.1 MAINS FAILURE REQUIRED
29 28.2 DC OUTPUT FAILURE REQUIRED
30 28.3 DC OVERVOLTAGE/UNDERVOLTAGE REQUIRED
31 28.4 RECTIFIER OVER-CURRENT REQUIRED
32 28.5 BATTERY OVER-CURRENT REQUIRED
33 28.6 DC EARTH FAULT REQUIRED
34 28.7 COOLING FAN FAILURE REQUIRED
35
36 I INVERTER
37 1 TYPE IGBT
38 2 PWM TECHNOLOGY REQUIRED
39 3 INVERTER QUANTITY 2
40 4 OPERATION MODE PARALLEL
41 5 RATED OUTPUT POWER 1 SET 60kVA
42 6 COOLING FORCED
43 7 OUTPUT STEADY VOLTAGE ±1%
44 8 OUTPUT TRANSIENT VOLTAGE <±5%
45 9 OUTPUT STEADY FREQUENCY ±1%
46 10 OUTPUT TRANSIENT FREQUENCY <±2%
47 11 OUTPUT VOLTAGE HARMONIC WAVE <2%
48 LINEAR/ NON-LINEAR
49 12 ALLOWABLE OVERLOAD AT NORMAL 120% FOR 3MIN
50 CONDITIONS
51 13 ALLOWABLE OVERLOAD AT EMERGENCY 150% FOR 1MIN
52 CONDITIONS
53 14 INVERTER EFFICIENCY BY VENDOR
54 15 STATIC SWITCH REQUIRED
55 16 INVERTER ON/OFF SWITCH REQUIRED
56 17 AC OUTPUT VOLTAGE ADJUSTMENT BY VENDOR
57 18 MANUAL/ AUTOMATIC SELECTOR REQUIRED
58 19 AC OUTPUT VOLTAGE ADJUSTMENT REQUIRED
59 20 MANUAL/ AUTOMATIC SELECTOR REQUIRED
60 21 AC OUTPUT V/A METER REQUIRED
61 22 AC OUTPUT FREQUENCY METER REQUIRED
62 23 BYPASS INPUT VOLTAGE METER REQUIRED
63
STAGE DETAIL DESIGN
PROVISION OF EPC SERVICE FOR FIELD
PROJECT CONTROL CENTER FOR MAJNOON DOC.NO. FOCP-FCC-CJI-EA-2015-0003
OPERATION CENTER PROJECT
PAGE NO. 4 OF 5

DOCUMENT DATA SHEET FOR AC UNINTERRUPTIBLE POWER SUPPLIES REV.: 004

MANUFACTURER: SERVICE: EQUIPMENT NO.: QTY:

DESIGAN LIFE: SIZE:


1 INFORMATION
2 24 INVERTER ON INDICATION REQUIRED
3 25 LOAD ON INVERTER/BYPASS INDICATION REQUIRED
4 26 INDICATION AND ALARM REQUIRED
5 26.1 AC OUTPUT FAILURE REQUIRED
6 26.2 OUTPUT OVERVOLTAGE / UNDERVOLTAGE REQUIRED
7 26.3 OUTPUT OVERLOAD REQUIRED
8 26.4 OUTPUT OVERCURRENT REQUIRED
9 26.5 BACKUP SUPPLY FAULT REQUIRED
10 26.6 FORCED COOLING FAILURE REQUIRED
11 26.7 AC EARTH FAULT REQUIRED
12 26.8 OVERTEMPERATURE REQUIRED
13 26.9 OVERFREQUENCY / UNDERFREQUENCY REQUIRED
14 27 VOLTAGE RECOVERY TIME BY VENDOR
15 28 POWER FACTOR 0.8
16
17 J SIGNAL SYSTEM COMPONENTS
18 1 TYPE CRYSTAL DISPLAY
19 2 LAMP TEST PUSHBUTTON REQUIRED
20 3 FAULT RESET PUSHBUTTON REQUIRED
21 4 SERIAL LINK COMMUNICATION ■PROTOCOL IEC61850 / RJ45
22 5 MIMIC DIAGRAM REQUIRED
23 6 GROUP BATTERY MONITORING REQUIRED
24
25 K CUBICLE GENERAL CHARACRISTICS
26 1 ACCESS FRONT/REAR
27 2 CABLE ENTRY TOP
28 3 OVERALL DIMENSION (H/W/D) BY VENDOR
29 4 OVERALL WEIGHT BY VENDOR
30 5 DEGREE OF PROTECTION IP20
31 6 PAINTING EPOXY RAL7032
32 7 COOLING FORCED
33 8 EMISSION BY VENDOR
34 9 NOISE LEVEL (AT CONDITION OF NO LOAD <68 dB
35 AND 1m POINT)
36 10 MIN SIDE CLEARANCE BY VENDOR
37 11 MIN BEHIND CLEARANCE BY VENDOR
38 12 WORK STYLE TWO EQUIPMENTS IN PARALLEL BY REDUNDANT
39
40 L BATTERY
41 1 TYPE lead-acid battery
42 2 QUANTITY 2 X 100%
43 3 RATED VOLTAGE / CELL BY VENDOR
44 4 NUMBER OF CELLS PER SET BY VENDOR
45 5 CELL BOOSTING VOLTAGE BY VENDOR
46 6 CELL EQUALIZING VOLTAGE BY VENDOR
47 7 CELL FLOATING VOLTAGE BY VENDOR
48 8 TIM FOR FULLY CHARGED CAPACITY 8-10HOURS
49 9 END VOLTAGE OF DISCHARGE AT 20℃ BY VENDOR
50 10 TIME OF BOOST UP TO 100% CAPACITY BY VENDOR
51 11 MAXIMUM STORAGE TIME BEFORE FIRST BY VENDOR
52 CHARGING OF BATTERY
53 12 BATTERY POSITION SEPARATE RACK OR CABINET IN SEPARATE ROOM
54
55 M BYPASS DEVICE
56 1 TYPE OF INPUT SWITCH MCCB
57 2 INPUT SUPPLY 400V 3PH
58 3 OUTPUT SUPPLY 380/400/415V
59 4 REGULATED TRANSFORMER REQUIRED
60 5 STATIC SWITCH REQUIRED
61 6 BYPASS INPUT VOLTAGE METER REQUIRED
62
STAGE DETAIL DESIGN
PROVISION OF EPC SERVICE FOR FIELD
PROJECT CONTROL CENTER FOR MAJNOON DOC.NO. FOCP-FCC-CJI-EA-2015-0003
OPERATION CENTER PROJECT
PAGE NO. 5 OF 5

DOCUMENT DATA SHEET FOR AC UNINTERRUPTIBLE POWER SUPPLIES REV.: 004

MANUFACTURER: SERVICE: EQUIPMENT NO.: QTY:

DESIGAN LIFE: SIZE:


1 INFORMATION
2 7 BYPASS OUTPUT VOLTAGE METER REQUIRED
3 8 BYPASS AVAILABLE INDICATION REQUIRED
4
5 N CABLE
6 1 AC SUPPLY CABLE TYPE / SIZE MAJ-0066-FOC-01-ELE-DWG-0001
7 2 BETWEEN BATTERY AND RECTIFIER BY VENDOR
8 3 BETWEEN BYPASS AND INVERTER BY VENDOR
9 4 AC FEEDER CABLE TYPE/SIZE MAJ-0066-FOC-01-ELE-DWG-0001
10 5 CABLE ENTRANCE TOP
11
12 O DRAWINGS & OTHER INFORMATION : AS PER SPECIFICATION
13
14 P NAME PLATES, LABLES AND THEIR FIXING : AS PER SPECIFICATION / IEC
15 MATERIALS
16
17 Q TESTS & INSPECTION : AS PER SPECIFICATION / IEC
18
19 R DISTRIBUTION DETAILS : MAJ-0066-FOC-01-ELE-DWG-0001
20
21 S MAKE OF EQUIPMENT : APPROVED BY PURCHASER
22
23 T FITTINGS & ACCESSORIES : SPECIAL TOOL KIT, FIXING ACCESSORIES,
24 SPARE PARTS
25
26 U NOTE
27 1. THE UPS SYSTEM SHALL BE DESIGNED FOR 40 oC DESIGN ENVIRONMENT TEMPERATURE. HOWEVER, EACH UPS BATTERY SHALL BE DESIGNED
28 TO PROVIDE THE SPECIFIED POWER FOR GAS FIRE EXTINGGUISHING SYSTEM : 4 HOUR AND FOR OTHERS: 1HOUR
BACKUP AT 100% LOADING CONDITION.
29 2. THE UPS SYSTEM SHALL BE AS PER ONE LINE DIAGRAMS MAJ-0066-FOC-01-ELE-DWG-0001 .
30 3. A LCD DISPLAY SHOULD BE REQUIRED C/W MIMIC FOR INDICATIONS, MESSAGES AND DIAGNOTICS.IEC 61850/RJ45 INTERFAC PORT SHOULD
31 BE REQUIRED.
32 4. THE COMMON ALARM SHOULD BE REQUIRED.
33 5. THE ITEMS NEED TO BE CONFIRMED BY VENDOR SHALL REFER TO VENDORS AS-BUILT DOCUMENTS.
34 6. UPS SHALL BE EMC COMPLIANT.
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62