Professional Documents
Culture Documents
AC VOLTAGE CONTROLLER
INTRODUCTION
AC voltage controllers (ac line voltage controllers) are employed to vary the RMS
value of the alternating voltage applied to a load circuit by introducing Thyristors
between the load and a constant voltage ac source.
The RMS value of alternating voltage applied to a load circuit is controlled by
controlling the triggering angle of the Thyristors in the ac voltage controller
circuits.
In brief, an ac voltage controller is a type of thyristor power converter which is used
to convert a fixed voltage, fixed frequency ac input supply to obtain a variable
voltage ac output.
The RMS value of the ac output voltage and the ac power flow to the load is
controlled by varying (adjusting) the trigger angle ‘’
V0(RMS)
AC Vs AC Variable AC
Input Voltage RMSO/P Voltage
Voltage fs Controller
fs fS
Fig.1
The ac voltage controllers are classified into two types based on the type of input ac supply
applied to the circuit.
Single Phase AC Controllers.
Three Phase AC Controllers.
Single phase ac controllers operate with single phase ac supply voltage of 230V RMS at
50Hz in our country.
Three phase ac controllers operate with 3 phase ac supply of 400V RMS at 50Hz supply
frequency.
Each type of controller may be sub divided into
Uni-directional or half wave ac controller.
Bi-directional or full wave ac controller.
In brief different types of ac voltage controllers are
Single phase half wave ac voltage controller (uni-directional controller).
Single phase full wave ac voltage controller (bi-directional controller).
Three phase half wave ac voltage controller (uni-directional controller).
1
Three phase full wave ac voltage controller (bi-directional controller).
There are two different types of thyristor control used in practice to control the ac power
flow
Phase control
On-Off control
These are the two ac output voltage control techniques.
In On-Off control technique Thyristors are used as switches to connect the load circuit to
the ac supply (source) for a few cycles of the input ac supply and then to disconnect it for
few input cycles.
The Thyristors thus act as a high speed contactor (or high speed ac switch).
By controlling the phase angle or the trigger angle ‘’ (delay angle), the output
RMS voltage across the load can be controlled.
The trigger delay angle ‘’ is defined as the phase angle (the value of t) at which
the thyristor turns on and the load current begins to flow.
Thyristor ac voltage controllers use ac line commutation or ac phase commutation.
Thyristors in ac voltage controllers are line commutated (phase commutated) since
the input supply is ac.
When the input ac voltage reverses and becomes negative during the negative half
cycle the current flowing through the conducting thyristor decreases and falls to
zero.
Thus the ON thyristor naturally turns off, when the device current falls to zero.
2
Phase control Thyristors which are relatively inexpensive, converter grade
Thyristors which are slower than fast switching inverter grade Thyristors are
normally used.
For applications up to 400Hz, if Triacs are available to meet the voltage and current
ratings of a particular application, Triacs are more commonly used.
Due to ac line commutation or natural commutation, there is no need of extra
commutation circuitry or components and the circuits for ac voltage controllers are
very simple.
Due to the nature of the output waveforms, the analysis, derivations of expressions
for performance parameters are not simple, especially for the phase controlled ac
voltage controllers with RL load.
But however most of the practical loads are of the RL type and hence RL load
should be considered in the analysis and design of ac voltage controller circuits.
EQUATIONS:
3
vs Vm sin t
Vm
VS Vin RMS = RMS value of secondary supply voltage.
2
vo vL 0 ; for t 0 to
vo vL Vm sin t ; for t to 2 .
vo Vm sin t
io iL ; for t to 2 .
RL RL
io iL 0 ; for t 0 to .
2
1
Vm sin t.d t
2 2
VO RMS
2
Vm 2 2 1 cos 2 t
VO RMS .d t
2 2
Vm 2 2
VO RMS 1 cos 2t .d t
4
Vm 2 2
VO RMS d t cos 2 t.d t
2
2 2
V sin 2 t
VO RMS m t
2 2
2
sin 2 t
2
V
VO RMS m
2 2
4
sin 4 sin 2
2
Vm
VO RMS ;sin 4 0
2 2 2
Vm sin 2
VO RMS 2
2 2
Vm sin 2
VO RMS 2
2 2 2
Vm 1 sin 2
VO RMS 2
2 2 2
1 sin 2
VO RMS Vi RMS 2
2 2
1 sin 2
VO RMS VS 2
2 2
Vm
Where, Vi RMS VS = RMS value of input supply voltage (across the transformer secondary
2
winding).
Note: Output RMS voltage across the load is controlled by changing ' ' as indicated by
the expression for VO RMS
2
Vm
VO dc
2 sin t.d t
2
V
VO dc m cos t
2
Vm
VO dc cos 2 cos ; cos 2 1
2
5
Vm
Vdc cos 1 ; Vm 2VS
2
2VS
Hence Vdc cos 1
2
Vm
When ' ' is varied from 0 to . Vdc varies from 0 to
Problem.1
A single phase half-wave ac voltage controller has a load resistance R 50 , input ac
supply voltage is 230V RMS at 50Hz. The input supply transformer has a turns ratio of 1:1.
If the thyristor T1 is triggered at 600 . Calculate
RMS output voltage.
Output power.
RMS load current and average load current.
Input power factor.
Average and RMS thyristor current.
GIVEN:
6
Vp Np 1
1
VS NS 1
Therefore Vp VS 230V
TO FIND:
2
1
VO RMS V
2
sin 2 t.d t
2
m
1 sin 2
VO RMS VS 2
2 2
1 sin1200
VO RMS 230 2
2 3 2
1
VO RMS 230 5.669 230 0.94986
2
7
VO RMS 218.46966
I O RMS 4.36939 Amps
RL 50
PO 0.9545799 KW
954.5799 W
PF 0.9498
230 4.36939 W
Average Output (Load) Voltage
2
1
VO dc Vm sin t.d t
2
We have obtained the expression for the average / DC output voltage as,
Vm
VO dc cos 1
2
2 230
cos 600 1
325.2691193
VO dc 0.5 1
2 2
325.2691193
VO dc 0.5 25.88409 Volts
2
8
iT1
Im
2 3
(2+) t
Referring to the thyristor current waveform of a single phase half-wave ac voltage controller
circuit, we can calculate the average thyristor current IT Avg as
1
IT Avg I m sin t.d t
2
Im
IT Avg sin t.d t
2
I
IT Avg m cos t
2
Im
IT Avg cos cos
2
Im
IT Avg 1 cos
2
Vm
Where, I m = Peak thyristor current = Peak load current.
RL
2 230
Im
50
I m 6.505382 Amps
Vm
IT Avg 1 cos
2 RL
2 230
IT Avg 1 cos 600
2 50
9
2 230
IT Avg 1 0.5
100
I m2 1 cos 2 t
IT RMS .d t
2 2
I m2
IT RMS cos 2t.d t
d t
4
1 sin 2t
IT RMS I m t
4 2
1 sin 2 sin 2
IT RMS I m
4 2
1 sin 2
IT RMS I m
4 2
Im 1 sin 2
IT RMS
2 2 2
IT RMS
2 2 3 2
1 2 0.8660254
IT RMS 4.6
2 3 2
10
PRINCIPLE OF ON-OFF CONTROL TECHNIQUE (INTEGRALCYCLE CONTROL)
(OR)
OPERATION OF SINGLE PHASE FULL WAVE AC VOLTAGE CONTROLLER
WITH R LOAD.
The basic principle of on-off control technique is explained with reference to a single phase full
wave ac voltage controller circuit shown below.
The thyristor switches T1 and T2 are turned on by applying appropriate gate trigger pulses
to connect the input ac supply to the load for ‘n’ number of input cycles during the time
interval tON .
The thyristor switches T1 and T2 are turned off by blocking the gate trigger pulses for ‘m’
number of input cycles during the time interval tOFF .
The ac controller ON time tON usually consists of an integral number of input cycles.
R RL = Load Resistance
11
Vs n m
wt
Vo
io
wt
wt
ig2 Gate pulse of T2
wt
Fig.3: Waveforms
Example
n Two input cycles. Thyristors are turned ON during tON for two input cycles.
m One input cycle. Thyristors are turned OFF during tOFF for one input cycle
Thyristors are turned ON precisely at the zero voltage crossings of the input supply.
12
The thyristor T1 is turned on at the beginning of each positive half cycle by applying the
gate trigger pulses to T1 as shown, during the ON time tON .
The load current flows in the positive direction, which is the downward direction as shown
in the circuit diagram when T1 conducts.
The thyristor T2 is turned on at the beginning of each negative half cycle, by applying
gating signal to the gate of T2 , during tON .
The load current flows in the reverse direction, which is the upward direction when T2
conducts.
Thus we obtain a bi-directional load current flow (alternating load current flow) in a ac
voltage controller circuit, by triggering the thyristors alternately.
This type of control is used in applications which have high mechanical inertia and high
thermal time constant (Industrial heating and speed control of ac motors).
Due to zero voltage and zero current switching of Thyristors, the harmonics generated by
switching actions are reduced.
For a sine wave input supply voltage,
Vm
VS RMS value of input ac supply = = RMS phase supply voltage.
2
If the input ac supply is connected to load for ‘n’ number of input cycles and
disconnected for ‘m’ number of input cycles, then
tON n T , tOFF m T
1
Where T = input cycle time (time period) and
f
tON t
We can show that, Output RMS voltage VO RMS Vi RMS VS ON
TO TO
13
Where Vi RMS is the RMS input supply voltage = VS .
t
1 ON 2 2
V Sin t.d t
TO t0 m
Output RMS voltage VO RMS
tON
Vm 2
VO RMS Sin 2 t.d t
TO 0
1 Cos 2
Substituting for Sin2
2
tON
Vm 2 1 Cos 2 t
VO RMS
TO 2 d t
0
Vm 2 tON tON
VO RMS Cos 2 t.d t
d t
2TO 0 0
tON tON
Vm 2 Sin2t
VO RMS t
2TO 0
2 0
Where T is the input supply time period (T = input cycle time period). Thus we
note that sin 2 tON 0
Vm 2 tON Vm tON
VO RMS
2 TO 2 TO
tON t
VO RMS Vi RMS VS ON
TO TO
14
Vm
Where Vi RMS VS = RMS value of input supply voltage;
2
tON tON nT n
k = duty cycle (d).
TO tON tOFF nT mT n m
n
VO RMS VS V k
m n S
PERFORMANCE PARAMETERS OF AC VOLTAGE CONTROLLERS:
Vm n
VO RMS V k VS k
2 m n i RMS
2. Duty Cycle:
t tON nT
k ON
TO tON tOFF m n T
n
Where, k = duty cycle (d).
m n
3. RMS Load Current:
VO RMS VO RMS
I O RMS ; for a resistive load Z RL .
Z RL
15
I O2 RMS RL
PF ; I S I in RMS RMS input supply current.
Vi RMS I in RMS
Hence, RMS supply current = RMS load current; I in RMS I O RMS .
n
PF k
mn
0 2 3 t
n
I m sin t.d t
2 m n 0
IT Avg
nI m
sin t.d t
2 m n 0
IT Avg
nI m
IT Avg cos t
2 m n 0
nI m
IT Avg cos cos 0
2 m n
nI m
IT Avg 1 1
2 m n
n
IT Avg 2I m
2 m n
16
Imn k.I
IT Avg m
m n
tON n
k duty cycle
tON tOFF n m
Imn k.I
IT Avg m ,
m n
Vm
Where I m = maximum or peak thyristor current.
RL
IT RMS mI 2
sin 2
t .d t
2 n m 0
1
nI m2
2
IT RMS
2 n m 0 2
1
nI m2
2
IT RMS t
4 n m 0 2 0
1
nI m2 sin 2 sin 0
2
IT RMS 0
4 n m 2
1
nI m2 2
IT RMS 0 0
4 n m
17
1 1
nI m2 2
nI m2 2
IT RMS
4 n m 4 n m
Im n I
IT RMS m k
2 m n 2
Im
IT RMS k
2
PROBLEM 1
A single phase full wave ac voltage controller working on ON-OFF control technique has
supply voltage of 230V, RMS 50Hz, load = 50. The controller is ON for 30 cycles and off
for 40 cycles. Calculate
1. ON & OFF time intervals.
2. RMS output voltage.
3. Input P.F.
4. Average and RMS thyristor currents.NOV/DEC-12
GIVEN:
F=50Hz, R= 50. Vin RMS 230V , m 40 n 30 .
TO FIND:
1. ON & OFF time intervals.
2. RMS output voltage.
3. Input P.F.
4. Average and RMS thyristor currents
SOLUTION:
Vin RMS 230V , Vm 2 230V 325.269 V, Vm 325.269V ,
1 1
T 0.02sec , T 20ms .
f 50 Hz
18
n 30
Duty cycle k 0.4285
m n 40 30
RMS output voltage:
n
VO RMS Vi RMS
m n
30 3
VO RMS 230V 230
30 40 7
n 30
PF 0.4285
m n 70
PF 0.654653
Im n k Im
IT Avg
m n
Vm 2 230 325.269
where Im
RL 50 50
6.505382 3
IT Avg
7
19
IT Avg 0.88745 A
Im n I 6.505382 3
IT RMS m k
2 m n 2 2 7
IT RMS 2.129386 A
PROBLEM 2
A Single phase full wave AC voltage controller has an input voltage of 230V, 50Hz, and it is feeding
resistive load of 10 Ω. If firing angle of thyristor is 110degree. Find the output rms voltage, Input Power
Factor and Average current of thyristor. NOV/DEC-14
GIVEN:
TO FIND:
The output rms voltage, Input Power Factor and Average current of thyristor.
SOLUTION:
sin 2 1/ 2
V (rms) V [1/ ( )]
o S 2
1/ 2
sin 2(110 )
11
230 1 / ( )
18 2
1/ 2
= 230 1 ( 7 ) (0.3214 )
18
230 (0.0675 )1 / 2
20
RMS output voltage, V ( rms) 59.76V
o
V (rms) 59.76
I (rms) o
o R 10
Po I
2
(rms).R
o
= (5.98) 2 10
Po 357.6W
Since , input current is the same as the load current , the input V-A rating
1
P V Sin 2
PF o o 1 / ( ) 2
VA VS 2
Vs 2
IA (cos 1)
2R
2 230
(cos110 1)
2 10
I A 3.41A
21
Phase Controlled Single-Phase AC Voltage Controller with RL load.
The basic power circuit of a single-phase ac-ac voltage controller, as shown in Fig. 16.1a, is
composed of a pair of
22
For a full-wave, symmetrical phase control, the SCRs T1 and T2 in Fig. 16.1a are gated at α and
π+α, respectively, from the zero crossing of the input voltage and by varying α, the power flow to
the load is controlled through voltage control in alternate half-cycles. As long as one SCR is
carrying current, the other SCR remains reverse-biased by the voltage drop across the conducting
SCR. The principle of operation in each half-cycle is similar to that of the controlled half-wave
rectifier and one can use the same approach for analysis of the circuit.
Operation with R-load. Figure 16.2 shows the typical voltage and current waveforms for the
single-phase bidirectional phase-controlled ac voltage controller of Fig. 16.1a with resistive load.
The output voltage and current waveforms have half-wave symmetry and thus no dc component.
𝐼𝑓 𝑉𝑠 = √2𝑉𝑠 𝑠𝑖𝑛𝜔𝑡
23
is the source voltage, then the rms output voltage with T1 triggered at a can be found from the
half-wave symmetry as
1 1
1 𝜋 2 𝛼 𝑠𝑖𝑛2𝛼 2
𝑉0 = [ ∫ 2𝑉𝑠 2 𝑠𝑖𝑛2 𝜔𝑡 𝑑(𝜔𝑡)] = 𝑉𝑠 [1 − + ]
𝜋 𝛼 𝜋 2𝜋
Note that Vo can be varied from Vs to 0 by varying α from 0 to π. The rms value of load current:
𝑉0
𝐼0 =
𝑅
As each SCR carries half the line current, the rms current in each SCR is
𝐼0
𝐼0,𝑆𝐶𝑅 =
√2
of the SCR depends on the firing delay angle a and the load impedance angle .
24
Three-Phase AC to AC Voltage Controllers
25
Here, current can flow between two lines even if one SCR is conducting, so each SCR requires
one firing pulse per cycle. The voltage and current ratings of SCRs are nearly the same as those of
the circuit in Fig. 6.11b.
It is also possible to reduce the number of devices to three SCRs in delta as shown in Fig. 16.11f
connecting one source terminal directly to one load circuit terminal. Each SCR is provided with
gate pulses in each cycle spaced 1200 apart. In both Figs. 16.11e and f each end of each phase must
be accessible.
The number of devices in Fig. 16.11f is fewer but their current ratings must be higher. As in the
case of the single-phase phase-controlled voltage regulator, the total regulator cost can be reduced
by replacing six SCRs by three SCRs and three diodes, resulting in threephase half-wave controlled
unidirectional ac regulators as shown in Fig. 16.11g and h for star- and delta-connected loads.
The main drawback of these circuits is the large harmonic content in the output voltage,
particularly the second harmonic because of the asymmetry. However, the dc components are
absent in the line. The maximum firing angle in the half-wave controlled regulator is 2100.
26
27
Fully Controlled Three-Phase Three-Wire AC Voltage Controller Star-
Connected Load with Isolated Neutral
The analysis of operation of the full-wave controller with isolated neutral as shown in Fig. 16.11c
is, as mentioned, quite complicated in comparison to that of a single-phase controller, particularly
for an RL or motor load.
As a simple example, the operation of this controller is considered here with a simple star-
connected R-load. The six SCRs are turned on in the sequence 1-2-3-4-5-6 at 600 intervals and the
gate signals are sustained throughout the possible conduction angle.
The output phase voltage waveforms for 30, 75, and 1200 for a balanced three-phase R-load are
shown in Fig. 16.12. At any interval, either three SCRs or two SCRs, or no SCRs may be on and
the instantaneous output voltages to the load are either line-to-neutral voltages (three SCRs on), or
one-half of the line-to-line voltage (two SCRs on) or zero (no SCR on). Depending on the firing
angle a, there may be three
operating modes.
Mode I (also known as Mode 2=3): 00 and 600. There are periods when three SCRs are conducting,
one in each phase for either direction and periods when just two SCRs conduct. For example, with
300 in Fig. 16.12a, assume that at 00, SCRs T5 and T6 are conducting, and the current through the
R-load in a-phase is zero making van 0 At 300, T1 receives a gate pulse and starts conducting; T5
and T6 remain on and van . vAN.
The current in T5 reaches zero at 600, turning T5 off. With T1 and T6 staying on, van . 1=2v AB.
At 900, T2 is turned on, the three SCRs T1, T2, and T6 are then conducting and van . vAN. At 1200,
T6 turns off, leaving T1 and T2 on, so vAN . 1=2vAC. Thus with the progress of firing in sequence
until 600, the number of SCRs conducting at a particular instant alternates between two and three.
Mode II (also known as Mode 2/2): 600 to 900. Two SCRs, one in each phase, always conduct.
For 750 as shown in Fig. 16.12b, just prior to a 750, SCRs T5 and T6 were conducting and van 0
At 750, T1 is turned on, T6 continues to conduct while T5 turns off as vCN is negative; van . 1=2vAB.
When T2 is turned on at 1350, T6 is turned off and van . 1=2vAC. The next SCR to turn on is T3,
which turns off T1 and van . 0. One SCR is always turned off when another is turned on in this
range of a and the output is either one-half line-to-line voltage or zero.
28
Mode III (also known as Mode 0/2): 900 to1500. When none or two SCRs conduct.
For 1200 (Fig. 16.12c), earlier no SCRs were on and van 0. At 1200 SCR T1 is given
a gate signal while T6 has a gate signal already applied. As v AB is positive, T1 and
T6 are forward-biased and they begin to conduct and van . 1=2vAB. Both T1 and T6
turn off when vAB becomes negative. When a gate signal is given to T2, it turns on
and T1 turns on again. For a > 1500, there is no period when two SCRs are
conducting and the output voltage is zero at 1500.Thus, the range of the firing angle
control is 00 to 1500. For star-connected R-load, assuming the instantaneous phase
voltages as
𝑉𝐴𝑁 = √2𝑉𝑠 𝑠𝑖𝑛𝜔𝑡
29
𝑉𝐶𝑁 = √2𝑉𝑠 sin(𝜔𝑡-2400 )
The expressions for the rms output phase voltage 𝑉0 can be derived for the three modes as
1
3𝛼 3
0≤ α ≤ 60 0
𝑉0 = 𝑉𝑠 [1 − 2𝜋
+ 4𝜋
𝑠𝑖𝑛2𝛼]2
1
1 3 3
600 ≤ α ≤ 900 𝑉0 = 𝑉𝑠 [2 + 4𝜋 𝑠𝑖𝑛2𝛼 + 4𝜋 sin(2𝛼 + 600 ]2
1
5 3 3 2
900 ≤ α ≤ 1500 𝑉0 = 𝑉𝑠 [4 − 2𝜋 + 4𝜋 sin(2𝛼 + 600 ]
For star-connect pure L-Load the effective control starts at α>900 and the expression for two
ranges of α are
1
0 0 5 3𝛼 3 2
90 ≤ α ≤ 120 𝑉0 = 𝑉𝑠 [ − + sin(2𝛼)]
2 𝜋 2𝜋
1
0 0 5 3𝛼 3 0 2
120 ≤ α ≤ 150 𝑉0 = 𝑉𝑠 [ − + sin(2𝛼 + 60 ]
2 𝜋 2𝜋
30
CYCLOCONVERTERS
It is defined as conversion of fixed AC power into variable AC power with change
in frequency.
Traditionally, ac-ac conversion using semiconductor switches is done in two
different ways:
1) In two stages (ac-dc and then dc-ac) as in dc link converters or
2) In one stage (ac-ac) cycloconverters (Fig. 1).
Cycloconverters are used in high power applications driving induction
and synchronous motors.
They are usually phase-controlled and they traditionally use thyristors
due to their ease of phase commutation.
31
There are other newer forms of cycloconversion such as ac-ac matrix converters
and highfrequency ac-ac (hfac-ac) converters and these use self-controlled
switches. These converters,however, are not popular yet.
CYCLOCONVERTERS:
cycloconverter is another class of ac to ac converters. output frequency can also
be varied.
It is possible to obtain 3 phase to 1 phase regulator. in this section we will study
some of these aspects.
TYPES OF CYCLOCONVERTER:
i) single phase cycloconverter
a) Step-up Cycloconverter
b) Step-down Cycloconverter
ii) 3 phase to 1 phaseCycloconverter
iii) 3 phase to 3 phaseCycloconverter
The waveforms of this converter are shown in Fig. 5.8.2. In the positive half cycle, T1
conducts from 0 to t1, hence output voltage is positive.
32
Then at t2, T4 is forced commutated and T1is turned-on again. Therefore output voltage
is again positive.
This sequence continues. Observe that output voltage waveform has the frequency of,
In the step-down cycloconverter, the output frequency is less than supply frequency.
The midpoint cycloconverter of Fig. 5.8.1 can be operated as step-down cycloconverter. Fig.
5.8.3 shows the waveforms of this converter.
These waveforms are shown for highly inductive load with continuous output current.
Output voltage is also controlled by varying the firing angle 'α'.
Consider that, the period of input supply is T. The period of output is 4T. Four cycles of
supply voltage make one cycle of output. The dotted line shows equivalent output voltage
waveform.
33
Thus the supply frequency is divided by four. T1 and T3 are triggered to obtain
Positive cycle of the output voltage. Similarly, T 2 and T4 are triggered to obtain Negative
half cycle of the output voltage.
1 Ф to 1 Ф Cycloconverters
The output and input, both are 1Фfor such converters. The cycloconvertersdiscussed in previous
two subsections are also 1Ф to 1Фcycloconverters. Fig. 5.8.4 shows the circuit diagram of bridge
type 1 Ф to 1 Ф cycloconverter.
Output waveform of the above cycloconverter will be similar to that of Fig. 5.8.3
for inductive load and continuous output current.
34
Fig.5.8.5 shows the waveform ofabove converter for resistive load.
Output voltage is positive, when SCRs of P-converter are conducting. Similarly the
output voltage is negative when SCRs of N-converter are conducting.
The firing angle of the SCRs is varied to control the output voltage. Above
waveforms are shown for step-down operation.
Step-up operation is also possible in this converter. Four cycles of input make one
cycle of output. Hence output frequency is,
35
Fig. 4. 3 Ф -1 Ф half-wave cycloconverter
Fig. 5 3 Ф -1 Ф
36
Fig. 6. 3 Ф -1 Фhalf-wave cycloconverter waveforms
The polarity of the current determines if the positive or negative converter should
be supplying power to the load.
Conventionally, the firing angle for the positive converter is named +P, and that of
the negative converter is named -N.
When the polarity of the current changes, the converter previously supplying the
current is disabled and the other one is enabled.
The load always requires the fundamental voltage to be continuous. Therefore,
during the current polarity reversal, the average voltage supplied by both of the
converters should be equal.
Otherwise, switching from one converter to the other one would cause an
undesirable voltage jump.
To prevent this problem, the converters are forced to produce the same average
voltage at all times.
Thus, the following condition for the firing angles should be met.
𝛼𝑃 + 𝛼𝑁 = 𝜋
𝑉0 ( 𝑡0 ) = √2𝑉0 𝑠𝑖𝑛𝜔0 𝑡0
The positive converter can supply this voltage if satisfies the following condition.
37
𝑉0 ( 𝑡0 ) = √2𝑉0 𝑠𝑖𝑛𝜔0 𝑡0 = 𝑉𝑑𝑏 cos 𝛼𝑃
Where
𝑃 𝜋
𝑉𝑑𝑏 = √2𝑉0 sin (𝑝 = 3 𝑓𝑜𝑟 ℎ𝑎𝑙𝑓 𝑤𝑎𝑣𝑒 𝑐𝑜𝑛𝑣𝑒𝑟𝑡𝑒𝑟 𝑎𝑛𝑑 6 𝑓𝑜𝑟 𝑏𝑟𝑖𝑑𝑔𝑒 𝑐𝑜𝑛𝑣𝑒𝑟𝑡𝑒𝑟)
𝜋 𝑃
From the condition (3)
The firing angles at any instant can be found from (6) and (7).The operation of the 3 Ф -1
Ф bridge cycloconverter is similar to the above 3 Ф -1 Ф half-wave cycloconverter.
38
Fig. 7. 3 Ф -3 Ф half-wave cycloconverter
39
To avoid this short circuit, an intergroup reactor (IGR) can be connected between
the convertersas shown in Fig. 9.
Instead of blocking the converters during current reversal, if they are both enabled,
then a circulating current is produced.
This current is called the circulating current. It is unidirectional because the
thyristors allow the current to flow in only one direction.
Some cycloconverters allow this circulating current at all times. These are called
circulating current cycloconverters.
40
However, no bulky IGRs are used, so the size and cost is less than that of the
circulating current case.
41
Note that it is zero when both of the converters produce the same instantaneous
voltage.
The center tap voltage of IGR is the voltage applied to the load and it is the mean
42
This hybrid cycloconverter operates in the blocking mode most of the time so a
smaller IGR can be used.
The efficiency is slightly higher than that of the circulating current cycloconverter
but much less than the blocking mode cycloconverter.
Moreover, the distortion caused by the blocking mode operation disappears due to
the circulating current operation around zero current.
Moreover, the control of the converter is still less complex than that of the blocking
mode cycloconverter.
Principle: The matrix converter uses the matrix of switches so that any of the input phase voltage
can be connected to any of the output load phase. There is exactly one switch for each of the
possible connections between supply and load.
• As shown in this circuit diagram, SRR, SYRand SBr are the switches that
connect any of the input to load phase r. Similarly the switches SRY, SYY and SByconnect any of
the input to load phase y. And the switches SRB, SYB, and SBBconnect any of the input to load
phase b.
The input LC filter is used to eliminate harmonic currents in the input side.
The switches 29 = 512 combinations but only 9 combinations are used.
The switches are controlled in such a way that there is no short circuit of the input
supply. The load voltages vRvY, vB,are related to supply voltages VR, VYand VBby
43
following matrix equation
Advantages:
1. Inherent bidirectional power flow control.
2. Input-output waveforms are sinusoidal.
3. No dc-link is required, hence it is compact.
4. Power factor is controlled by independent control of load current.
Disadvantages:
1. The switches are not available for high powers.
2. Implementation is complex.
3. The maximum voltage transfer ratio is limited.
4. The switches required protection and commutation circuits which makes the
converter bulley.
Applications:
1. Matrix converters are used for low power 3Ф AC controllers.
2. It is used for power factor control.
Principle: Multiple bidirectional voltage controllers are employed in parallel. Each is fed from the
multiple tap transformers. Depending upon the desired output voltage, particular controllers are
triggered.
44
Multistage sequence controller
The circuit diagram of multistage sequence controller is shown in Fig. 5.6.1. The secondary
of the transformer have 'n taps. Each tap has the output voltage of VS/n.When SCR pair 1 is
triggered, the load voltage will be maximum, i.e. Vs. This is because voltages of all the taps are
added. When the output voltage variation is required between and Vsthen SCR
Pair 2 is triggered at zero firing angle. This gives the load voltage of …and the Variation
above this voltage uptoVsis obtained by controlling the firing angle of SCR pair 1. Thus other
pairs can be selected depending upon required output voltage.
Advantages
i) Because of multistage output control, the amplitude variations in output are reduced.
ii) Harmonic content is reduced.
iii) Failure of particular pair does not stop the operation completely, since other pairs keep on
Working.
45
The fundamental load/supply current lags the supply voltage by the φ 1,
'Fundamental Power Factor' angle.
Cosφ1 is also called the 'Displacement Factor'. However this does not account for
the total reactive power drawn by the system.
This power factor is inspite of the actual load being resistive! The reactive power
is drawn also y the trigger-angle dependent harmonics. now
𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑝𝑜𝑤𝑒𝑟 𝑃
𝑃𝑜𝑤𝑒𝑟 𝑓𝑎𝑐𝑡𝑜𝑟 = =
𝑎𝑝𝑝𝑎𝑟𝑒𝑛𝑡 𝑣𝑜𝑙𝑡𝑎𝑚𝑝𝑒𝑟𝑒𝑠 𝑉𝐼𝐿
𝑉𝐼𝐿1 cos ф1
= 𝑉𝐼𝐿
𝐼𝐿1
𝑑𝑖𝑠𝑡𝑜𝑟𝑡𝑖𝑜𝑛 𝑓𝑎𝑐𝑡𝑜𝑟 =
𝐼𝐿
1 𝜋 2𝑉 2
= ∫ 𝑠𝑖𝑛2 𝜔𝑡 𝑑𝜔𝑡
𝜋 𝛼 𝑅
2𝑉 2 𝛼 𝑠𝑖𝑛2𝛼
= [𝜋 − + ]
𝑅𝜋 2 2
The portion within square brackets in Eq is identical to the first part of the expression
within brackets in Eq., which is called the Fourier coefficient 'B1
'
The rms load voltage can also be similarly obtained by integrating between α and π and the result
can be combined with Eq to give
46
Fig.1 Variation of various performance parameters with triggering angle
Fig. 2 Operation of a Phase Angle Controlled AC-AC converter with a resistive load
47
12. Applications –welding
48