Professional Documents
Culture Documents
DISTRIBUTION SHEET
TYPE OF DISTRIBUTION: C=COPY, E=E-MAIL, D=DATA CARRIER
Customer 1xE
EXTERNAL
DISTRIBUTION
Rev.-Index 0
Created Pickl
Creation date 26.04.2021
REVISION
Checked Kaiser
Check date 26.04.2021
Status Final
DISTRIBUTED Name Pickl
FROM Date 26.04.2021
AI = Analog input
AO = Analog output
DI = Digital input
DO = Digital output
Handling
Function
Signal Value
Signal
Connection Scope of Signal
Rev.
with
Tag
Loop Number Description Function Description Position Description Signal Signal Form Signal Level Signal Type Remark Cabinet Slot Rack Address
Type Supply Type
Min Max Unit
02009-CsT1 QIC Consistency Pump Chest LF QV DCS Valve Opening 0 100 %. 2 - wire 4..20 mA HW AO REM 02010 Electricat cabinet PAW 512 AO
02001-LT1 LIC Level LF Chest LT DCS Actual Level 0 100 % 2 - wire 4..20 mA SP HW AI REM 02010 Electricat cabinet Slot 7 PEW 522
02002-M1 M Motor Agitator LF Chest ET DCS Actual Load 0 130 % Field bus NO 4..20 mA BUS AI
02002-M1 M Motor Agitator LF Chest K1 DCS Run = 1 Field bus NO 24 VDC BUS DI
02002-M1 M Motor Agitator LF Chest K5 DCS Ready = 1 Field bus NO 24 VDC BUS DI
02002-M1 M Motor Agitator LF Chest K11 DCS Motor Start Field bus NO 24 VDC BUS DO
02003-AV1 HS Feed Valve LF Chest GS1 DCS Valve Closed = 1 2 - wire NO 24 VDC HW DI Stay the same in the actual software(no modification) DI
02003-AV1 HS Feed Valve LF Chest GS2 DCS Valve Open = 1 2 - wire NO 24 VDC HW DI Stay the same in the actual software(no modification) DI
02003-AV1 HS Feed Valve LF Chest HY DCS Valve Open 2 - wire NO 24 VDC HW DO Stay the same in the actual software(no modification) DO
02005-M1 M Motor Pump Chest LF ET DCS Actual Load 0 130 % Field bus NO 4..20 mA BUS AI
02005-M1 M Motor Pump Chest LF K1 DCS Run = 1 Field bus NO 24 VDC BUS DI
02005-M1 M Motor Pump Chest LF K5 DCS Ready = 1 Field bus NO 24 VDC BUS DI
02005-M1 M Motor Pump Chest LF K11 DCS Motor Start Field bus NO 24 VDC BUS DO
02007-AV1 HS Shut Off after LF Chest GS1 DCS Valve Closed = 1 2 - wire NO 24 VDC HW DI Stay the same in the actual software(no modification) DI
02007-AV1 HS Shut Off after LF Chest GS2 DCS Valve Open = 1 2 - wire NO 24 VDC HW DI Stay the same in the actual software(no modification) DI
02007-AV1 HS Shut Off after LF Chest HY DCS Valve Open 2 - wire NO 24 VDC HW DO Stay the same in the actual software(no modification) DO
02009-CsT1 QIC Consistency Pump Chest LF QT DCS Actual Consistency 2 6 % 2 - wire 4..20 mA FP HW AI REM 02010 Electricat cabinet PEW524 AI
A20-SIC1 SIC Speed Pump Chest LF ST DCS Actual Speed 0 100 % Field bus 24 VAC BUS AI
A20-SIC1 SIC Speed Pump Chest LF SY DCS Speed Setpoint 0 100 % Field bus 24 VAC BUS AO
A20-F1 FIC Flow Circulation LF Refining FV DCS Valve Opening 0 100 l/min 2 - wire 4..20 mA HW AO REM 02010 Electricat cabinet SLOT 11 1/1 RACK1 PAW526
A20-P7 PIC Pressure Feed LF Refiner 2 AO1 DCS Valve Opening 0 100 %. 2 - wire 4..20 mA HW AO REM 02010 Electricat cabinet SLOT 11 1/1 RACK1 PAW524
02012-PT1 PIC Pressure Accept HD-Cleaner PV DCS Valve Opening 0 100 % 2 - wire 4..20 mA HW AO Stay the same in the actual software(no modification) AO
02032-FT1 FIC Flow Mixing Chest LF Refining FV DCS Valve Opening 0 100 l/min 2 - wire 4..20 mA HW AO Stay the same in the actual software(no modification) AO
02012-PT1 PIC Pressure Accept HD-Cleaner PT DCS Actual Pressure 0 5 bar 2 - wire 4..20 mA HW AI mcc prep1(coloana 2) Electricat cabinet Slot 16 PEW ?
02029-HV1 GS Feed Valve LF Refiner 2 GS1 DCS Closed = 1 2 - wire NO 24 VDC HW DI No need DI
02029-HV1 GS Feed Valve LF Refiner 2 GS2 DCS Open = 1 2 - wire NO 24 VDC HW DI no need DI I wiil put a new siemens
02030-HV1 OS Flushing LF Refiner 2 GS1 DCS Closed = 1 2 - wire NO 24 VDC HW DI DI
02030-HV1 OS Flushing LF Refiner 2 GS2 DCS Open = 1 2 - wire NO 24 VDC HW DI DI
02030-HV1 OS Flushing LF Refiner 2 HY DCS Valve Open 2 - wire NO 24 VDC HW DO DO
02032-FT1 FIC Flow Mixing Chest LF Refining FT DCS Actual Flow 0 1000 l/min 2 - wire 4..20 mA FP HW AI Stay the same in the actual software(no modification) AI
02035-PT1 PIZ Pressure Outlet LF Refiner 2 PT DCS Actual Pressure 0 10 bar 2 - wire 4..20 mA SP HW AI Stay the same in the actual software(no modification) AI
02035-PT1 PIZ Pressure Outlet LF Refiner 2 F10 SRS Safety Off = 0 2 - wire NC 24 VDC HW DI DI
02036-HV1 GS Bypass Valve LF Refiner 2 GS1 DCS Closed = 1 2 - wire NO 24 VDC HW DI No need DI
02036-HV1 GS Bypass Valve LF Refiner 2 GS2 DCS Open = 1 2 - wire NO 24 VDC HW DI No need DI
02037-HV1 GS Outlet Valve LF Refiner 2 GS1 DCS Closed = 1 2 - wire NO 24 VDC HW DI No need DI
02037-HV1 GS Outlet Valve LF Refiner 2 GS2 DCS Open = 1 2 - wire NO 24 VDC HW DI No need DI
02040-E1 JIC Power LF Refiner 2 JT DCS Actual Power 0 665 W BUS AI
02040-M1 M Motor Plate Adjustment LF Refiner 2 ET DCS Actual Load 0 130 % Field bus NO 4..20 mA BUS AI
02040-M1 M Motor Plate Adjustment LF Refiner 2 K1 DCS Run = 1 Field bus NO 24 VDC BUS DI
02040-M1 M Motor Plate Adjustment LF Refiner 2 K5 DCS Ready = 1 Field bus NO 24 VDC BUS DI
02040-M1 M Motor Plate Adjustment LF Refiner 2 K11 DCS Start FWD Load Field bus NO 24 VDC BUS DO
02040-M1 M Motor Plate Adjustment LF Refiner 2 K12 DCS Start REV Release Field bus NO 24 VDC HW DO Stay the same in the actual software(no modification) DO
02040-M1 M Motor Plate Adjustment LF Refiner 2 K13 DCS Fast Speed Field bus NO 24 VDC HW DO Stay the same in the actual software(no modification) DO
02040-M1 M Motor Plate Adjustment LF Refiner 2 SRS SRS Safety Release Field bus NC 24 VDC HW DO DO
02040-M2 M Motor LF Refiner 2 ET DCS Actual Load 0 130 % Field bus NO 4..20 mA BUS AI
02040-M2 M Motor LF Refiner 2 K1 DCS Run = 1 Field bus NO 24 VDC BUS DI
02040-M2 M Motor LF Refiner 2 K5 DCS Ready = 1 Field bus NO 24 VDC BUS DI
02040-M2 M Motor LF Refiner 2 K11 DCS Motor Start Field bus NO 24 VDC BUS DO
02040-M2 M Motor LF Refiner 2 SRS SRS Safety Release Field bus NC 24 VDC HW DO DO
20001-LT1 LIC Level Mixing Chest LT DCS Actual Level 0 100 % 4..20 mA SP HW AI Stay the same in the actual software(no modification) AI
20002-M1 M Motor Agitator Mixing Chest LF ET DCS Actual Load 0 130 % Field bus NO 4..20 mA BUS AI
20002-M1 M Motor Agitator Mixing Chest LF K1 DCS Run = 1 Field bus NO 24 VDC BUS DI
20002-M1 M Motor Agitator Mixing Chest LF K5 DCS Ready = 1 Field bus NO 24 VDC BUS DI
20002-M1 M Motor Agitator Mixing Chest LF K11 DCS Motor Start Field bus NO 24 VDC BUS DO
20007-AV1 HS Shut Off after Mixing Chest GS1 DCS Valve Closed = 1 2 - wire NO 24 VDC HW DI Stay the same in the actual software(no modification) DI
20007-AV1 HS Shut Off after Mixing Chest GS2 DCS Valve Open = 1 2 - wire NO 24 VDC HW DI Stay the same in the actual software(no modification) DI
20007-AV1 HS Shut Off after Mixing Chest HY DCS Valve Open 2 - wire NO 24 VDC HW DO Stay the same in the actual software(no modification) DO
A20-E1 EIC Specific Power LF Refining SP DCS Spec. Power Setpoint ### ### SW
A20-E2 JIC Power LF Refiner 1 JT DCS Actual Power 0 665 W BUS AI
A20-F1 FIC Flow Circulation LF Refining FT DCS Actual Flow 0 1000 l/min 2 - wire 4..20 mA FP HW AI REM 02010 Electricat cabinet SLOT 9 1/2 RACK1 PEW554 (wire 07902)
A20-F2 FS Flow Sealing Water Feed LF Refiner 1 FS DCS Flow Low = 0 2 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 4 4/4 RACK1 I27 [12.2]
A20-F3 FS Flow Sealing Water Outlet LF Refiner 1 FS DCS Flow Low = 0 2 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 4 4/4 RACK1 I28 [12.3]
A20-F4 FS Flow Sealing Water Feed LF Refiner 2 FS DCS Flow Low = 0 2 - wire NC 24 VDC HW DI No need DI
A20-F5 FS Flow Sealing Water Outlet LF Refiner 2 FS DCS Flow Low = 0 2 - wire NC 24 VDC HW DI No need DI
A20-G1 GS Position Plate LF Refiner 1 GS1/A DCS Refiner Start Position = 1 4 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 2/4 RACK1 I9 [14.0] wire (05501)
A20-G1 GS Position Plate LF Refiner 1 GS1/B DCS Open Position = 0 4 - wire NC 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 2/4 RACK1 I10 [14.1] wire (05502)
A20-G1 GS Position Plate LF Refiner 1 GS2 DCS Safety Position = 0 2 - wire NC 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 2/4 RACK1 I16 [14.7] wire (05508)
A20-G2 GS Position Plate LF Refiner 2 GS1/A DCS Refiner Start Position = 1 2 - wire NO 24 VDC HW DI Stay the same in the actual software(no modification) DI
A20-G2 GS Position Plate LF Refiner 2 GS1/B DCS Open Position = 0 2 - wire NC 24 VDC HW DI Stay the same in the actual software(no modification) DI
A20-G2 GS Position Plate LF Refiner 2 GS2 DCS Safety Position = 0 2 - wire NC 24 VDC HW DI Stay the same in the actual software(no modification) DI
A20-HV1 HS Upper HD-Cleaner GS1 DCS KV1, Closed = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV1 HS Upper HD-Cleaner GS2 DCS KV1, Open = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV1 HS Upper HD-Cleaner HY DCS KV1, Valve Open 2 - wire NO 24 VDC HW DO No need Stay the same DO
Handling
Function
Signal Value
Signal
Connection Scope of Signal
Rev.
with
Tag
Loop Number Description Function Description Position Description Signal Signal Form Signal Level Signal Type Remark Cabinet Slot Rack Address
Type Supply Type
Min Max Unit
A20-HV2 HS Backwash HD-Cleaner GS1 DCS KV3, Closed = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV2 HS Backwash HD-Cleaner GS2 DCS KV3, Open = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV2 HS Backwash HD-Cleaner HY DCS KV3, Valve Open 2 - wire NO 24 VDC HW DO No need Stay the same DO
A20-HV3 HS Deaeration HD-Cleaner GS1 DCS KV4, Closed = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV3 HS Deaeration HD-Cleaner GS2 DCS KV4, Open = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV3 HS Deaeration HD-Cleaner HY DCS KV4, Valve Open 2 - wire NO 24 VDC HW DO No need Stay the same DO
A20-HV4 HS Fill/Flush HD-Cleaner GS1 DCS KV5, Closed = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV4 HS Fill/Flush HD-Cleaner GS2 DCS KV5, Open = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV4 HS Fill/Flush HD-Cleaner HY DCS KV5, Valve Open 2 - wire NO 24 VDC HW DO No need Stay the same DO
A20-HV5 HS Bottom HD-Cleaner GS1 DCS KV2, Closed = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV5 HS Bottom HD-Cleaner GS2 DCS KV2, Open = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV5 HS Bottom HD-Cleaner HY DCS KV2, Valve Open 2 - wire NO 24 VDC HW DO No need Stay the same DO
A20-HV6 GS Feed Valve LF Refiner 1 GS1 DCS Closed = 1 2 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 I27 [16.2] (wire 05703)
A20-HV6 GS Feed Valve LF Refiner 1 GS2 DCS Open = 1 2 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 I28 [I16.3] (wire 05704)
A20-HV7 GS Bypass Valve LF Refiner 1 GS1 DCS Closed = 1 2 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 I29 [I16.4] (wire 05705)
A20-HV7 GS Bypass Valve LF Refiner 1 GS2 DCS Open = 1 2 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 I30 [I16.5] (wire 05706)
A20-HV8 OS Sealing Water LF Refiner 1 GS1 DCS Closed = 1 2 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 4/4 RACK1 I25 [I16.0] (wire 05701)
A20-HV8 OS Sealing Water LF Refiner 1 GS2 DCS Open = 1 2 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 I26 [I16.1] (wire 05702)
A20-HV8 OS Sealing Water LF Refiner 1 HY DCS Valve Open 2 - wire NO 24 VDC HW DO REM 02010 Electricat cabinet SLOT 6 4/4 RACK1 Q27 [Q6.1] (wire 06903)
A20-HV9 OS Flushing LF Refiner 1 GS1 DCS Closed = 1 2 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 3/4 RACK1 I23 [I15.6] (wire 05607)
A20-HV9 OS Flushing LF Refiner 1 GS2 DCS Open = 1 2 - wire NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 I24 [I15.7] (wire 05608)
A20-HV9 OS Flushing LF Refiner 1 HY DCS Valve Open 2 - wire NO 24 VDC HW DO REM 02010 Electricat cabinet SLOT 6 3/4 RACK1 Q19 [Q5.1] (wire 06803)
A20-HV10 OS Sealing Water LF Refiner 2 GS1 DCS Closed = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV10 OS Sealing Water LF Refiner 2 GS2 DCS Open = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-HV10 OS Sealing Water LF Refiner 2 HY DCS Valve Open 2 - wire NO 24 VDC HW DO No need Stay the same DO
A20-K1 KC Sluice Control HD-Cleaner SF1 DCS Local Start = 1 2 - wire NO 24 VDC HW DI No need Stay the same DI
A20-M1 M MCC Plate Adjustment LF Refiner 1 ET DCS Actual Load 0 130 % Field bus NO 4..20 mA BUS AI
A20-M1 M MCC Plate Adjustment LF Refiner 1 K1 DCS Run = 1 Field bus NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 1/2 RACK1 I19 [15.2] (wire 05603)
A20-M1 M MCC Plate Adjustment LF Refiner 1 K5 DCS Ready = 1 Field bus NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 1/2 RACK1 I18 [15.1] (wire 05602)
A20-M1 M MCC Plate Adjustment LF Refiner 1 K11 DCS Motor Start FWD Load Field bus NO 24 VDC HW DO mcc prep1(coloana 2) Electricat cabinet slot14 1/1 rack1 I7 [2.6]
A20-M1 M MCC Plate Adjustment LF Refiner 1 K12 DCS Motor Start REV Release Field bus NO 24 VDC HW DO mcc prep1(coloana 2) Electricat cabinet slot14 1/1 rack1 I8 [2.7]
A20-M1 M MCC Plate Adjustment LF Refiner 1 K13 DCS Fast Speed Field bus NO 24 VDC HW DO mcc prep1(coloana 2) Electricat cabinet slot15 1/2 rack1 I9 [3.1] I wiil put a new siemens
A20-M1 M MCC Plate Adjustment LF Refiner 1 SRS SRS Safety Release Field bus NC 24 VDC HW DO DO
A20-M2 M Motor LF Refiner 1 ET DCS Actual Load 0 130 % Field bus NO 4..20 mA BUS AI
A20-M2 M Motor LF Refiner 1 K1 DCS Run = 1 Field bus NO 24 VDC BUS DI
A20-M2 M Motor LF Refiner 1 K5 DCS Ready = 1 Field bus NO 24 VDC BUS DI
A20-M2 M Motor LF Refiner 1 K11 DCS Motor Start Field bus NO 24 VDC BUS DO
A20-M2 M Motor LF Refiner 1 SR SRS Safety Release Field bus NC 24 VDC HW DO DO
A20-P2 PIC Pressure Feed HD-Cleaner PT DCS Actual Pressure 0 5 bar 2 - wire 4..20 mA HW AI I dont think is needed because we dont have the converter for 02005 -M1
A20-P5 PI Pressure Feed LF Refiner 1 AI1 DCS Actual Pressure 0 10 bar 2 - wire 4..20 mA HW AI REM 02010 Electricat cabinet SLOT 9 1/2 RACK1 PEW548 AI
A20-P6 PIZ Pressure Outlet LF Refiner 1 DI1 SRS digital input HW DI DI
A20-P6 PIZ Pressure Outlet LF Refiner 1 PT DCS Actual Pressure 0 10 bar 2 - wire 4..20 mA HW AI REM 02010 Electricat cabinet SLOT 9 1/2 RACK1 PEW550
A20-P7 PIC Pressure Feed LF Refiner 2 AI1 DCS Actual Pressure 0 10 bar 2 - wire 4..20 mA HW AI AI
A20-T1 TIZ Temperature Outlet LF Refiner 1 DI1 SRS digital input HW DI DI
A20-T1 TIZ Temperature Outlet LF Refiner 1 TT DCS Actual Temperature 0 120 °C 2 - wire Continous signal 4..20 mA HW AI REM 02010 Electricat cabinet SLOT 9 1/2 RACK1 PEW552
A20-T2 TIZ Temperature Outlet LF Refiner 2 DI1 SRS digital input HW DI DI
A20-T2 TIZ Temperature Outlet LF Refiner 2 TT DCS Actual Temperature 0 120 °C 2 - wire 4..20 mA SP HW AI Stay the same in the actual software(no modification) AI
A20-W1 WIC Production LF Refining SP DCS Production Setpoint 30 t/d ### SW
A20-XS1 XS Local Operation Plate Adjustment LF Refiner 1 S11 DCS Release = 1 Dry Contact NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 1/2 RACK1 I20 [15.3] (wire 05604)
A20-XS1 XS Local Operation Plate Adjustment LF Refiner 1 S12 DCS Load = 1 Dry Contact NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 1/2 RACK1 I21 [15.4] (wire 05605)
A20-XS1 XS Local Operation Plate Adjustment LF Refiner 1 S20 DCS DCS = 0/Service = 1 Dry Contact NO 24 VDC HW DI REM 02010 Electricat cabinet SLOT 5 1/2 RACK1 I22 [15.5] (wire 05606)
A20-XS2 XS Local Operation Plate Adjustment LF Refiner 2 SF11 DCS Release = 1 2 - wire NO 24 VDC HW DI Stay the same in the actual software(no modification) DI
A20-XS2 XS Local Operation Plate Adjustment LF Refiner 2 SF12 DCS Load = 1 2 - wire NO 24 VDC HW DI Stay the same in the actual software(no modification) DI
A20-XS2 XS Local Operation Plate Adjustment LF Refiner 2 SF20 DCS DCS = 0/Service = 1 2 - wire NO 24 VDC HW DI Stay the same in the actual software(no modification) DI
total output digital (PLC): 0 total output digital (PLC, SRS): 4 total output digital (DCS): 17 total output digital (DCS, SRS): 0 total spare output digital needed (DCS): 16
total abort: 0
Rev. Rev.Date Created Checked Description of Revision Creation date: 26.04.2021
Exported: 26.04.2021 15:12 Page 4 of 5 Printed: 11/26/2021 06:50:21
Project name: VRANCART Ref. CS380 I/O List Basic
Project number: C-01-842859 Doc. no.: 508981501_EN_0 for
Project description: CS380 Status: Final / Refining
Customer: VRANCART S.A. Customer
legend: red=missing information blue=signal BUS
Customer project no: doc. no.: green=verified and confirmed to use spare I/O
Yellow=safety light orange=need to know if there is
a spare I/O to be used
Handling
Function
Signal Value
Signal
Connection Scope of Signal
Rev.
with
Tag
Loop Number Description Function Description Position Description Signal Signal Form Signal Level Signal Type Remark Cabinet Slot Rack Address
Type Supply Type
Min Max Unit
Rev. Rev.Date Created Checked Description of Revision Creation date: 26.04.2021
Created: Pickl
Checked: Kaiser