You are on page 1of 1

PLANT NOTES:-

NORTH
TRUE 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS NOTED OTHERWISE.
NORTH 42°
2. CONCRETE WORKS SHALL BE IN ACCORDANCE WITH SPECIFICATION
DRAWING LIMIT N 11689.324 KZ01-CV-SPE-68-0003.

3. STRUCTURAL CONCRETE SHALL BE GRADE 40. BLINDING CONCRETE SHALL BE


GRADE 20. ALL CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH
WINDROSE KZ02-CV-SPE-68-2002.
5%
10%
15%
20%
25%

4. FOR FOUNDATION STRATA REFER STANDARD DRAWING NO.


KZ01-CV-STD-53-0003-001.

5. SOIL BELOW THE FOUNDATION SHALL BE WELL COMPACTED TO 98% MAXIMUM


DRY DENSITY.

6. BLINDING CONCRETE SHALL BE PROVIDED FOR CAST-IN-SITU FOUNDATION ONLY.


EXISTING ELECTRICAL BLINDING CONCRETE SHALL NOT BE PROVIDED ON MASS CONCRETE FILL.

475
EXISTING CABLE TRENCH (TYP)
ELECTRICAL CABLE F1 LEGEND 7. LINK AND PEDESTAL TOP REINFORCEMENT TO BE ADJUSTED AT SITE TO CLEAR
ANCHOR BOLTS.
TRENCH (TYP)
8. CONTRACTOR TO EXCAVATE MANUALLY FOR FOUNDATIONS AS THERE ARE

DRAWING LIMIT E 11027.050

DRAWING LIMIT E 11051.298


1250 1250 1250 FOUNDATIONS

1674
EXISTING CABLE TRENCHES AROUND.

2700

E11039.755
216 100 EXISTING
NEW ELECTRICAL
N11680.826 ELECTRICAL CABLE 9. RECOMMENDED FOUNDATION LOCATIONS ARE PROVIDED IN THE DRAWING. THE
CABLE TRENCH

(REF)
TRENCH (TYP) LOCATIONS TO BE ADJUSTED TO SUIT AT SITE FOR EXISTING U/G FACILITIES.
F1 F1 F1 F1 300W X 850D
FOUNDATIONS (TYP) N11679.675
TELECOM CABLE ROUTE
10. ALL ANCHORS TO BE POST DRILLED HILTI BOLTS M16 DIA HAS-U-8.8. EMBEDDED

1425
LENGTH =125 mm (MIN)
N11678.776
450 N11678.375
(REF)
ELECTRICAL CABLE ROUTE 11.LIFTING HOLES / POCKET SHALL BE FILLED WITH CEMENT SAND MORTAR AFTER
ERECTION OF PRECAST ELEMENT IN POSITION.
2840
TELECOM TRENCH 12.USE 32 DIA LIFTING ROD IN PVC SLEEVE.

3100
NEW 300W X 800D NEW
F1 ELECTRICAL
N11675.494 CABLE TRENCH

1150
LEGEND:-

806
TELECOM TRENCH F1 F1
EXISTING 4000
N11673.849 1. ELECTRICAL CABLE TRENCH (EXISTING)
1950 1250 3584

E11038.491
2. TELECOM TRENCH (EXISTING)

(REF)
E11033.996
3. ELECTRICAL CABLE TRENCH (NEW)

E11038.041

E11045.496
4. TELECOM TRENCH (NEW)

(REF)
DRAWING LIMIT N 11667.880
0 500 1000 1500 2000 2500 mm

SCALE 1 : 25
FOUNDATION AND TRENCH LAYOUT FOR MUSTER POINT 3
SCALE 1:100 0 1000 5000 10000 mm

SCALE 1 : 100

KZ01-TE-LAY-53-1015-001-19008 TELECOMMUNICATION FIELD EQUIPMENT AND CABLE


L OF PED/ FOUNDATION

CL OF PED/ FOUNDATION
ROUTING LAYOUT - CONDENSATE AND GAS EXPORT 2 AREA
750 CPF POWER LAYOUT CONDENSATE STORAGE AND EXPORT
KZ01-EL-LAY-53-1254-001-19008
== CENTRAL AREA PHASE 2
450 STANDARD DRAWING CIVIL CONCRETE GENERAL NOTES
KZ01-CV-STD-53-0001-001
==
P1 KZ01-CV-STD-53-0002-001 CONCRETE PROTECTION DETAILS
STANDARD DRAWING REINFORCEMENT DETAILS FOR
A A KZ01-CV-STD-53-0037-001
ELECTRICAL / INSTRUMENTATION INSTALLATIONS
450
750
==

==
C

KZ01-CV-LAY-53-2343-001-19008 COMPOSITE UG SERVICES LAYOUT MUSTER POINT 3

4 NOS. 16 DIA
HILTI HAS - U 8.8 ANCHOR RODS
(SEE NOTE 10)
BOLT LOCATIONS TO MATCH THE
BASE PLATE HOLES FOR THE POST

FOUNDATION PLAN FOR - F1


(8 NOS. REQUIRED)
SCALE 1:25
NONSHRINK
GROUT
25 THK

TOC
SLEEVE

EL.+0.175 FGL
EL.+0.000
300

L
C OF

STS
50 DIA PIPE SLEEVE FOR

SWIS Worley
600

LIFTING (IN CASE OF Integrated


PRECAST CONSTRUCTION)
Solutions
BOTTOM OF
FOUNDATION
FOR REINFORCEMENT
DETAILS REFER
FOUNDATION

SECTION K IN DRAWING 50
KZ01-CV-STD-53-0037-001 (TYP)
THK.
250

50MM BLINDING (TYP)


REFER NOTE 6
FOUNDATION STRATA (TYP)
REFER NOTE 4

SECTION A
SCALE 1 : 25 -