SAUDIARAMCO.

NOTES:

1.ALL ELECTRICAL INSTALLATION SHALL BE DONE IN


ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE
(NFPA 70) AND ALL THE APPLICABLE SAUDI
ARAMCO ENGINEERING STANDARDS.

2.PANELBOARD SHALL BE MANUFACTURED AS PER SAUDI


ARAMCO MATERIAL SPEFICATION NO. 16-SAMSS-518.

OF
3.ALL CIRCUIT BREAKERS SHALL BE THERMAL MAGNETIC

CONSENT
TRIP RATED FOR 50 DEG. CELCIUS AMBIENT
TEMPERATURE.

4.FULLY BUSSED CUBICLE, VENDOR SHALL PROVIDE THE


REQUIRED MINIMUM OF 10% SPARE CIRCUIT BREAKERS
AND MINIMUM 10% OF SPARE POLE SPACES.

TTEN
5.THE ENCLOSURE FOR THE PANELBOARD SHALL HAVE
FROM EXISTING MDP
THE TOP AND BOTTOM WIRE-BENDING SPACE SIZED
208/120V, 3{, 3W+G, 60HZ

WRI
IN ACCORDANCE WITH NEC ARTICLE 384.35 AND
POWER SUPPLY
TABLE 373-6 (A AND B).
(REFER TO DWG. NO.
PA-01P322.001)

THE
PC-0001

THOUT
WI NG
X27-DSW(D)-001

DRAWI
400A, 208V, 3PH
NEMA 4X

S
THI
PC-0002

FROM
X27-XFR(T)-001

NED
75kVA, 208-400/230V,
3{, 4W, 60HZ, dYN1

OBTAI
NEMA-4 LEGEND

POWER CABLE

BE
PC-XXXX
NUMBER

PC-0003

PART,SHALL
75KVA, 208-400/230V,
3{, 4W, 60HZ, dYN1

GATEHOUSE POWER PANEL


X27-PP-001, NEMA-4

MOLDED CASE
3P
CIRCUIT BREAKER

N
I
150AF

FULL,OR
3P
150AT
MINIATURE
1P CIRCUIT BREAKER

150A, 400/230V, 3{, 4W+G, 60HZ, 10KAIC


PANELBOARD

N
I
(RATING AS SHOWN)

ON
REPRODUCTI
EQUIPMENT
100AF 100AF 100AF 100AF 100AF 100AF
3P 3P 3P 3P 3P 3P 1P 20A 1P 20A 1P 20A 1P 20A GROUND
100AT 100AT 100AT 100AT 30AT 30AT

PC PHOTOCELL

SAUDIARAMCO.NO
LIGHTING CONTROL
LCP
PANEL
PC-0004

PC-0005

PC-0006

PC-0007

PC-0011
FCU FAN COIL UNIT

X27-DSW(D)-002 X27-DSW(D)-010
30A, 400V, 3PH 30A, 400V, 3PH ACCU AIR COOLER CONDENSING UNIT
NEMA 4X NEMA 4X
PC-0008

PC-0012

OF
X27-LCP-001 X27-LCP-002 REFERENCE DRAWINGS

PC LCP PC LCP DWG. CONTROL FOR J.O. 10-00965-0001 PD-00ADCL

PROPERTY
PANELBOARD SCHEDULE PA-01O276
X27-PP-002 X27-PP-003 X27-PP-004
REFER TO PANEL SCHEDULE CABLE AND CONDUIT SCHEDULE PD-01O278
(GATE HOUSE) SUPPORT BUILDING CRASH BARRIER
SPARE AIR COOLED CONDENSING AIR COOLED CONDENSING DWG. NO. PA-01O276.001
REFER TO DWG. NO. REFER TO DWG. NO. REFER TO DWG. NO.
UNIT-GATE HOUSE UNIT-GATE HOUSE
PA-01O276.001 PA-01P326.001 PA-01O276.001
FCU/ACCU-01 FCU/ACCU-02
7KW (DUTY) 7KW (STANDBY)

SOLE
THE
ARE N
HEREINED
SCALE:

CONTAI
REVISION VALIDATION

THIS REVISION NO. C IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
10-00965-0001-001

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

REV.NO. DATE REVISION DESCRIPTION

I
C 12/05/19 ISSUED FOR 100% PROJ. PROPOSAL

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-00965-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

ELECTRICAL ONE LINE DIAGRAM GAT

NG
DH AIRPORT FUEL TANK FARM GATE21-GH

DRAWI
DHAHRAN AFO/KAAB

DHAHRAN SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
X27 O PA-01O274 001 C
Saudi Aramco 2615 ENG. (05/05)