You are on page 1of 2

NOTES

1. NEGATIVE LEAD AND TEST LEAD CONNECTION SHALL


BE BY PAD WELDED. CLEATS SHALL BE FABRICATED
INTERNAL CP SYSTEM SCHEMATIC DRAWING FOR TANK - 712-T-301A FROM SAME MATERIAL OF TANK SHELL AND THE
LOCATION SHALL BE ADJUSTED TO SUIT THE SITE
CONDITION.
2. CABLE SHALL BE ROUTED TO SUIT THE SITE
CONDITION AND SUFFICIENT CABLE LENGTH SHALL
The document has been given Code-3, in case BE PROVIDED FOR SITE ACTUAL REQUIREMENTS.
of any error / discrepancy / non-compliance are 3. FOR CP EQUIPMENTS/MATERIALS INSTALLATION
10 REFER LAYOUT DRAWING FOR TANKS INTERNAL CP
observed at later date, Company reserves the
right to make comment for Contractor's SYSTEM - POTABLE WATER TANKS(712-T-301A/B),
8 712-RE1-901C 4. EQUIPMENT TAGS SHALL BE ENGRAVED TRAFFOLYTE
incorporation
9 712-RE2-901C OR EQUIVALENT AS PER 9686-8530-SP-000-3519:
SPECIFICATION FOR ELECTRICAL BULK EQUIPMENT
712-CPTR-601-C 3 4 5 6
ESS01A-60093-P01
AC 415V, 3PH
LEGEND
- + HHLL: +7550
50Hz TRANSFORMER RECTIFIER UNIT
TEST BOX
ANODE JUNCTION BOX
1
WELD CLEAT CONNECTION
7
712-CPJB-901-C PERMANENT REFERENCE CELL (Ag/AgCl)
2 712-CPTS-901-C MMO ANODE
LLLL: +600 1CX25 SQ.MM ANODE TAIL CABLE
G\L 1CX10 SQ.MM REFERENCE CELL CABLE
1CX10 SQ.MM MONITORING CABLE
712-T-301A
1CX50 SQ.MM NEGATIVE HEADER CABLE
1CX50 SQ.MM POSITIVE HEADER CABLE
CABLE TAG LIST 1CX10 SQ.MM PROBE CABLE

NO CABLE TAG FROM TO CABLE SIZE REMARKS


4CX2.5 SQ.MM MULTI CORE CABLE
1 CPTR601C-9000-P 712-CPTR-601-C 712-CPJB-901-C 1X50 SQ.MM HEADER CABLE PRE PERMANENT REFERENCE ELECTRODE
2 CPTR601C-9001-P 712-CPTR-601-C 712-T-301A 1X50 SQ.MM HEADER CABLE
AS ANODE STRING
3 CPJB901C-9000-P 712-CPJB-901-C 712-AS1-901-C 1X25 SQ.MM ANODE STRING CABLE 1 REVISION CLOUD
4 CPJB901C-9001-P 712-CPJB-901-C 712-AS2-901-C 1X25 SQ.MM ANODE STRING CABLE 2
5 CPJB901C-9002-P 712-CPJB-901-C 712-AS3-901-C 1X25 SQ.MM ANODE STRING CABLE 3
6 CPJB901C-9003-P 712-CPJB-901-C 712-AS4-901-C 1X25 SQ.MM ANODE STRING CABLE 4 REFERENCE DOCUMENTS
7 CPTS901C-9000-P 712-CPTS-901-C 712-T-301A 1X10 SQ.MM MONITORING CABLE LAYOUT DRAWING FOR TANKS
8 CPTS901C-9001-P 712-CPTS-901-C 712-RE1-901-C 1X10 SQ.MM PERMANENT REFERENCE CELL 1 9686-8360-85-712-2504 INTERNAL CP SYSTEM - POTABLE
9 CPTS901C-9002-P 712-CPTS-901-C 712-RE2-901-C 1X10 SQ.MM PERMANENT REFERENCE CELL 2 WATER TANKS (712-T-301A/B)
10 CPTS901C-9003-P 712-CPTR-601-C 712-CPTS-901-C 4CX2.5 SQ.MM MULTI CORE CABLE DESIGN REPORT FOR TANKS
INTERNAL CP SYSTEM-POTABLE
9686-8360-RP-712-2502
WATER TANKS-(712-T-301A/B)
GENERAL ARRANGEMENT &

A3 (420 x 297) PLOT DATE / TIME : 4/21/2020 2:05:15 PM


9686-8430-14-712- ORIENTATION DRAWING FOR
4002-001 POTABLE WATER TANKS
(712-T-301A)
CLIENT : EPC CONTRACTOR: PROJECT TITLE:
RAS MARKAZ CRUDE OIL PARK PROJECT (PHASE1)
DRAWING TITLE:
DOC. CLASS/CAT. : 2 SCHEMATIC DRAWING FOR TANKS
INTERNAL CP SYSTEM-POTABLE
中国石油管道局工程有限公司 PROJECT No. 9686 WATER TANKS(712-T-301A/B)
B1 21/04/20 ISSUED FOR APPROVAL NK SK HP MJH
A1 06/04/20 ISSUED FOR REVIEW / COMMENTS NK SK HP MJH OMAN TANK TERMINAL COMPANY CHINA PETROLEUM PIPELINE ENGINEERING SCALE DRAWING No. SHEET REV.
(OTTCO) CO., LTD.
REV DATE DESCRIPTION BY CH'D APP APP NTS 9686-8360-85-712-2502 01 OF 02 B1
This document contains information which is subject to obligations of non-disclosure and is to be returned to Oman Tank Terminal Company L.L.C. upon request. The contents may not be copied, disclosed or made available to any CAD FILE NAME : 9686-8360-85-712-2502_B1.dwg
third party or used other than for the intended purpose for which it has been provided unless Oman Tank Terminal Company L.L.C. provides written consent for such copy, disclosure, availability and/or use.
NOTES
1. NEGATIVE LEAD AND TEST LEAD CONNECTION SHALL
BE BY PAD WELDED. CLEATS SHALL BE FABRICATED
INTERNAL CP SYSTEM SCHEMATIC DRAWING FOR TANK - 712-T-301B FROM SAME MATERIAL OF TANK SHELL AND THE
LOCATION SHALL BE ADJUSTED TO SUIT THE SITE
CONDITION.
2. CABLE SHALL BE ROUTED TO SUIT THE SITE
CONDITION AND SUFFICIENT CABLE LENGTH SHALL
BE PROVIDED FOR SITE ACTUAL REQUIREMENTS.
3. FOR CP EQUIPMENTS/MATERIALS INSTALLATION
10 REFER LAYOUT DRAWING FOR TANKS INTERNAL CP
SYSTEM - POTABLE WATER TANKS(712-T-301A/B),
8 712-RE1-901D 4. EQUIPMENT TAGS SHALL BE ENGRAVED TRAFFOLYTE
9 OR EQUIVALENT AS PER 9686-8530-SP-000-3519:
712-RE2-901D
SPECIFICATION FOR ELECTRICAL BULK EQUIPMENT

712-CPTR-601-D 3 4 5 6
ESS01A-60094-P01 LEGEND
AC 415V, 3PH HHLL: +7550
50Hz - + TRANSFORMER RECTIFIER UNIT
TEST BOX
ANODE JUNCTION BOX
1 WELD CLEAT CONNECTION
7 PERMANENT REFERENCE CELL (Ag/AgCl)
712-CPJB-901-D
MMO ANODE
2 712-CPTS-901-D
LLLL: +600 1CX25 SQ.MM ANODE TAIL CABLE
1CX10 SQ.MM REFERENCE CELL CABLE
G\L
1CX10 SQ.MM MONITORING CABLE
712-T-301B 1CX50 SQ.MM NEGATIVE HEADER CABLE
1CX50 SQ.MM POSITIVE HEADER CABLE
CABLE TAG LIST 1CX10 SQ.MM PROBE CABLE
4CX2.5 SQ.MM MULTI CORE CABLE
NO CABLE TAG FROM TO CABLE SIZE REMARKS PRE PERMANENT REFERENCE ELECTRODE
1 CPTR601D-9000-P 712-CPTR-601-D 712-CPJB-901-D 1X50 SQ.MM HEADER CABLE AS ANODE STRING
2 CPTR601D-9001-P 712-CPTR-601-D 712-T-301B 1X50 SQ.MM HEADER CABLE
3 CPJB901D-9000-P 712-CPJB-901-D 712-AS1-901-D 1X25 SQ.MM
REVISION CLOUD
ANODE STRING CABLE 1
4 CPJB901D-9001-P 712-CPJB-901-D 712-AS2-901-D 1X25 SQ.MM ANODE STRING CABLE 2
5 CPJB901D-9002-P 712-CPJB-901-D 712-AS3-901-D 1X25 SQ.MM ANODE STRING CABLE 3 REFERENCE DOCUMENTS
6 CPJB901D-9003-P 712-CPJB-901-D 712-AS4-901-D 1X25 SQ.MM ANODE STRING CABLE 4
7 CPTS901D-9000-P 712-CPTS-901-D 712-T-301B 1X10 SQ.MM
LAYOUT DRAWING FOR TANKS
MONITORING CABLE
9686-8360-85-712-2504 INTERNAL CP SYSTEM - POTABLE
8 CPTS901D-9001-P 712-CPTS-901-D 712-RE1-901-D 1X10 SQ.MM PERMANENT REFERENCE CELL 1
WATER TANKS (712-T-301A/B)
9 CPTS901D-9002-P 712-CPTS-901-D 712-RE2-901-D 1X10 SQ.MM PERMANENT REFERENCE CELL 2
DESIGN REPORT FOR TANKS
10 CPTS901D-9003-P 712-CPTR-601-D 712-CPTS-901-D 4CX2.5 SQ.MM MULTI CORE CABLE
9686-8360-RP-712-2502 INTERNAL CP SYSTEM-POTABLE
WATER TANKS-(712-T-301A/B)
GENERAL ARRANGEMENT &

A3 (420 x 297) PLOT DATE / TIME : 4/21/2020 2:13:15 PM


9686-8430-14-712- ORIENTATION DRAWING FOR
4002-001 POTABLE WATER TANKS
(712-T-301A)
CLIENT : EPC CONTRACTOR: PROJECT TITLE:
RAS MARKAZ CRUDE OIL PARK PROJECT (PHASE1)
DRAWING TITLE:
DOC. CLASS/CAT. : 2 SCHEMATIC DRAWING FOR TANKS
INTERNAL CP SYSTEM-POTABLE
中国石油管道局工程有限公司 PROJECT No. 9686 WATER TANKS(712-T-301A/B)
B1 21/04/20 ISSUED FOR APPROVAL NK SK HP MJH
A1 06/04/20 ISSUED FOR REVIEW / COMMENTS NK SK HP MJH OMAN TANK TERMINAL COMPANY CHINA PETROLEUM PIPELINE ENGINEERING SCALE DRAWING No. SHEET REV.
(OTTCO) CO., LTD.
REV DATE DESCRIPTION BY CH'D APP APP NTS 9686-8360-85-712-2502 02 OF 02 B1
This document contains information which is subject to obligations of non-disclosure and is to be returned to Oman Tank Terminal Company L.L.C. upon request. The contents may not be copied, disclosed or made available to any CAD FILE NAME : 9686-8360-85-712-2502_B1.dwg