GENERAL NOTES

CONCRETE POST

1. ALL ELECTRICAL WORKS SHALL CONFORM TO THE LATEST EDITION OF PHILIPPINE


ELECTRICAL CODE , TO THE RULES AND REGULATIONS OF THE LOCAL AND NATIONAL
AUTHORITIES CONCERNED AND THE REQUIREMENTS OF LOCAL UTILITY COMPANIES.

2. ALL WIRING INSTALLATION SHALL BE CONCEALED FROM VIEW AND INSTALLING THE
CONDUCTORS IN POLYVINYL CHLORIDE CONDUIT (PVC) AND RIGID STEEL CONDUIT (RSC)
WHEN USED AS SERVICE ENTRANCE.
KILOWATT HOUR
METER
3. MINIMUN SIZE OF CONDUCTORS SHALL BE 3.5 mm2 THHN (NO. 12 AWG) AND OF CONDUIT
1
CONDUIT SHALL BE 15mm DIA. ( 2") NOMINAL DIAMETER, UNLESS OTHERWISE SPECIFIED ON PLANS.

4. NO BRANCH CIRCUIT WIRING IN LIGHTING AND POWER SHALL HAVE A LOAD MORE
PANEL BOARD THAN 80% OF ITS RATING.

PB PB 5. LIGHT CONTROL SWITCHES SHALL BE RATED 15 AMPERES,


120
277 VAC ONLY.

6. UNLESS OTHERWISE SPECIFIED PULLBOXES OR JUNTION BOXES SHALL BE PROVIDED.

7. WHENEVER REQUIRED AND NECESSARY, ALTHOUGH SUCH BOXES ARE NOT INDICATED ON
PLANS.

8. FOR EACH SPARE CIRCUIT IN PANELBOARD, PROVIDED AN EMPTY CONDUIT 20mm DIA.
CKT FIN. FLOOR LINE 3
(4") TERMINATING TO A COVERED SQUARE BOX.
2 2-8.00mm2 TW IN 9. ALL MATERIALS AND EQUIPMENT TO BE USE SHALL BE BRAND NEW AND OF APPROVED
32mm DIA. PVC TYPE AS TO LOCATION AND PURPOSES.

10. SERVICE ENTRANCE SHALL BE 230 VOLTS, SINGLE PHASE, THREE-WIRE, 60 HERTZ.
RISER DIAGRAM
NOT TO SCALE

LEGEND:

- 22 W CIRCULAR COOL LIGHT 2-8mm2 THHN IN


32mm DIA. PVC

- 20W FLOURESCENT LIGHT MAIN CB


CKT 60 A CB, 60HZ
1 - DUPLEX CONVENIENCE OUTLET 220V, 2POLE

S1 - ONE GANG SWITCH 15 AMP 20 AMP


L.O. 1 2 C.O.
S2ab - TWO GANG SWITCH SPARE SPARE
3 4
S3W - THREE-WAY SWITCH

- POWER PANEL BOARD

- WEATHERPROOF CON. OUTLET


WP
PANEL BOARD DETAIL
NOT TO SCALE
SITE

FLOOR LIGHTING LAYOUT FLOOR POWER LAYOUT


-- -- SCALE 1:50 M -- -- SCALE 1:50 M

SCHEDULE OF LOADS

NO. OF
CIRCUIT NO. DESCRIPTION OUTLET WATTS VOLTS AMPERE CKT. BKEAKER SIZE OF WIRE

1 LIGHTING OUTLET 13 1300 220 5.91 15A

COMPUTATIONS:
2 DUPLEX CONVENIENCE OUTLET 10 2000 220 9.91 20A

It= IcoX 80%


4 SPARE It= 15.82X 80%DF = 12.66 AMP
5 SPARE MAIN CKT BKR : USE 1-60A, 225AF, 250V L O C A T I O N P L A N
-- --
SCALE N.T.S
TOTAL 23 3300 220 15.82 60A

COMPUTATIONS:
PROJECT TITLE: PROJECT OWNER: DRAWN BY: SHEET CONTENT

DESIGN BY: SCALE: AS SHOWN


ELECTRICAL ENGINEER ONE STOREY RESIDENTIAL
BUILDING FEDERICO & CHERRYLYN CHECKED BY: SHEET NO:
REG. NO. VALIDITY:
CARPENA AS SHOWN
APPROVED BY:
PTR. NO. ISSUED ON: LOCATION: LOT 9,BLK 4 PALM PLACE 2
ISSUED AT: TIN NO: NASUGBU, BATANGAS DATE: