You are on page 1of 24

Design Guide DG022011EN Effective September 2021

Medium-voltage power distribution and control systems > Switchgear >

Metal-enclosed switchgear—
MVS medium-voltage
5–15 kV load interrupter switch
Contents
General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-2
MVS Load Interrupter Switchgear . . . . . . . . . . . . . . . . 8.1-2
Mini-MVS (26-Inch Wide). . . . . . . . . . . . . . . . . . . . . . . 8.1-6
MVS and Mini-MVS Switchgear Assembly Ratings. . . 8.1-7

Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-8
Switch Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-8
Motor Operated MVS . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-10
Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-11
Ohmic Voltage Sensing (OVS) . . . . . . . . . . . . . . . . . . . 8.1-12
System Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-13
MVS Switchgear with Automatic Transfer Control. . . . 8.1-15

Layouts and Dimensions . . . . . . . . . . . . . . . . . . . . . . . 8.1-17


MVS Layouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-17
Mini-MVS Layouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-23

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-24


Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1-24

More about this product


Eaton.com/mvs

Complete library of design guides


Eaton.com/designguides
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
General Description 8.1-2

MVS Load Interrupter Standards and Certifications


Switchgear Eaton’s MVS load interrupter switchgear
meets or exceeds the requirements of the
Eaton’s MVS Load Interrupter Switchgear following industry standards:
is an integrated assembly of switches, bus ■ IEEET Standard C37.20.3
and fuses that is constructed for medium-
voltage circuit protection. All major ■ ANSI C37.57
components are manufac­tured by Eaton, ■ NEMA SG5
establishing one source of responsibility ■ Canadian Standard CAN/CSAR
for the equipment’s performance and C22.2 No. 31
ensuring high standards in quality,
coordination, reliability and service. Type MVS switches meet or exceed the
requirements of the following industry
A complete line of Eaton switches and standards:
fuses is available:
■ IEEE Standard C37.20.4
■ 5 kV and 15 kV voltage classes
■ ANSI C37.58
■ 600 A and 1200 A continuous load
interrupting ratings for 5 kV and ■ ANSI C37.22
15 kV classes ■ NEMA SG6
■ 350 A continuous and load interrupting ■ Canadian Standards CAN/CSA C22.2
ratings for 5 kV and 15 kV classes for Outdoor Duplex with Customer Metering No. 193 and CAN/CSA C22.2 No. 58
capacitive circuits
5 kV and 15 kV MVS switchgear assem­
■ Non-fused or fused with current blies are available as listed products with
limiting or boric acid-type fuses Application Description Underwriters Laboratories and Canadian
■ Manual or motor operated Eaton’s Load Interrupter Type MVS Standards Association for most options.
metal-enclosed switchgear provides safe,
■ Indoor or outdoor non-walk-in Load interrupter switches should not
reliable switching and fault protection
enclosures for medium-voltage circuits rated from be used to interrupt load currents above
■ Single switches and transformer 2.4 kV to 15 kV. The MVS switch is ideal their interrupting rating of 600 A or 1200 A,
primary switches for applications where high duty cycle as they are not designed nor tested for
■ Duplex loadbreak switch arrange­ments operation is not required. interrupting fault currents on electrical
for selection of alternate feeds systems. Optional fuses can be provided
MVS switchgear has the advantage of for phase overcurrent protection.
■ Two-position, manual no-load selector low initial cost inherent in switch designs
switches for selection of alternate feeds while offering the characteristics most
■ Lineups with main bus vital to safety and coordination.
■ Standard arrangements with auto­matic The MVS switch’s quick-make, quick-
transfer control systems (two sources break mechanism provides full-load
feeding one bus or two sources feeding current interrupting capability while
two buses with tie switch) fuses provide accurate, permanently
calibrated short circuit detecting and
Standard design configurations for: interrupting capabilities. Visibility of
■ NEMAT pads for cable lugs actual blade position improves safety
by giving positive assurance of circuit
■ Surge arresters
de-energization.
■ Instrument transformers
■ Control power transformers
■ Power XpertT and IQ
electronic metering
■ Other auxiliary equipment

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
General Description 8.1-3

Switch Mechanism When the main blades reach a pre- Bus Insulation System
determined angle of opening, a stop All bus runs are supported using a high
The quick-make, quick-break mecha­nism post on the main blades prevents further
uses a heavy-duty coil spring that provides strength and high creep, finned support
angular movement between the main providing in excess of 12.00 inches
powerful opening and closing action.To and flicker blades. This starts the flicker
close the switch, the handle is inserted into (304.8 mm) for 5/15 kV of creep distance
blades out of the high pressure contacts between phases and ground. The molded
the spring charging cam, then rotated in the arc chutes and as contacts are
upward through an angle of 120 degrees. high track-resistant fins are constructed
broken, the flicker blades are snapped as standard of Aramid nylon or optional
This action charges the operating spring, into position by their torsion springs.
as the mechanism is forced past toggle. Cycloaliphatic epoxy.
The stored energy of the spring is released The heat of the arc, meanwhile, releases ■ Significantly superior bus bracing than
and transferred to the main shaft that a blast of de-ionizing gas from the standoff type A20 insulators
snaps the switch closed. gas-generating material of the arc chute.
■ Significantly increased creep distance
This combination of quick-break and
As a result of the over-toggle action, the DE-ION action quickly extinguishes the phase-to-phase and phase-to-ground
blades are moved independently of the arc and the circuit is safely de-energized. ■ Improved endurance from
operator. It is impossible to operate the fault incidents
switch into an intermediate position. A non-fused switch has the ability to close
■ Minimizes bus system failures due
and latch four times when rated 40 kA
To open the switch, the handle is inserted and one time when rated 61 kA and to tracking
into the spring charging cam and rotated continue to carry rated current thus ■ Eliminates additional ground
downward through 120 degrees resulting adding a large margin of integrity to planes in the switchgear for bus
in charging of the operating spring, the electrical system. supporting systems
then releasing its stored energy in
similar sequence. The 5/15 kV switch designs have also
demonstrated the ability to surpass
Quick-Break DE-ION Arc Interruption the number of ANSI C37.22 required
loadbreak current operations by no
With the switch closed, both main and
less than 200%.
auxiliary (flicker) blades are closed, and
all of the current flows through the main
blades. The flicker blades are in the closed
position in the arc chutes, but are past the
Bus Support
arcing contacts and thus carry no current.
As the main blades open, current is
transferred momentarily to the flicker
blades, which are held in the arc chutes
by high pressure contact fingers. There
is no arcing at the main blades.

Main, Flicker Blades Main Blades Disengaged, Both Blades Disengaged


Engaged Flicker Blade Engaged

Figure 8.1-1. Switch Operation

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
General Description 8.1-4

Duplex Switch Configuration Two-Position, No-Load Selector Switch Loadbreak Switch with Grounding Jaw
Two MVS load interrupter switch sections Eaton’s MVS load interrupter switches can The loadbreak switch can be supplied
can be used to provide cost- effective be used to provide the most cost-effective with optional grounding jaws for auto­
source selectivity with a common load source selectivity solution in a single matic grounding of the load circuit. When
side bus feeding one load (fused or compact structure with a two-position the switch is opened, the switch main
nonfused). Key interlocks are a standard Type MVS non-loadbreak selector switch blades engage grounding jaws to ground
feature provided to per­mit only one in series with the load break MVS switch. the load circuit. This feature cannot be
switch to be closed at one time and This selector switch is mechanically used in a duplex switch configuration.
prevent opening any switch door unless interlocked such that operation can be The ground jaw option is available at
both switches are open. performed only when the load interrupter 5–15 kV. It is meant for applying a static
switch is in the open position. Also, ground, and is not rated for carrying
neither the MVS switch nor the main door fault currents.
can be closed without the selector switch
being positively locked in one of the two
feeder positions.

K1 K1

95.40
K1 K1 (2423.2)

Door Door

Figure 8.1-5. Typical Feeder Switch with Optional


Grounding Jaw (5–15 kV)

Grounding
Jaw Arrestor
36.00 36.00 62.00
(914.4) (914.4) (1574.8)
Bottom
entry/
exit
Figure 8.1-2. Typical Duplex Switch Figure 8.1-3. Typical Two-Position Selector
Configuration with One K1 Key— Switch for Bottom Cable Entrance— Line
Dimensions in Inches (mm) Dimensions in Inches (mm)
Switch Top
entry/exit
Non 90.37
Load Bottom
(2295.4) entry/exit
Break
Selector Fuse
Switch

Load
Mechanical
Interlock Top
Load entry/
Break exit
Switch
2.19 62.00
(55.6) (1574.8)

Figure 8.1-6. Typical Section View of Feeder


Switch with Optional Grounding Jaws

36.00
(914.4)

Figure 8.1-4. Typical Selector Switch


Configuration—Dimensions in Inches (mm)

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
General Description 8.1-5

Construction

b
a
c
h
f
Switch with Hinged Screen Barrier Open
g g i High Quality Insulation
h h Bus and switch insulators, switch
drive rod barriers between phases,
and barriers between outer phases
and the housing, are of high strength,
non-hygroscopic, track-resistant glass
polyester as standard. Optional switch,
d fuse and main bus epoxy insulation
i system is available.
b j Red-Green Switch Position Indicators
k Provisions for Padlocking Switch
Open or Closed
l Provisions for Door and Switch
Key Interlocks
e m The Operating Handle
It is conveniently located behind a
Typical Switch with Front Door Open small access door giving the structure
a Switch Mechanism b Provisions for Padlocking Door a smooth homogeneous appearance
and discourages casual contact by
Quick-make, quick-break stored Handle not visible in the photo.
unauthorized personnel.
energy operation.
c Inspection Window
n Switchgear Assembly
The opening and closing of the switch A large 8.00-inch x 16.00-inch Rating Nameplate
blades is done by the operating spring. (203.2 x 406.4 mm) gasketed,
An operator’s actions only charge and rectangular, high impact viewing
release the operating spring. window permits full view of the
posi­tion of all three switch blades m
The switch blades cannot be operated through the closed door.
in any intermediate position. During
the closing operation, full clearance d Full Height Main Door
l
between blades and stationary The door has a return flange and two
contacts is maintained until the rotary latch-type handles to provide
switch mechanism goes over toggle. latching members held in shear. It n
closes over a projecting frame.
The switch mechanism has only
metal-to-metal linkage—no chains e Foot-Operated Door Stop j
or cables are used. f Grounded Metal Safety Barrier
Arc interruption takes place between Prevents inadvertent contact with any
copper-tungsten tipped auxiliary live part, yet allows full-view inspec­ k
(flicker) blade and arcing contacts with tion of the switch blade position.
a DE-IONT arc chute; no arcing takes g Door Interlock
place between the main blades and the
Prevents the door of the enclosure
stationary contacts to prolong the life
from being opened when the switch
of the main blades.
is closed. l
Blow-out forces cannot be transmit­ted h Switch Interlock
to the operating handle.
Prevents inadvertent closure of the
switch if the door of the enclosure
is open. Switch Operating Compartment Door Open

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
General Description 8.1-6

Mini-MVS (26-Inch Wide) Eaton’s Mini-MVS switchgear assemblies


are rated 200 A, 4.76 kV. The medium-
Optional Features
■ Enclosed type—indoor or outdoor
voltage Mini-MVS switchgear assembly
❏ Outdoor enclosure includes
is for use in power distribution,
transformer primary connections and space heater
isolation applications requiring a stand- Note: If the application requires a heater for
alone assembly, cable in/cable out condensation, an outdoor enclosure should
be selected.
terminations and manual operation.
The Mini-MVS switchgear assembly ■ Fused or unfused switch
is seismically qualified. The assembly ❏ If fused, Eaton’s Type CLE current
is listed by ULT or CSA. The switch is limiting fuses from 10E amperes to
available fused or non-fused. There is 200E amperes are supplied
an option for an outdoor enclosure.
■ Distribution type surge arresters,
Several built-in interlocks and safety
3 kV or 6 kV
features are provided (see below).
■ Spare fuses

Mini-MVS Switchgear Assembly


Standard Features
■ Seismically qualified
■ Manually operated switch
■ Door-to-switch safety interlocking
■ Auxiliary switch, one Form C contact
■ Viewing window for switch position
■ Provisions for padlocking the switch in
the OPEN position
■ Provision for padlocking the two door
handles closed
■ Spare fuse rack
■ Grounded metal screen barrier in front
of the switch
Mini-MVS Switchgear Assembly
W = 26.00 inches (660.4 mm) ■ Cycloalaphatic epoxy insulators
H = 66.00 inches (1676.4 mm) ■ Line, load and ground cable lugs for
D = 27.25 inches (692.2 mm) #6 solid-4/0 stranded cable aluminum
or copper
■ Key interlock provisions
■ Listed—UL/CSA

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
General Description 8.1-7

MVS and Mini-MVS Switchgear Assembly Ratings


Table 8.1-1. Switchgear Assembly Main Cross Bus Ratings
Rated Maximum Rated Rated Main Rated Momentary Rated Short-Time
Voltage BIL Bus Current Short-Circuit Current Short-Circuit Current (2 sec.)
kV kV Amperes kA Asym kA Peak kA rms Sym.

  4.76   60   600–1200   40   65 25


  4.76   60   600–1200   61   99 38
  4.76   60   600–1200   80 130 50
  4.76   60 1200 101 164 63
  4.76   60 2000   61   99 38
  4.76   60 2000   80 130 50
  4.76   60 2000 101 164 63
15   95   600–1200   40   65 25
15   95   600–1200   61   99 38
15   95   600–1200   80 130 50
15   95 1200 101 164 63

Table 8.1-2. Mini-MVS Ratings, rms Values


Description Unfused Fused

Rated maximum voltage   4.76 kV   4.76 kV


Impulse withstand voltage (BIL) 60 kV 60 kV
Low frequency withstand voltage 19 kV 19 kV
Frequency 60 Hz 60 Hz
Continuous current, maximum 200 A 200 A
Load current interrupting rating a 200 A 200 A
Magnetizing interrupting current     4 A     4 A
Short-time short-circuit current, 2 seconds, rms sym 12.5 kA b
Momentary current, asymmetrical/peak 20 kA/32.5 kA 101 kA/164 kA c
Fault close current, asymmetrical/peak 20 kA/32.5 kA 101 kA/164 kA c
a 100% to 80% power factor lagging.
b Not applicable for fused units.
c Rating with Eaton BHLE fuse.

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Devices 8.1-8

Switch Technical Data Table 8.1-3. Switch Ratings (Non-Fused)


Rated Impulse Continuous and Fault-Close & Momentary Rated Short-Time
Eaton’s MVS switch ratings have been Maximum Withstand Load-Break Short-Circuit Current Short-Circuit Current
thoroughly tested in recognized high Voltage (2 sec.)
power laboratories with certified kV kV Amperes kA Asym kA Peak kA rms Sym.
inspectors from both UL and CSA
organizations. Tests were performed   4.76   60   600 40   65 25
  4.76   60   600 61   99 38
to substantiate all published ratings in   4.76   60 1200 40   65 25
accordance with ANSI, IEEE, CSA and   4.76   60 1200 61   99 38
NEMA standards. 15   95   600 40   65 25
The testing program included tests of: 15   95   600 61   99 38
15   95 1200 40   65 25
■ Basic impulse levels 15   95 1200 61   99 38

■ Momentary withstand
■ Short-time withstand Table 8.1-4. MVS Switch Duty Cycle for Full Load Operations
■ Fault closing Rated Switch Load ANSI Required Eaton MVS Switch
Maximum Interrupting Number of Load Number of UL Tested
■ Load interrupting at various loads, kV Ampere Rating Interrupting Operations Load Break Operations
various power factors
  4.76   600 50 60
■ Mechanical life tests   4.76 1200 20 50
■ Temperature rise test 15   600 30 60
15 1200 10 50
These tests verified not only the
performance of the switch and
Table 8.1-5. MVS Switch Duty Cycle for Fault Close Operations—Non-Fused
integrated switch-fuse assembly, but
also the suitability of the enclosure Rated Switch Fault Close Rating ANSI Required Eaton MVS Switch Number
Maximum Number of Fault of UL Tested Fault
venting, rigidity and bus spacing. kA Asym kA Peak
kV Close Operations Close Operations
The mechanical life test subjected the   5 and 15 40 65 1 4
MVS switch to a number of no load cycles   5 and 15 61 99 1 1
greater than the requirements tabulated
in ANSI C37.22 standards. There were no
moving or current carrying part failures
as a result.
The Fault Close and Load Interrupting
test demonstrated significant improved
performance above ANSI/IEEE standards.
See Table 8.1-4 and Table 8.1-5 for results.

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Devices 8.1-9

Table 8.1-6. Primary Fuses, Standard Ratings and Fused Switch Fault Close Rating
Fuse Type Switchgear Rated Fuse Rated Continuous Rated Interrupting Fused Switch Momentary
Maximum Voltage, kV Current Range, Amperes Capacity kA and Fault-Close Rating a
Symmetrical a kA Asym kA Peak

RBA-200   4.76   10–200 19   30.4   49


RBA-400   4.76   10–200 25   40   65
RBA-400   4.76  0.5–400 37.5   60   97.5
RBA-800   4.76  0.5–400 25   40   65
RBA-800   4.76  0.5–720 37.5   60   97.5
BHLE   4.76   10–450 63 101 b 164
CLE600/750   4.76 600–750 40   64 104
RBA-200 15   10–200 14.4   23   37
RBA-400 15  0.5–400 25   40   65
RBA-400 15  0.5–400 29.4   47   76
RBA-800 15  0.5–720 25   40   65
RBA-800 15  0.5–720 29.4   47   65
HRBA-400 14.4  0.5–400 34.8   55.7   90
HRBA-800 14.4  0.5–720 34.8   55.7   90
BHLE 15   10–250 63 101 b 164
BHCL 15 300 63 101 b 164
a When RBA expulsion fuses are used, and two ratings appear, the lower rating applies when the lower-rated switch (15 kV, 40 kA fault close, 25 kA short-time
current) versus the higher rating that applies when the higher-rated switch (15 kV, 61 kA fault close, 38 kA short-time) is used.
b UL and CSA listed integrated rating with an Eaton BHLE or BHCL ­fuse.

Table 8.1-7. Metal-Enclosed Switchgear Fuse Correction Factors


Eaton Fuse Type kV Class Fuse Rated Continuous Current Enclosure Correction Factor (F1)

RBA 200/400/800 All All 1.0


CLE, HLE, BHLE, HCL   5.5   10–150 1.00
CLE, HLE, BHLE, HCL   5.5 175 0.94
CLE, HLE, BHLE, HCL   5.5 200 0.90
CLE, HLE, BHLE, HCL   5.5 250 0.81
CLE, HLE, BHLE, HCL   5.5 300 0.94
CLE, HLE, BHLE, HCL   5.5 350 0.84
CLE, HLE, BHLE, HCL   5.5 400 0.80
CLE, HLE, BHLE, HCL   5.5 450 0.84
CLE   5.5 600, 750, 1100 0.83
CLE, HLE, BHLE, HCL, BHCL 15.5   10–150 1.00
CLE, HLE, BHLE, HCL, BHCL 15.5 175 0.89
CLE, HLE, BHLE, HCL, BHCL 15.5 200 0.86
CLE, HLE, BHLE, HCL, BHCL 15.5 250 0.82
CLE, HLE, BHLE, HCL, BHCL 15.5 300 0.75

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Devices 8.1-10

Motor Operated MVS Description Manual Operation


A MVS Pow-R-Drive motor operated To operate manually, loosen the holding
Application switch is a standard, manually operated screw that keeps the pin connecting the
switch in combination with a heavy-duty linear actuator to the mechanism, and
Eaton’s MVS Pow-R-DriveE motor
electric motor-driven linear actuator that remove the pin. Remove the clevis pin
operator makes possible the safety
charges the spring. The linear actuator on the support of the bottom of the
and convenience inherent in remote
is located in a separate isolated low- linear actuator. Unplug the cord from
switch operation.
voltage compartment. During electrical the disconnect­ing terminal block as the
operation, it smoothly and quietly actuator is removed and set the actuator
extends or retracts the proper distance to aside. The switch can now be operated
cause the switch mechanism to operate. manually with the removable handle.
Standard motor operators are mounted in
the switch enclosure. This eliminates the
Lock Open Key Interlock
need for a separate motor compartment A keyed lock is standard to lock the switch
conserving floor space. in the open position only.
This lock not only locks the switch in
the open position, but also breaks the
electrical motor contacts integral to the
motor control circuit and permits the key
to be removed. With the key, the operator
can then open the lock on the switch door.
This scheme gives positive assurance that
the switch is open and cannot be closed
with the door open.

Motor Operated MVS Switch


Manual Operation Override

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Devices 8.1-11

Metering
Electronic Metering and Power Xpert and IQ Meters monitor Outdoor Enclosures
common electrical parameters and
Communications Apparatus communicate the data via standard Weatherproofing complying with the
MVS switchgear assemblies can be industry protocols and optional web requirements of IEEE standard C37.20.3 is
equipped with Eaton’s family of Power interfaces. Power Xpert Gateways available for MVS switch­gear assemblies.
XpertT and IQ digital meters to monitor consolidate devices into a single web The weatherproofing consists of sloped
a power circuit’s electrical quantities browser interface and provide Ethernet roof panels that are joined together with
within the capabilities of each device. connectivity. Eaton’s Foreseer web-based caps. Doors and rear covers are fully
software system can display, analyze and gasketed. Externally accessible louvered
Eaton’s power management products store data from multiple devices across filtered covers, top and bottom, front and
provide hardware and software solu­tions the facility to enable management of the rear, are provided for ventilation. At least
that allow customers to interface with customer’s power system. one 250 watt heater is provided in each
their switchgear at varying levels of vertical section. Power for the heaters
sophistication. may be supplied from an external source,
or an optional integral control power
transformer may be specified to provide
power for the heaters.

Outdoor Enclosure

Power Xpert Meter IQ 130/140/150/250/260


PXM 4000/6000/8000 PXM 2250/2260/2270/2280/2290

Electronic Metering

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Devices 8.1-12

Ohmic Voltage Sensing (OVS)


Eaton’s Ohmic Voltage Sensing (OVS) is an alternative to
traditional VTs in medium voltage. While traditional VTs are
susceptible to transients and ferro-resonance, the OVS system
is not. The OVS system consists of three resitive voltage divider
sensors connected to an amplifier. The sensors reduce the
voltage from the primary voltage to a lower voltage which is then
transmitted to the amplifier to provide an output of 120 Vac to
meters and relays (see Figure 8.1-7). The system can be utilized
with various meter and relay selections used in protection and
control schemes.
The OVS system is rated for applications 2.4 to 36 kV as a
replacement for VTs. The selection of sensors for the system
is dependent on the nominal voltage being applied to the
switchgear. The OVS systems must be applied with three sensors
installed line to ground; the low-voltage control circuit can be
configured to provide a line-to-line or a line-to-ground output
dependent upon the wiring to the relay or meter. Relays and
meters installed in the protection and controls scheme would Figure 8.1-8. OVS Sensors Mounted in Cable Compartment
process the signal from the OVS system in the same manner it
would a VT. The sensors are traditionally mounted in the rear OVS is not to be used to provide control power to devices in the
switchgear compartment (see Figure 8.1-8). However, if an switchgear, or to be used for utility metering applications.
existing installation requires the OVS system, it can be retrofitted
The OVS system has been tested to IEEE C37.20.2.2015 Annex D.
into the existing VT drawer.

Technical Data
Medium Voltage ■ 24 to 230 Vac or Vdc control power for amplifier
■ Voltage system accuracy better than 1%
■ Phase angle accuracy of better than 0.1% over frequency
OVS Sensors range of 2 kHz
■ Burden 0.78 VA L-L, 0.45 VA L-N

Amplifier

120 V Signal

Figure 8.1-7. Typical OVS System Setup

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Devices 8.1-13

System Options
Sensing and Monitoring The coupling capacitor sensor detects
Eaton’sType MVS metal-enclosed partial discharges within the switchgear
switchgear (2.4–27 kV) is corona-free by cubicle and/or adjacent cubicles, and is
design. By making switchgear assemblies typically installed on the load side of the
corona-free, Eaton has made its standard feeder switches or on the main bus. The
switchgear more reliable. However, as second sensor is a small donut type radio
indicated above, with time, airborne frequency current transformer (RFCT). It
particles, contaminants and humidity lead is designed for installation around the
to conditions that cause partial discharges ground shields of incoming or outgoing
to develop in switchgear operating at power cables. It detects partial dis­charges
Coupling Capacitor RFCT Sensor in power cables and monitors for external
voltages 4000 V and above.Type MVS
Type PD Sensor electrical noise.
switchgear can be equipped with factory-
installed partial discharge sensors and Typically one set of coupling capacitor
a partial discharge sensing relay for sensors is used at every two cubicles. One
continuous monitoring under normal RFCT sensor is used for each incoming and
operation.Timely detection of insulation outgoing power cable circuit.
degradation through increasing partial
discharges can identify potential problems Output signals from sensors (coupling
so corrective action can be planned and capacitor and RFCT) are wired out to
implemented long before permanent terminal blocks for future or field use,
deterioration develops. Partial discharge or connected to the InsulGard relay.
detection can be the foundation of an One InsulGard relay can monitor up to
effective predictive maintenance program. 15 input signals, as well as temperature
InsulGard Relay Trending of partial discharge data over and humidity. The temperature and
(PD Monitoring) time allows prediction of failures, which humidity sensors are included with each
can be corrected before catastrophic InsulGard relay system. The relay
Partial Discharge in Switchgear failure occurs. continuously monitors the switchgear
Partial discharge (PD) is a common name primary system for partial discharges
for various forms of electrical discharges The PD sensing and monitoring system and provides an alarm signal (contact
such as corona, surface tracking, and consists of Eaton’s InsulGardT relay and closure) when high PD level is detected.
discharges internal to the insulation. It PD sensors, specifically developed for Also, data analysis and diagnostics by
partially bridges the insulation between application in the switchgear to work Eaton engineers can also be provided
the conductors. These high frequency with the relay. There are two types of PD by remote communication with the
discharges are essentially small arcs sensors used in the switch­gear: the first InsulGard relay.
occurring in or on the surface of the sensor is a coupling capacitor type sensor
insulation system when voltage stress developed for use with 5 kV, 15 kV and The sensors and InsulGard relay are
exceeds a critical value. With time, 27 kV switchgear. optional in MVS switchgear.
airborne particles, contaminants and
humidity lead to conditions that result
in partial discharges. Partial discharges
start at a low level and increase as Input
the insulation becomes deteriorated. Temp Sensor Terminal InsulGard
Optional
Examples of partial discharge in Humidity Sensor
Block Relay
Modem
switchgear are surface tracking across
bus insulation, or discharges in the air
gap between the bus and a support
(such as where a bus passes through an
insulating window between the sections
of the switchgear). If partial discharge
activity is not detected and corrected, it 120 Vac
can develop into a full-scale insulation Auxiliary
failure followed by an electrical fault. Signals (up to 15 Total) from Power Output
PD Sensors (Coupling Capacitors, Alarm
Most switchgear flashover and bus RFCT Sensor, RTD Input, etc.) Status
failures are a result of insulation
degradation caused by various
forms of partial discharges. Figure 8.1-9. InsulGard Relay System

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Devices 8.1-14

Partial Discharge Sensors and Monitoring for Switchgear

Radio Frequency Current Sensor (RFCT)

Coupling Capacitor

PD Sensors

Figure 8.1-10. How the Process Works—Sensing and Data Collection

Coupling Capacitor detects partial discharges internal to


switchgear compartment.

RFCT detects partial discharges in customer’s cables up to 100 ft


from switchgear.

Figure 8.1-11. Typical Partial Discharge Sensor Connections in


MVS Switchgear (5–15 kV)
Note: Use one set of PD sensing capacitors at every two vertical sections,
or portion thereof. Use one RFCT at each incoming/outgoing cable circuit.

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Devices 8.1-15

MVS Switchgear with Automatic Transfer Control

ATC Controller
Two-Switch Automatic Transfer
Standard Features
Application Typical Two-Switch Automatic Transfer ■ Voltage sensing on both sources is
Using ATC Controller provided by the ATC controller
Eaton’s MVS switchgear with an
automatic transfer control system is an Eaton’s ATC-900 controller continu­ously ■ Lights to indicate status of switches,
integrated assembly of motor operated monitors all three phases on both sources sources, etc.
MVS switches, sensing devices and for correct voltages.The controller can be ■ Interlocking to prevent paralleling of
control components. Available in applied in a two utility or utility/generator sources via software
5–15 kV classes. arrangement. Should the voltage of the
normal source be lost while the voltage ■ Control power for the automatic
It is typically applied where the continuity of the alternate source remains normal, transfer control system is derived from
of service for critical loads from two the voltage sensing function in the ATC the sensing voltage transformers
power sources in either a main/main or a controller will change state starting the ■ Manual override operation
main/tie/main configuration is desired. time delay function. If the voltage of the ■ Open transition on return to normal
normal source is not restored by the end of
MVS switchgear with an automatic ■ Programmable time delays on
the time delay interval, the normal switch
transfer control system can meet most both sources, “OFF DELAY” and
will open and the alternate source switch
automatic throwover requirements as “ON DELAY”
will close, restoring power to the load.
it has a wide variety of operational ■ Four programmable digital inputs
sequences embodied in one standard and outputs
automatic transfer control system. ATC Controller
Eaton’s ATC controller is equipped to ■ Single-source responsibility; all
Please note that the duty cycle of load display history information via the front basic components are manufac­tured
interrupter switches is limited by ANSI panel. ATC-900 controller stores 320 time by Eaton
Standard C37.22. Refer to Table 8.1-4 stamped events. Oscillographic data for ■ Key interlocking of operating system
for maximum number of switching last 10 events can be downloaded via the and doors where required to provide
operations allowed. If the number of USB port or displayed in the controller’s operator safety
switching operations is expected to display window. The controller allows
exceed the maximum allowed, then load communications via RS-232 or Modbus
interrupter switches should not be used. Optional Features
through RS-485 port, Ethernet or via
Use circuit breakers (refer to Type MSB, ■ Lockout on phase and/or ground
USB interface.
MEB, MEF or VCP-W switchgear designs). overcurrents and/or internal bus faults
Also note that the operating times of ■ Blown fuse overcurrent lockout
Eaton’s motor operated load interrupter
■ Load current, power and PF metering
switches are much longer compared to
with optional dcT module
circuit breakers, therefore, the switches
are not suitable for closed-transition ■ 24 Vdc control power input
transfer applications. Use circuit breakers ■ Up to four additional I/O modules, each
if closed-transition transfer is required. with four programmable digital inputs
and digital outputs

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Devices 8.1-16

Surge Protection
IEEE standard C62.11 for Metal Oxide Surge Arresters lists the
maximum rated ambient temperature as 40 °C. The ambient
temperature inside an Eaton MVS switchgear vertical section
may exceed this temperature, especially in outdoor applications
where solar radiation may produce a significant contribution to
the temperature. Table 8.1-8 lists the recommended minimum
duty cycle voltage rating for various system grounding methods.
Surge arrester rating is based upon the ambient air temperature
in the switchgear vertical section not exceeding 55 °C.

Table 8.1-8. Suggested Minimum Ratings (kV) for Metal Oxide Surge Arresters Located in Metal-Enclosed Switchgear
Service Distribution Class Arresters Station Class Arresters
Voltage Solidly Grounded Low Resistance High Resistance or Solidly Grounded Low Resistance High Resistance or
Line-to-Line System Grounded System Ungrounded System System Grounded System Ungrounded System
kV
Arrester Ratings kV Arrester Ratings kV
Nominal MCOV Nominal MCOV Nominal MCOV Nominal MCOV Nominal MCOV Nominal MCOV

  2.30   3   2.55   3   2.55   3   2.55   3   2.55   3   2.55   3   2.55
  2.40   3   2.55   3   2.55   6   5.10   3   2.55   3   2.55   6   5.10
  3.30   3   2.55   3   2.55   6   5.10   3   2.55   3   2.55   6   5.10
  4.00   3   2.55   6   5.10   6   5.10   3   2.55   6   5.10   6   5.10
  4.16   6   5.10   6   5.10   6   5.10   6   5.10   6   5.10   6   5.10
  4.76   6   5.10   6   5.10   9   7.65   6   5.10   6   5.10   9   7.65
  4.80   6   5.10   6   5.10   9   7.65   6   5.10   6   5.10   9   7.65
  6.60   6   5.10   6   5.10   9   7.65   6   5.10   6   5.10   9   7.65
  6.90   6   5.10   6   5.10   9   7.65   6   5.10   9   7.65   9   7.65
  7.20   6   5.10   6   5.10 10   8.40   6   5.10   9   7.65 10   8.40
  8.32   9   7.65   9   7.65 12 10.20   9   7.65   9   7.65 12 10.20
  8.40   9   7.65   9   7.65 12 10.20   9   7.65   9   7.65 12 10.20
11.00   9   7.65   9   7.65 15 12.70   9   7.65 10   8.40 15 12.70
11.50   9   7.65 10   8.40 18 15.30   9   7.65 12 10.20 18 15.30
12.00 10   8.40 10   8.40 18 15.30 10   8.40 12 10.20 18 15.30
12.47 10   8.40 12 10.20 18 15.30 10   8.40 12 10.20 18 15.30
13.20 12 10.20 12 10.20 18 15.30 12 10.20 12 10.20 18 15.30
13.80 12 10.20 12 10.20 18 15.30 12 10.20 15 12.70 18 15.30
14.40 12 10.20 12 10.20 21 17.00 12 10.20 15 12.70 21 17.00
18.00 15 12.70 15 12.70 27 22.00 15 12.70 18 15.30 27 22.00
20.78 18 15.30 18 15.30 30 24.40 18 15.30 21 17.00 30 24.40
22.00 18 15.30 18 15.30 30 24.40 18 15.30 21 17.00 30 24.40
22.86 18 15.30 21 17.00 — — 18 15.30 24 19.50 36 29.00
23.00 18 15.30 21 17.00 — — 18 15.30 24 19.50 36 29.00
Note: MCOV = Maximum Continuous Operating Voltage.

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Layouts and Dimensions 8.1-17

MVS Layouts
Typical Arrangements—5 kV and 15 kV
The drawings in this section represent the most common require­ments, the addition of lightning arrest­ers, instrument
arrangements. Layouts shown are for rear-accessible equipment. transformers, special cable terminators, etc. Disconnect fuses may
Front-accessible designs are available—refer to Eaton. Many other require wider sections. Cables are shown out top and bottom for
configurations and combinations are available.Two voltage layout only.Top or bottom must be selected for incoming and for
transformers for customer metering and one control transformer outgoing cables. Structure depth is based on two 500 kcm XLP or
for auxiliary power can be mounted in the structures shown. For EPR insulated cables per phase using preformed slip-on cable
control power transformer larger than 1 kVA, additional space is termination devices. Refer to note below for minimum required
required. Depth of units will vary due to cable entrance and exit depth when more than two cables per phase are used.

Top
b 55.25 70.00 b
34.94–49.25 Entry (1778.0) 55.25 62.00
(887.5–1251.0) (1403.4) (1403.4) (1574.8)
Bottom
62.00
(1574.8)

Outdoor Outdoor Outdoor Outdoor Outdoor


95.50 95.50 95.50 95.50 95.50
(2425.7) (2425.7) (2425.7) (2425.7) (2425.7)
Indoor Indoor Indoor Indoor Indoor
90.38 90.38 90.38 90.38 90.38
(2295.7) (2295.7) (2295.7) (2295.7) (2295.7)

Outdoor
36.00 41.00 (1041.4) 36.00 36.00 20.00 36.00 36.00
(914.4) (914.4) (914.4) (508.0) (914.4) (914.4)
Indoor
36.00 (914.4)
Arrangement 1 Arrangement 2 Arrangement 3 Arrangement 4 Arrangement 5
Single Unit— Primary for Dry-Type Selector Switch Primary for Liquid Duplex Arrangement—
Cable In and Out a Transformer Filled Transformer Source Selective

b 55.25
b 55.25
(1403.4) (1403.4)

Outdoor
95.50 Outdoor
(2425.7) 95.50
(2425.7)
Indoor
90.38 Indoor
(2295.7) 90.38
(2295.7)

36.00 – 48.00 36.00 36.00 36.00


(914.4 – 1219.2) (914.4) 15.00 (914.4) (914.4) 36.00 – 48.00 36.00 36.00 36.00
(381.0) (914.4 – 1219.2) (914.4) (914.4) (914.4)

Arrangement 6 Arrangement 7
Main Incoming Metering Section (optional) Main Incoming Metering Section (optional)
with Main Switch and Feeders with Main Lugs Only Feeders

62.00 b 55.25
(1574.8) (1403.4)

Outdoor Outdoor
95.50 M M 95.50 M M M
(2425.7) (2425.7)

Indoor Indoor
90.38 90.38 PLC
(2295.7) (2295.7)
ATC

36.00 36.00 36.00 36.00 36.00 36.00 36.00 36.00


(914.4) (914.4) 15.00 (914.4) (914.4) 15.00 (914.4) 15.00 (914.4) (914.4) 15.00 (914.4)
(381.0) (381.0) (381.0) (381.0)

Arrangement 8 Arrangement 9
Two Switch Auto Transfer—Single Load Three Switch Auto Transfer—Main—Tie—Main with Feeders

Figure 8.1-12. 5 kV and 15 kV Typical Arrangements—Dimensions in Inches (mm)


a Mini-MVS switch unit in 26.00-inch (660.4 mm) wide, 27.25-inch (692.2 mm) Note: Width for Utility Metering Structures may vary.
deep and 66.00-inch (1676.4 mm) tall enclosure can be provided for 5 kV, ATC = AutomaticTransfer Controller (see Page 8.1-15)
200 A.
M = Motor Operator
b 62.00 (1578.4) for 15 kV MVS.
PLC = Programmable Logic Controller
Minimum depth of MVS unit: Up to two 500 kcm per phase: 55.00 inches
(1397.0 mm) or 62.00 inches (1574.8 mm) deep; three or four 500 kcm
per phase: 70.00 inches (1778.0 mm) deep, five or six 500 kcm per phase:
80.00 inches (2032.0 mm) deep.
Not to be used for construction purposes unless approved.

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Layouts and Dimensions 8.1-18

Typical Arrangements—MVS Connecting to Other Switchgear


The drawings in this section represent the most common requirements, the addition of lightning arresters, instrument
arrangements. Layouts shown are for rear-accessible equipment. transformers, special cable terminators, etc. Discon­nect fuses
Front-accessible designs are available—see Page 8.1-22. may require wider sections. Cables are shown out top and
Many other configurations and combinations are available.Two bottom for layout only. Top or bottom must be selected for
voltage transformers for metering and one control transformer for incoming and for outgoing cables. Cable sizing is based on
auxiliary power can be mounted in the structures shown. For two 500 kcmil XLP or EPR insulated cables per phase using
control power transformer larger than 1 kVA, additional space is preformed slip-on cable termination devices.
required. Depth of units will vary due to cable entrance and exit

20.00
(508.0)
Main Feeder
Switch Switch 62.00
a 55.30 a 55.30 (1574.8)
MVS AMPGARD MVS AMPGARD MVS MEF
(1404.6) (1404.6)
Switchgear Medium- 30.00 Switchgear Medium- 30.00 Switchgear Switchgear
Voltage (762.0) Voltage (762.0)
Starters Starters
36.00
36.00 36.00 36.00 36.00 (914.4) 26.00 or 19.00
(914.4) (914.4) 1.25 (914.4) (914.4) 1.25 (660.4 or 482.6)
(31.8) (31.8) Plan View
Plan View Plan View

Main
Switch
Switch
Feeder

AMPGARD AMPGARD
Medium- Medium- MEF
92.00
Voltage 92.00 Voltage 92.00

Switch
Feeder
(2336.8) Switchgear
90.40 Starters (2336.8) Starters (2336.8)
(2296.2)

36.00 20.00 36.00


(914.4) (508.0) (914.4) 36.00
(914.4) 26.00 or 19.00
Front View Front View (660.4 or 482.6)
Front View
Arrangement 1— Arrangement 2— Arrangement 3—Indoor MVS
Indoor Top Cable to MV MCC Indoor Bottom Cable to MV MCC Close-coupled to MEF Switchgear

4.00
(101.6)

Feeder VCP-W Feeder VCP-W


Switch Medium- Switch Medium-
Voltage Voltage
94.37 80.00 Switchgear
MVS Switchgear 96.25 MVS
(2397.0) (2444.8) (2032.0) Switchgear
Switchgear

36.00 36.00 36.00 36.00


4.60 (914.4) (914.4) (914.4) (914.4)
(116.8) Plan View Plan View
(Vac-Clad Main Bus Location Only)

VCP-W VCP-W
Medium- Medium-
Voltage
Voltage Switchgear
Switchgear
Switch
Feeder
Switch
Feeder

Switch
Feeder
Switch
Feeder

90.40 95.50
(2296.2) (2425.7)

36.00 36.00 36.00 4.00


(914.4) (914.4) (914.4) (101.6)
Front View
Front View
A) Depth—Section adjacent MVA, 80.00 inches (2032).
A) Depth 84.00 (2133.6) or 94.00 (2387.6) inches to rear align with MVA. B) Depth addition MVS sections 55.30 inches (1404.6).
B) Cable exit rear only, top or bottom. C) 2000A bus maximum.
Arrangement 4—Indoor to Metal-Clad Switchgear Arrangement 5—Outdoor Only to Metal-Clad Switchgear

Figure 8.1-13. Connections to AMPGARDT MCC (7.2 kV Maximum) and to VCPW Switchgear (15 kV Maximum)—Dimensions in Inches (mm)
a 62.00 (1578.4) for 15 kV MVS.
Not to be used for construction purposes unless approved.

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Layouts and Dimensions 8.1-19

Main Bus Main Bus

95.46 Taps
1.36
(2425.0)
90.37 (35.0)
(2295.0) Outdoor H1,2
Indoor Switch
5–15 kVA
90.37 CPT
95.46 Switch X1-4 (Single-
(2295.0) Phase)
(2425.0)
Outdoor Indoor
Fuse Fuse
Load Load
2.19 2.19
(56.0) (56.0)
31.60 31.60
(803.0) (803.0)

Depth Depth
See Table 8.1-9 See Table 8.1-11

Figure 8.1-14. Front Access Feeder Circuit—Fused or Unfused— Figure 8.1-16. Rear Access Feeder Circuit With Bus Connected CPT—
Dimensions in Inches (mm) Dimensions in Inches (mm)

Table 8.1-9. Front Access


Main Bus No. of Cables per Phase Minimum Structure Depth—Inches (mm)
(Based on 500 kcmil) 5 kV 15 kV

1 or 2 out bottom 34.94 (887.5) 34.94 (887.5)


1.36 1 or 2 out top 49.25 (1250.0) 49.25 (1250.0)
(35.0)
90.37 Table 8.1-10. Rear Access
(2295.0)
Indoor No. of Cables per Phase Minimum Structure Depth—Inches (mm)
Switch (Based on 500 kcmil) 5 kV 15 kV
95.46 Load
3 or 4 top or bottom 62.00 (1574.8) 70.00 (1778.0)
(2425.0) Fuse
Outdoor 5 or 6 top or bottom 70.00 (1778.0) 80.00 (2032.0)
Load
2.19
(56.0) 34.15 Table 8.1-11. Rear Access
(867.0)
No. of Cables per Phase Minimum Structure Depth—Inches (mm)
(Based on 500 kcmil) 5 kV 15 kV

1 or 2 top or bottom 62.00 (1574.8) 62.00 (1574.8)


Depth
See Table 8.1-10
Not to be used for construction purposes unless approved.
Figure 8.1-15. Rear Access Feeder Circuit—Fused or Unfused—
Dimensions in Inches (mm)

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Layouts and Dimensions 8.1-20

Main Bus Main Bus

95.46
(2424.7) 40.22
1.36 95.46
Outdoor (1021.6)
Taps (34.5) (2424.7)
Switch Outdoor Switch
5–15 kVA CPT Line
X1-4 H1,2 (Single-Phase)
90.37 90.37
(2295.4) (2295.4)
Indoor Indoor
Fuse Fuse
2.19
Load
(55.6)
2.19
(55.6) Load
34.15
(867.4)

Depth
Depth
See Table 8.1-12 See Table 8.1-14

Figure 8.1-17. Rear Access Feeder Circuit With Bus Connected CPT— Figure 8.1-19. Rear Access Cable In/Cable Out With Main Bus—
Dimensions in Inches (mm) Dimensions in Inches (mm)

Table 8.1-12. Rear Access


Main Bus No. of Cables per Phase Minimum Structure Depth—Inches (mm)
(Based on 500 kcmil) 5 kV 15 kV
Bottom
entry/
exit 1 or 2 out top 70.00 (1778.0) 70.00 (1778.0)
95.46
(2424.7)
Line
Outdoor Table 8.1-13. Rear Access
Switch
Main Bus No. of Cables per Phase Minimum Structure Depth—Inches (mm)
Top (Based on 500 kcmil) 5 kV 15 kV
entry/exit
90.37
Bottom 1 or 2 top or bottom 55.25 (1403.3) 62.00 (1574.8)
(2295.4) entry/exit
Indoor
Fuse
Switch
Table 8.1-14. Rear Access
2.19 No. of Cables per Phase Minimum Structure Depth—Inches (mm)
(55.6) Load (Based on 500 kcmil) 5 kV 15 kV
Top 3 or 4 top in/bottom out 62.00 (1574.8) 70.00 (1778.0)
entry/
exit 5 or 6 top in/bottom out 70.00 (1778.0) 80.00 (2032.0)

Depth
Fuse
See Table 8.1-13 Not to be used for construction purposes unless approved.

Figure 8.1-18. Rear Access Cable In/Cable Out With Main Bus—
Dimensions in Inches (mm)

Depth

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Layouts and Dimensions 8.1-21

20.00
(508.0)

18.00
(457.0)
Line
Line

110.37 Switch 115.46 Switch


(2803.0) (2933.0)
Indoor Outdoor

Fuse
Fuse
Load
Load

31.60
(803.0) 31.60
(803.0)

Depth
Depth
See Table 8.1-15
See Table 8.1-15

Figure 8.1-20. Front Access Indoor, Cable In/Cable Out— Figure 8.1-21. Front Access Outdoor, Cable In/Cable Out—
Dimensions in Inches (mm) Dimensions in Inches (mm)

Table 8.1-15. Front Access, Cable Exit—Top or Bottom


No. of Cables per Phase Minimum Structure Depth—Inches (mm)
(Based on 500 kcmil) 5 kV 15 kV

1 or 2 top in bottom out 34.94 (887.5) 34.94 (887.5)


1 or 2 top in top out 49.25 (1250.0) 49.25 (1250.0)

Not to be used for construction purposes unless approved.

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Layouts and Dimensions 8.1-22

Front Only Access Bottom Entry,


Top or Bottom Exit
16.00 (406.4)
16.00 (406.4) 16.00 (406.4)
10.00 (254.0) 10.00 (254.0)
10.00 (254.0) 10.00 (254.0) 33.00 (838.2) 13.00 (330.2)
Optional
Rear Door 1.25 (31.8)
1.50 (38.1) 1.50 (38.1) 1.50 (38.1)
8.00 (203.2) A&B 8.00 (203.2) A 8.00 (203.2) A

Roof Layout D Roof Layout D Roof Layout D


10 16 10

8.00 (203.2) B

Front 19.00 (482.6) Front Front

36.00 (914.4) 36.00 (914.4) 20.00 (508.0)


56.00 (1422.4)
16.00 (406.4)
10.00 (254.0) 10.00 (254.0) 42.00 (1066.8)
6.00 (152.4)
Optional 8.00 (203.2)
Rear Door 1.25 (31.8)
6.60 (167.6)
8.00 (203.2) A&B

Floor Layout Floor Layout D Floor Layout D


D
10 16 10 10 16 10 10 16 10
16.00 (406.4) B
8.00 (203.2) A 8.00 (203.2) A A
8.00 (203.2) 8.00 (203.2) Front 8.00 (203.2) Front

36.00 (914.4) 36.00 (914.4) 56.00 (1422.4)

Figure 8.1-22. 5 kV and 15 kV Roof Layouts and Floor Layouts—Dimensions in Inches (mm)
a Cable location not available with top main bus.
b When high continuous current fusing or instrumentation is required, consult the Eaton factory for guidance.
Note: A = Power Cable to Load. B = Power Cable from Source. See Figure 8.1-12 and Figure 8.1-14 through Figure 8.1-21 as applicable for dimension D
on Page 8.1-17 and Page 8.1-19 through Page 8.1-21.

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Layouts and Dimensions 8.1-23

Mini-MVS Layouts Arrester


Option
Mini-MVS Switch (5 kV, 200 A Only)
12.69
Dimensions and Weights (322.3)
a

6.00 17.38 Line


Maximum weight of switch assembly is (152.4) (441.5) Lug
550 lb (250 kg).

Cable
Routing
53.56 Area
2.12 (1360.4)
a
Entrance/Exit (53.8)
Load
27.25 Area Top Lug
(692.2)
16.38
(416.1)
15.00
(381.0)
29.50
4.11 Front 4.11 (749.3)
(104.4) 26.00 (104.4)
(660.4) a
Ground
Top View Lug

27.25
Front View w/o Door and (692.2)
Screen Barrier Non-Fused Switch
Side Section View Non-Fused Switch
2.12
(53.8) Figure 8.1-24. Front and Side View of Non-Fused Mini-MVS Switchgear Assembly—
Entrance/Exit
27.25
(692.2)
Area Bottom Dimensions in Inches (mm)
3.37 a Cable Size #6–2/0, 1/Phase.
(85.6)
Arrester
Option

4.11 Front 4.11 12.69


b
(104.4) 26.00 (104.4) (322.3)
(660.4) 6.00 17.38 Line
Floor Plan (152.4) (441.5) Lug

Lifting Plates

Cable
Routing
Area

53.56
Viewing (1360.4)
Window

66.25
(1682.8) Load
16.25 Lug
b
11.50 (412.8)
(292.1) Ground
Lug
b
Front View w/o Door and 27.25
Screen Barrier CLE Fused Switch (692.2)
Side Section View CLE Fused Switch

Figure 8.1-25. Front and Side View of Fused CLE Mini-MVS Switch Assembly—Dimensions in Inches (mm)
b Cable Size #6–2/0, 1/Phase.
26.00 Note: The Mini-MVS unit is designed for front access only or as front and rear access. Cable
(660.4) terminations are accessible from the front. Line and load cables can both enter from top, or both
Front View can enter from bottom, or line can enter from top and load can exit from bottom. However, for
California applications, line cables must enter from top, and load cables must exit from bottom.
The unit can be placed against the wall, with a minimum 6.00-inch (152.4 mm) clearance. For rear
Figure 8.1-23. Front View and Conduit Entrance— access applications, a minimum 30.00-inch (762.0) clearance is recommended. Check for additional
Dimensions in Inches (mm) NEC code clearance requirements.

EATON www.eaton.com
Metal-Enclosed Switchgear—MVS Medium-Voltage Design Guide DG022011EN
5–15 kV Load Interrupter Switch Effective September 2021
Application Data 8.1-24

Weights
. a Locations for tie-down 0.65 (16.5) diameter holes in four
places. Customer provided bolts for anchoring should be
0.50–13 min. SAE Grade 5 (M12 x 1.75 CL 10.9) and tightened
to 75 ft-lb (101.7 Nm).
b Door swing equals unit width at 90º.

5 7 c The standard minimum clearances on side. The authority


5.00 2
(127.0) 6 having jurisdiction may require a larger distance.
Typ.
Optional d Minimum clearances in front is the width of the widest
Rear Door vertical section plus 1.00 inch (25.4 mm). The authority having
4.25 jurisdiction may require a larger distance.
(108.0)
1.25 e The standard minimum recommended distance is 30.00
(31.8)
2.95 inches (762.0 mm) for assemblies requiring rear access for
(74.9)
installation and maintenance. The authority having
3 jurisdiction may require a larger distance.
6.00 6.00
(152.4) (152.4) f For MVS only. If the application is specifically provided by
Min. Min.
contract as not requiring rear access as stated in 5, then the
3 minimum recommended distance is 6.00 inches (152.4 mm).
1
g If optional rear door is supplied, the minimum is the width of
the widest vertical section plus 1.00 inch (25.4 mm). The
1.25 authority having jurisdiction may require a larger distance.
(31.8)
4.25
h Finished foundation’s surface shall be level within 0.06 inch
(108.0) (1.5 mm) in 36.00 inches (914.4 mm) left-to-right, front-to-
FRONT DOOR back and diagonally, as measured by a laser level.

Table 8.1-16. Approximate Weights in Lb (kg)


4
2 Switch Indoor Outdoor
Min. Description
5 kV or 15 kV Class
Non-fused switch 1500 (681) 1800 (817)
Fuses (3), add   200 (91)   200 (91)
Indoor transition   300 (136) —
Outdoor throat — 500 (227)
Figure 8.1-26. Typical Anchor Plan—5–15 kV Indoor or Outdoor
Not to be used for construction purposes unless approved.

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

© 2021 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. DG022011EN / Z25378 All other trademarks are property
September 2021 of their respective owners.

You might also like