Professional Documents
Culture Documents
Electrical Machines
G.C University, Lahore
Transformer
A Lossless device
i.e. no leakage flux,
Cu or eddy current loss
THE IDEAL TRANSFORMER
𝑑∅
• On primary side Vp = 𝑁𝑝
𝑑𝑡
(Faradays Law)
𝑑∅
• 𝑑𝑡
(change of flux) travels through the core towards
secondary coil. (No leakage flux, ideal transformer)
𝑑∅
• 𝑑𝑡
is due to the AC source as it changing frequency
𝑑∅
• So on secondary side, Vs = 𝑁𝑠
𝑑𝑡
THE IDEAL TRANSFORMER
• Ratio of primary and secondary voltages gives us
𝑉𝑝 𝑁𝑝 𝑁𝑝
• 𝑉𝑠
=
𝑁𝑠
= 𝑎, ℎ𝑒𝑟𝑒 𝑎 𝑖𝑠 𝑡𝑢𝑟𝑚 𝑟𝑎𝑡𝑖𝑜 𝑎 =
𝑁𝑠
• Since ∅𝑚 ≫
∅𝐿 𝑓𝑜𝑟 𝑝𝑟𝑖𝑚𝑎𝑟𝑦 𝑎𝑛𝑑 𝑠𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦 therefore
𝑉𝑝 𝑡 𝑁𝑝
• 𝑉𝑠 𝑡
=
𝑁𝑠
=𝑎
Magnetization Current
𝑉𝑏𝑎𝑠𝑒 480
• 𝑍𝑏𝑎𝑠𝑒 = 𝐼𝑏𝑎𝑠𝑒
= 20.83 = 23.04Ω
• The turns ratio of transformer T1 is a = 1/10 = 0.1, so the base voltage in
the transmission line region is
𝑉𝑏𝑎𝑠𝑒 1 480
• 𝑉𝑏𝑎𝑠𝑒 2 = 𝑎
=
0.1
= 4800𝑉
• Other quantities are
• 𝑆𝑏𝑎𝑠𝑒 2 = 10𝑘𝑉𝐴
10000
• 𝐼𝑏𝑎𝑠𝑒 2 = 4800
= 2.083𝐴
4800
• 𝑍𝑏𝑎𝑠𝑒 2 = 2.083 = 2304Ω
• The turns ratio of transformer T1 is a = 20/1 = 20, so the base
voltage in the load region is
𝑉𝑏𝑎𝑠𝑒 1 480
• 𝑉𝑏𝑎𝑠𝑒 2 = 𝑎
=
0.1
= 4800𝑉
• The other base quantities are
• 𝑆𝑏𝑎𝑠𝑒 3 = 10𝑘𝑉𝐴
10000
• 𝐼𝑏𝑎𝑠𝑒 3 = 240
= 41.67𝐴
240
• 𝑍𝑏𝑎𝑠𝑒 3 = 41.67 = 5.76Ω
• B) To convert a power system to a per-unit system, each component must
be divided by its base value
• The generator s per-unit voltage is its actual value divided by its base value
480∠0°
• 𝑉𝐺 , 𝑝𝑢 = 480
=1∠0° pu
• The transmission line s per-unit impedance is its actual value
divided by its base value:
20+𝑗60
• 𝑍𝑙𝑖𝑛𝑒 , 𝑝𝑢 = 2304
= 0.0087 + 𝑗0.0260 𝑝𝑢
• The loads per-unit impedance is also given by actual value
divided by base value
10∠30°
• 𝑍𝑙𝑜𝑎𝑑 , 𝑝𝑢 = 5.76
= 1.736∠30° pu
• The per-unit equivalent circuit of the power system is
shown in Figure
TRANSFORMER VOLTAGE
REGULATION AND
EFFICIENCY
• The output voltage of a transformer varies with the load
even if the input voltage remains constant.
• This is because a real transformer has series impedance
within it.
• Full load Voltage Regulation is a quantity that compares
the output voltage at no load with the output voltage at
full load, defined by this equation
𝑉𝑠 ,𝑛𝑙−𝑉𝑠,𝑓𝑙
• 𝑉𝑅 = 𝑉𝑠 ,𝑓𝑙
× 100
The Transformer Phasor
Diagram
• Consider the simplified
equivalent circuit referred
to the secondary side
• Voltage Regulation
depends on magnitude of
the series impedance and
the phase angle of the
current flowing through
the transformer
• Assume that the reference phasor is the secondary
voltage, VS. Therefore the reference phasor will have
0 degrees in terms of angle
• Based upon the equivalent circuit, apply Kirchoff
Voltage Law
𝑉𝑃
• 𝑎
= 𝑉𝑆 + 𝑅𝑒𝑞 𝐼𝑆 + 𝑗𝑋𝑒𝑞 𝐼𝑠
• Figure below shows a phasor diagram of a
transformer operating at a lagging power factor.
• For lagging loads, VP / a > VS so the voltage
regulation with lagging loads is > 0
• When the power factor is unity, VS is lower than VP
so VR > 0. But, VR is smaller than before (during
lagging PF).
• With a leading power factor, VS is higher than the
referred VP so VR < 0
Transformer Efficiency
• Transformer efficiency is defined as
𝑃𝑜𝑢𝑡 𝑃𝑜𝑢𝑡
• η= 𝑃𝑖𝑛
× 100 =
𝑃𝑜𝑢𝑡 +𝑃𝑙𝑜𝑠𝑠
× 100
𝑁𝑆𝐸
• 𝐼𝐶 = 𝑁 𝐼𝐿
𝑆𝐸 +𝑁𝐶
𝑆1∅,𝑏𝑎𝑠𝑒 (𝑉1∅,𝑏𝑎𝑠𝑒 )2
• 𝐼1∅,𝑏𝑎𝑠𝑒 = 𝑉 𝑎𝑛𝑑 𝑍𝑏𝑎𝑠𝑒 =
𝑆1∅,𝑏𝑎𝑠𝑒
1∅,𝑏𝑎𝑠𝑒
2
𝑆𝑏𝑎𝑠𝑒 3 𝑉∅,𝑏𝑎𝑠𝑒
• 𝐼1∅,𝑏𝑎𝑠𝑒 = 3𝑉𝑏𝑎𝑠𝑒
𝑎𝑛𝑑 𝑍𝑏𝑎𝑠𝑒 =
𝑆𝑏𝑎𝑠𝑒
WYE-DELTA CONNECTION
• WYE-WYE CONNECTION
𝑉L𝑝 3𝑉∅𝑃
• 𝑉𝐿𝑆
=
3𝑉∅𝑆
= 𝑎
• If loads on the transformer circuit are unbalanced, then the voltages on the
phases of the transformer can become severely unbalanced
• Third-harmonic voltages can be large.
• WYE-DELTA CONNECTION
𝑉L𝑝 3𝑉∅𝑃
• 𝑉𝐿𝑆
= 𝑉∅𝑆
= 3𝑎
• the secondary voltage is shifted 30" relative to the primary voltage of the
transformer