Steam Turbine Control System

Description General Description

The turbine has a hydraulic speed control valves MAB10+20AA002 and


governor MAX46BY001 and an electro- reheat stop valves MAB10+20AA001 is
hydraulic turbine controller. The hydraulic routed into condenser MAG10BC001
speed governor adjusts main & reheat through LP bypass valves.
control valves MAA10+20AA002 and
The IP turbine is fitted with its own control
MAB10+20AA002 by way of hydraulic
valves to prevent steam remaining in the
amplifier MAX45BY011 whilst: the electro-
reheater from entering the turbine via the
hydraulic turbine controller adjusts these
IP section and causing further acceleration
control valves by way of electro-hydraulic
of the turbine after the main steam control
converter MAX45BY001.
valves have been closed due to a load
Hydraulic amplifier MAX45BY011 and rejection condition. In addition the steam
electro-hydraulic converter MAX45BY001 pressure in the main steam line would
are switched in parallel to form a minimum build up after sudden closure of the main
value gate. The system not exercising steam control valves, thus causing the
control at any given time is at its maximum relief/HP bypass valves to open, with the
position. result that even more steam would flow
into the IP section of the turbine.
The special operating conditions existing
in reheat condensing turbines necessitate The oil supply is maintained by main oil
additional control elements. On start-up of pump MAV21AP001, driven directly by the
the high-pressure boiler, it is necessary to turbine shaft, and by two electrically driven
start up with a considerable steam rate full-load auxiliary oil pumps and one
straight away and, due to the high electrically driven bearing oil pump.
temperature in the reheater, to admit
The turbine is equipped with an electro-
steam to the reheater immediately.
pneumatic gland steam control system,
As long as the HP section of the turbine is high pressure electro-hydraulic bypass
unable to accommodate all the steam system and an automatic turbine tester for
supplied by the boiler. The rejected steam the protective devices, main stop and
is routed directly to the reheater via the control valves and reheat stop and control
relief valve/HP bypass valve. The steam valves and an automatic functional group
from the reheater, which can not be control.
accommodated by the IP section with its

BHEL Bhopal 2-2100-07