You are on page 1of 23

P1: GNH/GWT P2: GPB Final Pages Qu: 00, 00, 00, 00

Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators
Dean B. Harrington
General Electric Company, Retired

I. Introduction
II. The Generator System
III. Description
IV. Rating Range
V. Capability
VI. Characteristics
VII. Requirements
VIII. Excitation System
IX. Electromagnetic Design
X. Mechanical Design

GLOSSARY number of pairs of poles and by 360. One pole pitch of


any machine is 180 electrical degrees.
Air gap Annular region between the rotor body and the Excitation Magnetomotive force of the field-winding
stator core. current (dc), which produces the magnetic flux in a
Apparent power Product of the magnitudes of voltage synchronous machine. Thus, the field current “excites”
and current. (Power is the product of apparent power the generator. The process of applying the field current
and power factor.) Used in ac systems. is also called excitation. Field current is also called
Armature reaction Magnetomotive force of armature “excitation current.”
current. Exciter Source of field-winding current.
Armature winding That winding in which alternating Field winding That winding which carries the current
voltage is generated by virtue of the relative motion of that excites the generator.
the rotor-produced magnetic flux field. Magnetomotive force (mmf ) Driving force for magnetic
Direct axis Angular position of the peak of the sinu- flux, taken as the product of current and the number of
soidal component of radial air-gap flux produced by turns per pole in a winding or circuit.
field-winding current. It is commonly at the center of a Quadrature axis Angular position of zero value of the si-
pole. nusoidal component of radial air-gap flux produced by
Electrical degree Angle, measured about the center line field-winding current. It is commonly located midway
of a machine, of the complete circle divided by the between two adjacent poles.

193
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

194 Turbine Generators

Rating Values of those quantities which are needed to as total energy per year), based on trends throughout this
define the required function and hence the design of century. Therefore, the generators that provide the electric
a generator. These quantities are (1) apparent power, power are a key element in the way of life of the entire
(2) power factor, (3) voltage, (4) frequency, (5) speed, population.
and (6) hydrogen pressure (if hydrogen is used). Power, rather than energy, is basic to turbine generator
design and operation. Energy is important in considering
fuel supplies, but power is the key parameter in any appara-
A TURBINE GENERATOR is a high-speed syn-
tus or system that handles, converts (i.e., from mechanical
chronous ac generator suitable to be driven by a steam
to electrical), transmits, or utilizes it. The term “energy,”
turbine or a gas turbine. It is also known informally as a
accordingly, is rarely used in this article.
“turbogenerator,” a term that in some countries is used
The turbine generator is presented briefly in this article
to describe a type of machine, regardless of its prime
by (1) direct description, (2) its attributes and characteris-
mover: a high-speed synchronous generator using a cylin-
tics, (3) what is required of it, and (4) how it is designed,
drical rotor made from a solid steel forging. The most
so that the machine can be perceived from many angles
common rated speed is 3600 rpm in the United States
and can thus be understood.
and those other countries in which the power system
has a frequency of 60 Hz, and 3000 rpm in countries
using 50 Hz. Where the prime mover requires a some- A. Design
what lower speed, a speed of 1800 or 1500 rpm may be
employed. Turbine generators range from relatively small machines
to the highest ratings of any rotating electric machines
produced. They are technology intensive. That is, they are
highly refined designs in which each component is the
I. INTRODUCTION result of extensive development and careful engineering
design. Many components require materials and processes
Essentially all of the electrical power in any country is that have been developed specifically for use in a turbine
supplied by synchronous generators. Approximately 85– generator.
95% of the electric power generated in the United States Figure 1 shows a large steam-turbine generator in a
is derived from a thermal power source using a thermo- power station, with its exciter (left) and steam-turbine
dynamic cycle that employs a high-speed steam-turbine- prime mover (right).
or a gas-turbine-driven generator, commonly called a tur- A turbine generator is a power converter that transforms
bine generator. This is less than a perfect distinction since the mechanical power delivered to it from the shaft of its
virtually all of the remaining electric power is gener- prime mover, into electrical power. It is a magnetic device
ated by hydraulic-turbine-driven generators, commonly in which a rotating magnetic flux produced by current in
called hydrogenerators, which are usually large slow- a field winding on the rotor generates voltages in three
speed machines. phases of an armature winding mounted on the stator. The
Fossil-fuel and nuclear steam supplies are used as the armature-winding terminals are connected to the power
steady electric power supply for “base” loads. Fossil steam system of which the generator is a part. Torques in the
plants are also used for variable loads, including peaks, generator, which are a consequence of armature-winding
where many hours of operation per year are required. currents, and, therefore, also of power system currents,
Gas turbines tend to be less efficient than steam tur- are such as to cause the rotor of the generator to rotate
bines because of the high exhaust temperature and the
heat loss in the effluent gas. Gas-turbine generators are
used where low initial powerplant cost and speed of con-
struction are important, and many peaking power appli-
cations have been made on this basis. In locations where
fuel costs are extremely low, gas turbines are occasionally
used for normal power production.
Using a gas turbine as a “topper” with a steam turbine
operating on the exhaust energy in a combined cycle pro-
vides efficiency higher than that of a steam-turbine cycle.
The gross national product of most countries has been
found to follow very closely the power, and particularly FIGURE 1 Large steam-turbine generator in a power station.
the electric power used by the economy (usually expressed (Courtesy of the General Electric Co.)
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 195

in synchronism with the power system and with all other than 6000 A may be required. The exciter may be a rotat-
synchronous machines in the power system. When either ing machine, a stationary device, or a combination of the
steady or transient conditions cause the machine to lose two.
this synchronous relationship with the power system, it is
said to have lost stability. This can interrupt the successful C. Excitation Control System
operation of the power system and damage the turbine
generator set, if the condition is permitted to persist. The excitation control system controls the generator by
controlling the exciter. Briefly, its functions are (1) to con-
trol the output voltage of the generator by its “voltage
B. Requirements
regulator,” (2) to keep the exciter output current within
A turbine generator must supply the power system of an prescribed limits, and (3) to enhance the stability of the
electric utility or an industrial enterprise with the active power system.
and reactive power needed, respectively, to supply the load
needs of all users of power, and to maintain the voltages D. Hydrogen Supply System
in the power system to keep it operating effectively. It
must function well in the power system in the steady state Many turbine generators use hydrogen as the ventilating
as well as during sudden or slowly changing events. To medium. In such machines, hydrogen at a purity of ap-
the extent that the generator is durable and forgiving, it proximately 98% is maintained from a continuous supply
contributes to the economic design and operation of the of commercial purity, which replaces gas lost at a low rate
power system. Its inherent tolerance, however, for severe by scavenging, by absorption in the seal oil, and through
conditions is limited and it may be unjustifiably costly untraceably small leaks in the hydrogen containment. A
to construct a machine with significantly more capability pressure regulator holds the hydrogen pressure at a level
for certain conditions. The final choice of specified gen- selected by the operator. Valving is provided to purge the
erator performance and power system design is based on generator of air by an inert gas, such as carbon dioxide,
the economic considerations of first cost and operating before introducing hydrogen, and to purge the hydrogen
expense. before introducing air.
Reliability and availability of a turbine generator are
most important. The cost of not having a needed generator E. Seal Oil System
in service is extremely high even on a daily basis. Oil is used to prevent leakage of hydrogen along the shaft
As a dynamic part of the power system, a turbine gen- at each end of the generator. Oil is provided at sufficient
erator, through its specified rating and characteristics in- pressure to contain the hydrogen pressure, in sufficient
cluding its excitation system, must contribute to the stable quantities to remove the viscous losses in the seals, while
operation of the power system. maintaining proper temperature of the close-fitting parts.
Hydrogen that is absorbed by the oil is removed by a
II. THE GENERATOR SYSTEM “detraining” process, which some manufacturers do in a
vacuum.
A turbine generator that is part of an electric power system
is itself a system. All parts of the generator system work F. Armature-Winding Water-Cooling System
together to make the generator function successfully. The
key elements of the generator system will be described Modern large turbine generators commonly have water-
briefly. cooled armature windings. (The rating range for this fea-
ture varies among the various manufacturers.) Cooling
water must pass from ground potential to points on the
A. Generator
winding which may be above 15,000 V. Water of extreme
The heart of the generator system is the generator, itself. purity is provided by the cooling water system to maintain
It converts mechanical power from its drive turbine into water conductivity at a satisfactorily low value. A deioniz-
electrical power at a suitable voltage and frequency. ing system is commonly used. Storage, cooling, pumping,
and filtering are provided.
B. Exciter
G. Bearing Lubrication System
A source of dc power that is fully and rapidly control-
lable is required by the field winding of the generator. Lubricating oil is pumped to the bearings by the bearing
For large generators, ratings of 4000 kW or more at more lubrication system which also stores the oil, cools it to
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

196 Turbine Generators

dissipate the bearing losses, and filters it. This function is


normally provided by the lubrication system of the prime
mover.

III. DESCRIPTION

Being a synchronous machine, a turbine generator em-


ploys a steady magnetic flux passing radially across the
air gap at two or four poles (on rare occasions, six) on
the rotor. This flux pattern, which varies approximately
sinusoidally about the periphery of the rotor, rotates in
synchronism with the rotor, past a three-phase armature
winding located on the stator, and generates therein an al-
ternating voltage, which is very nearly sinusoidal, in each
phase. The armature winding is the output winding, de-
livering three-phase power to a connected electric power
system. FIGURE 2 Cross section of a two-pole generator, showing useful
flux. (Courtesy of the General Electric Co.)

A. Frequency and Speed


One cycle of alternating voltage is generated in each phase known as the air gap separates the slotted outer surface of
of the armature winding each time one pair of magnetic the rotor from the slotted inner surface of the stator. On
poles (one “north” and one “south”) of the rotor-produced “open circuit,” that is when the armature winding is carry-
flux passes a fixed point on the stator. The frequency of ing no current, the flux is produced by the magnetomotive
stator voltage, in hertz, is equal to the speed of the rotor in force (mmf) of the field winding on the rotor. Lines of flux
revolutions per second, multiplied by the number of pairs for this condition are shown.
of poles. The following equation expresses this frequency As can be seen in the figure, the major elements of the
relationship: magnetic circuit are (1) the solid steel rotor, including the
rotor core (below the slots) and poles, (2) the air gap, the
f = NP/120 (1) principal reluctance in the circuit, and (3) the laminated
where f is frequency (Hz), N speed (rpm), and P number steel stator core, including the stator teeth and stator yoke
of poles (must be divisible by 2). A two-pole generator is (outside the slots).
used when the highest possible speed is desired. It should be noted that the air gap does more than pro-
In the United States, Canada, the southern part of Japan, vide a nonrubbing separation between the rotor and the
and several other countries, the electric utility systems stator. The reluctance of the magnetic circuit affects the
use a frequency of 60 Hz. Equation (1) fixes the speed steady-state stability of the generator. The higher that re-
of the generator at 3600 rpm for a two-pole generator, luctance, the more stable the generator tends to be. This is
or 1800 rpm for a four-pole generator. In virtually all of discussed in relation to “short-circuit ratio” in Section IV.
the remaining countries, 50 Hz is the standard frequency.
There, the generator speed is most commonly 3000 rpm. C. Field Winding
A few generators are built for 1500 rpm.
The economics of the design of the prime mover de- The field winding is located in slots and is distributed
termine which speed is used. Gas turbines tend to be around the rotor, between poles. These slots, which are ma-
high-speed machines, and indeed small gas turbines are chined in the solid rotor body, are shown roughly in Fig. 2.
geared down to permit the generator to run at 3600 or The winding is made up of series-connected concentric
3000 rpm. Steam turbines are generally designed for 3600 coils, each located in a pair of slots in corresponding po-
or 3000 rpm, but some are designed for 1800 or 1500 rpm. sitions on opposite sides of a pole. Methods of varying
A tabulation of rated speed is presented in Section IV. sophistication are used to remove the heat produced in the
field winding conductors. There are significant differences
in the designs used by different manufacturers around the
B. Magnetic Circuit
world. It is common in small turbine generators to use
The magnetic circuit of a 2-pole turbine generator is shown “conventional cooling,” where the heat is removed by con-
in Fig. 2, which is a cross-section view. The circular region duction through the ground insulation to the rotor body.
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 197

For many medium-size turbine generators and for large bars, or coils having a few turns may be used to achieve
units the field windings are “conductor cooled.” Cooling the specified voltage.
passages are provided within the conductors themselves Each slot normally has two coil sides, one above the
to eliminate the temperature drop across the ground insu- other. The armature current causes alternating magnetic
lation as a major impediment to heat removal. It is com- flux at the power-system frequency to cross the slot. To
mon to use the machine’s ventilating gas as the coolant. reduce eddy currents produced in the conductors by this
However, a few manufacturers use purified water as the flux to an acceptable level, the conductors within each
coolant. turn are subdivided into thin rectangular strands. To reduce
Gas-conductor-cooled field windings are built to a num- currents which the flux would cause to circulate among the
ber of different designs. In an “axially cooled” system, the strands, they are transposed so that each strand occupies
gas passes through axial passages in the conductors, be- essentially every radial position in the slot.
ing fed from both ends, and exhausted to the air gap at the The winding is composed of three phases, wye con-
axial center of the rotor. In other designs, radial passages nected, and designed to produce voltages one-third of a
in the stack of conductors are fed from subslots machined cycle (120◦ ) apart in time phase. Each phase may have
along the length of the rotor at the bottom of each slot. one or more parallel circuits. Phase belts are usually se-
In yet another design, a “zoned” or “gap-pickup” method lected and connected to form each of the circuits in such
is used whereby the cooling gas is picked up from the air a way that the generated voltages in the circuits of each
gap, is used to cool a relatively short length of the rotor, phase are equal in magnitude and phase angle.
and is then discharged back to the air gap. The cooling Conventionally cooled windings are used in small,
of the end regions of the winding varies from design to medium, and many large generators. The heat generated
design, as much as that of the slot section. in the conductors is removed by conduction through the
Current is supplied to the field winding by two different ground-insulation wall. Conductor-cooled armature wind-
approaches, according to present-day practice. In the first ings are used in many large generators. Here, the coolant
approach, direct current is supplied by the exciter through passes along the bar, inside the ground insulation. The
a collector that has two rings on the rotor shaft, one for each coolant is either hydrogen or water.
polarity, and a sliding contact through graphite “brushes.” In a hydrogen-conductor-cooled bar, the gas passes
In the second approach, the exciter produces a polyphase from end to end in rectangular ducts with low-conductivity
ac output from the winding on its rotating element. This nonmagnetic metal walls. These ducts are insulated using
output is rectified by rotor-mounted rectifiers, and direct a system similar to strand insulation and are stacked in a
current is delivered to the field winding directly without column alongside the copper conductors. Cooling is very
requiring a collector. effective since the impediment to heat flow is very much
thinner than the ground insulation.
In a water-cooled bar, the coolant passes through hollow
D. Armature Winding
rectangular copper strands which are insulated and trans-
The armature winding is made up of coils which are dis- posed. It is usually not necessary for all of the strands
tributed around the inner periphery of the stator in equally to be water cooled. The hollow strands are interspersed
spaced slots, so as to be linked by the flux produced by among solid strands, which being thinner, have lower
the field winding. The coils are short pitched (the separa- eddy-current loss, thus contributing to high generator ef-
tion of the two slots occupied by a coil is less than 180 ficiency. Figure 3 is the stator of a large steam-turbine
electrical degrees) to minimize the harmonic content of generator showing the end region of the water-cooled ar-
the generated voltage. Adjacent coils which belong to the mature winding.
same phase form a “phase belt.” There is a phase belt for
each phase for each pole. The polarity of the connection
E. Rotor and Shaft
of the coils in the successive phase belts of a given phase
is reversed to accommodate the alternating “north” and The rotor is made from a single steel forging or as an
“south” poles of rotor-produced flux. assembly of a few forged parts. The rotor material is highly
For medium- and large-size turbine generators, each stressed in operation, particularly in large two-pole turbine
coil is made up of two single-turn bars (also called “half- generators. Thus, the steel must have excellent mechanical
turns”). Bars are used to avoid the strains which would properties, as well as good magnetic characteristics. The
be produced in completed coils during assembly into the teeth that separate the slots carry the centrifugal load of
slots. These bars have a large cross section and are quite the coils while providing as much space for conductors
rigid. One turn per coil is appropriate for the voltages of as possible. Wedges at the top of the slots transmit the
these generators. For small turbine generators, two-turn radial load of the coils to the teeth. The rotor end windings
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

198 Turbine Generators

A stator core for a large turbine generator may contain


over 200,000 punchings. These punchings are clamped ax-
ially to cause them to act as a solid mechanical body. Two
basic methods are used to achieve the axial clamping force.
In one, “through bolts” are passed through holes punched
in the core yoke. In the other, the axial key bars behind
the core to which the punchings are assembled are used to
apply the force. Pressure is spread over the surface of the
end punchings using plates, or ring flanges. “Fingers” (or
“outside space blocks”) are used to extend the clamping
pressure to the ends of the teeth. Friction between punch-
ings causes them to transmit peripheral bending stresses.
Bonding of punchings may be used in places to help assure
the mechanical integrity of the core.
The laminated construction is used to limit eddy-current
losses due to the alternating flux that the core carries. To
FIGURE 3 Stator of a large turbine generator with a water-cooled
accommodate stray flux impinging on the ends of the core,
armature winding. (Courtesy of the Westinghouse Electric Corp.) the ends of the teeth are commonly slit to reduce eddy
currents that are produced in the end punchings.
are held in against centrifugal force by retaining rings It is common to cool the stator core with gas (air or hy-
(also called “end bells”), usually of very high-strength drogen), and radial ducts are generally provided in the
nonmagnetic steel. core for this purpose. Water cooling is used by some
A high-speed rotor is long and relatively slender, par- manufacturers.
ticularly for a two-pole generator. At rated speed, the rotor In a two-pole generator, the stator core experiences a
may operate above its second or even third critical speed, rotating inward magnetic pull at the two diametrically op-
which requires sophisticated balancing. posite locations of maximum air-gap flux density, deflect-
Figure 4 shows the rotor of a large 3600 rpm steam- ing the core a few thousandths of an inch (of the order
turbine-driven generator. The four rings on the rotor body of 0.1 mm) from a circle to an oval. The result is a vi-
help to subdivide the air gap into ventilation zones. bration at a frequency twice that of the power system,
which, in medium and large generators, must be isolated
F. Stator so that it is not felt by the foundation and the surround-
ing building. This is accomplished by spring mounting the
The stator core is built up of thin punched laminations of core. The detail designs of the various manufacturers vary
electrical grade steel, which are commonly called “punch- substantially, but they all must provide vibration isolation
ings.” They are segmented, meaning that 12 to 24 punch- while supporting the weight of the core and handling both
ings are laid side-by-side to form a complete 360◦ ring, steady and high transient torques developed in the stator
comprising one layer. Each layer is “staggered” relative core.
to the locations of the gaps between punchings in the lay- A stator frame is provided to support the stator core,
ers below and above to assure a sound body of assembled and to contain the ventilation circuit of the generator.
punchings. For medium and large generators, hydrogen of noncom-
bustible purity is commonly used, at elevated pressure
(commonly 3–6 atm absolute). The stator frame provides
containment for the hydrogen, and normally houses
coolers to dessipate those generator losses absorbed by
ventilation.

G. Ventilation
1. Ventilation Circuit
Gas (air or hydrogen) is circulated throughout the genera-
tor by shaft-mounted fans (also called blowers) to remove
FIGURE 4 Rotor of a large turbine generator. (Courtesy of the heat generated as losses in the windings, in the stator core,
Westinghouse Electric Corp.) in the air gap (rotor windage), and in structures (losses
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 199

properties are such that its heat transfer coefficient is 50%


more effective than that of air at the same pressure. Thus,
hydrogen is much more effective in “washing” heat from
a heated surface.
The heat capacity per unit volume (the product of spe-
cific heat at constant pressure and density) of hydrogen
is approximately equal to that of air at the same pres-
sure. Thus, the temperature rise of hydrogen would be
approximately the same as that of air if the same volume
flow rate of the two gasses were used to remove the same
FIGURE 5 Cutaway drawing showing the ventilation circuit of a amount of heat. Actually, the temperature rise is substan-
large turbine generator with zoned rotor cooling. (Courtesy of the tially reduced because the fan and windage loss is reduced
Westinghouse Electric Corp.) in hydrogen.

induced by stray alternating magnetic fluxes). Hot rotor


gas is discharged to the air gap, having absorbed field- H. Hydrogen Containment
winding losses. Being combustible, hydrogen must be maintained at a pu-
A variety of ventilation patterns is provided by the vari- rity well above 75% or below 4%. A purity of 98% and
ous manufacturers for the different machine sizes. Figure 5 above is commonly maintained. It is also important to
is a cutaway drawing showing the ventilation circuit of a keep the hydrogen content of the air outside the generator
large steamturbine generator with zoned cooling of the at a low level to assure safe operation of the power plant.
rotor. To minimize hydrogen escaping from the generator, great
An air-cooled turbine generator is commonly open ven- care in design, installation, and operation is required. The
tilated, taking its air from the surroundings, and discharg- primary containment of the hydrogen is provided by the
ing warm air to the surroundings. Closed-circuit air-cooled stator frame.
machines and hydrogen-cooled generators dissipate heat To prevent hydrogen from escaping along the shaft, a
absorbed by the gas, through coolers to a circulating water close-clearance oil seal is provided. The design must ac-
system. commodate axial motion of the shaft up to 2 in. (5 cm)
or more due to variations in steam-turbine temperatures.
2. Air Both journal-bearing and thrust-bearing configurations
Air cooling is relatively simple. Air is an effective venti- are used by different manufacturers to provide a shaft
lating gas for small turbine generators. Here the benefits seal.
of hydrogen, evaluated on an economic basis, are not suf-
ficient to justify the hydrogen containment design of the
machine, and the hydrogen supply facilities. There are IV. RATING RANGE
also special considerations, such as simplicity of station
design or operation, that may justify using air cooling for A. Apparent Power
medium-size generators. This has been the case for cer-
The rating of a turbine generator is defined as the ap-
tain power plants using gas-turbine generators and also for
parent power, MVA (rather than the power, MW), that is
certain steam plants.
required, primarily because the physical size of the ma-
chine is largely determined by the product of the voltage
3. Hydrogen
and the current. The design of a generator will vary ac-
Hydrogen is the most effective gas that has been found for cording to the economic requirements and the required
ventilating a rotating machine. It is used in large turbine sophistication appropriate to different ranges of apparent
generators and generally in medium-size machines. power. These ranges are referred to in various parts of
Hydrogen’s density at 98% purity is of the order of one- this article, according to the following very approximate
tenth that of air at a comparable pressure. This reduces the definitions: small turbine generators, 2–20 MVA; medium
fan and windage loss to such a low value, that it is feasible turbine generators, 20–200 MVA; and large turbine gen-
to raise hydrogen pressure to as much as 75 psi (517 kPa) erators, 200 MVA and up.
relative to atmospheric pressure without adversely af- Gas-turbine generators have been built with ratings
fecting efficiency. This higher pressure greatly increases up to approximately 130 MVA. Steam-turbine genera-
the heat-removal capability of the hydrogen. Hydrogen’s tors have been built with ratings up to approximately
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

200 Turbine Generators

1600 MVA. The upper limits of ratings may continue to TABLE I Rated Speeds of Turbine Generators
be increased in accordance with need and technology. Power system frequency

Generator 60 Hz 50 Hz
B. Power Factor
Gas-turbine generators 3600 rpm 3000 rpm
Generator power factor has great significance in a power
Tandem-compound steam-turbine generators
system, as is discussed in relation to “control system” in
Fossil-fuel steam supply 3600 rpm 3000 rpm
Section VIII.
Nuclear-fuel steam supply 1800 rpm or 1500 rpm or
It is common to describe a generator power factor as
3600 rpm 3000 rpm
“overexcited” or “underexcited,” as it is descriptive of the
Cross-compound steam-turbine generators
generator condition, as the equivalent of the corresponding
High-pressure turbine drive 3600 rpm 3000 rpm
terms “lagging” or “leading,” referring, respectively, to the
Low-pressure turbine drive 1800 rpm 1500 rpm
generator supplying an inductive or capacitive load.
Rated power factor is at the highest level of excitation
for which the generator is designed to operate at rated
output. It is commonly the maximum hydrogen pressure
apparent power and rated voltage. The rated power factor
for which the generator is designed to operate. The range
is commonly in the range of 80–90%, overexcited.
of rated hydrogen pressures for generators now being built
and those built over the past 15 years or more, is as follows:
C. Power conventionally cooled generators, 30 psig (207 kPa); and
The product of rated apparent power and rated power fac- conductor-cooled generators, 45–75 psig (310–517 kPa).
tor can be thought of as the rated power of the generator. (The unit psig is pounds per square inch “gage,” relative
However, of major interest is the rated power of the turbine to standard atmosphere.)
generator set, which is determined for the prime mover by
the requirements of the user. G. Short-Circuit Ratio
The rated power of the generator may be selected to be
somewhat higher than that of the turbine to take advan- The inherent stability of a generator in a power system is
tage of additional output that may be available. In a steam in part determined by its short-circuit ratio. It is a measure
turbine, this may come, for example, from the beneficial of the relative influence of the field winding versus the
effect of unusually low cooling-water temperature on the armature winding on the level of useful magnetic flux in
condenser vacuum. the generator. The higher the short-circuit ratio, the less
influence changes in armature current have on the flux
D. Voltage level and the more stable the machine tends to be, but it
will also be larger for the same apparent-power rating, and
The rated voltage (rms) of a three-phase turbine generator less efficient. Short-circuit ratio is defined as the ratio of
is defined as the line-to-line voltage at which the genera- the field current for rated open-circuit armature voltage to
tor is designed to operate continuously. The rated voltage the field current for rated armature current on sustained
of small- and medium-sized generators is normally se- three-phase short circuit, the machine operating at rated
lected to be one of a list of standard voltages, while that speed. The short-circuit ratio for turbine generators built in
of large generators is commonly selected at a level ap- recent years has been in the approximate range of 0.4–0.6.
propriate to economic and efficient generator design. The
range of rated voltages is approximately as follows: small
generators, 4000–14,000 V; medium generators, 12,000– V. CAPABILITY
20,000 V; and large generators, 14,000–28,000 V.
A. Armature Current
E. Speed For an air-cooled generator, the capability of the armature
winding is normally the rated armature current. In gas-
The rated speed of a generator is selected to match as
turbine-driven generators, however, the capability of the
closely as possible the best rated speed of the drive turbine,
armature winding is recognized to increase with lower
as shown in Table I.
inlet air temperature, and vice versa, while maintaining a
hot-spot winding temperature within the capability of the
F. Hydrogen Pressure
winding insulation. This matches well the variations of
The rated hydrogen pressure is the pressure of the hydro- maximum prime mover output power with changes in the
gen in the generator, required when it is providing rated temperature of the ambient air.
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 201

The capability of a conventionally cooled winding is 1. Load Excitation Curves


mildly sensitive to hydrogen pressure, and reduced capa-
Figure 6 shows the load excitation curves for a typical con-
bilities are commonly stated for pressures below rated, at
ventionally cooled two-pole hydrogen-cooled turbine gen-
15 psig (103 kPa) and at slightly above atmospheric, for
erator, rated 150 MVA, 3600 rpm, 15,500 V, 0.85 power
example, at 5 psig (34 kPa).
factor, 0.58 short-circuit ratio, at 30 psig hydrogen pres-
A hydrogen-cooled conductor-cooled armature wind-
sure. It is the apparent power as a function of field current,
ing is quite sensitive to hydrogen pressure. Capabilities
plotted for various constant power factors, holding speed
are commonly stated for two or three increments of 15 psi
and armature voltage at the rated values.
(103 kPa) each, below rated hydrogen pressure.
In this figure, horizontal lines represent constant arma-
The capability of a water-cooled armature winding is
ture current. The rating of the generator is the intersection
not normally sensitive to hydrogen pressure, but hydrogen
of the line for rated apparent power (1.0 per unit) and the
pressure does affect the cooling and, therefore, the temper-
curve for rated power factor (0.85, lagging). All constant-
ature of many parts of a generator in which losses are pro-
power-factor curves converge at a common point at zero
duced (magnetically) by armature current. Accordingly,
apparent power. This is at the field current for rated volt-
it is common to recognize a reduction in capability with
age, open circuit.
hydrogen pressure. Again, capabilities are stated for two
Vertical and horizontal lines are shown for the field and
or three 15 psi increments below rated hydrogen pressure.
armature-winding capabilities at three hydrogen pressures
The above capabilities are constant for all power factors.
(30, 15, and 5 psig). Also shown is the reduction in capa-
bility caused by stator core end heating at low levels of
B. Field Current excitation, below 0.95 power factor leading.
For air-cooled generators, the capability of the field wind-
ing is normally the field current at rated apparent-power 2. Reactive Capability Curves
load, power factor, and armature voltage. All of the con- Figure 7 shows the reactive capability curves for three
siderations described for the armature-winding capability hydrogen pressures for the generator depicted in Fig. 6.
apply to the field winding as well. As the field current is This is a plot of apparent power capability at rated voltage
varied, holding armature current and voltage constant, the using active power and reactive power as the abscissa and
power factor varies. ordinate, respectively. Here, curves of constant apparent
power, and, therefore, also constant armature current, are
C. Stator Core Ends circles with their centers at the origin. Curves of constant
power factor are radial lines. The generator rating is the
Heating of the ends of the stator core is strongly affected intersection of the circle (30 psig) for rated apparent power
by stray magnetic flux in the end region. This flux field and the line (0.85) for rated power factor. For each curve,
is complex in nature and is affected by the magnitudes the part (AB) limited by field-winding capability, the part
and angular positions of the current in the armature and (BC) limited by armature-winding capability, and the part
field windings. At constant armature current and voltage, (CD) limited by core end heating are shown.
as field current is reduced and the power factor changes
from lagging to unity to leading, the core ends become
E. Volts per Hertz
hotter.
It is common to reduce the permissable armature current As with most magnetic devices, a generator is limited as
for power factors below approximately 95% underexcited. to the level of useful flux that it can tolerate. The terminal
The lower the underexcited power factor, the lower the voltage divided by the frequency is proportional to the
armature current that is permitted. level of flux. At excessive volts per hertz, then, saturation
develops to the point where flux will stray into regions
where damage may ensue. The same applies to the unit
D. Capability Curves
step-up transformer.
As power factor is varied from zero, overexcited, through To protect both the generator and the transformer, volts-
unity to zero, underexcited, first the field current, then per-hertz protection is normally provided.
the armature current, and then the stator core ends are
limiting. Accordingly, curves that define a turbine gener-
F. Negative-Sequence Current
ator’s capability have three segments that pictorially de-
scribe the effect of the capability of the three machine Symmetrical components can be used as the equivalent
components. of any combination of the values and phase angles of the
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

202 Turbine Generators

FIGURE 6 Load-excitation curve for a 150-MVA conventionally cooled hydrogen-cooled turbine generator. (Courtesy
of the General Electric Co.)

three armature phase currents. When there is an imbalance, approximately sinusoidally around the perimeter of the ro-
a lack of symmetry, in the three currents, the negative- tor, and, hence, reverse axial direction every 180 electrical
sequence component is present. Here, the phase sequence degrees. At the ends of the rotor body, these currents turn
of the currents is opposite to the normal sequence, and to the peripheral direction to reach the location of reverse
these negative-sequence currents produce a sinusoidal flux axial direction. This pattern of current rotates backward
pattern in the air gap, which rotates in the direction oppo- around the rotor, essentially at constant amplitude (if the
site to that of the rotor. The relative motion of this “back- negative-sequence armature current is constant), sweep-
ward” rotating flux and the “forward” rotating rotor causes ing all portions of the rotor body. Skin effect will cause
currents to appear on the rotor surface, which oppose the these currents to be concentrated near the surface of the
magnetomotive force of the negative-sequence component rotor.
of armature current. These rotor currents are at a frequency These currents will produce general heating over the
twice that of the power system and their magnitude is es- rotor body surface and local heating at points of contact,
sentially proportional to the negative-sequence component or high concentration. Years of experience, as well as
of armature current. These currents are directed axially on tests in which rotor body surface and contact tempera-
the central section of the rotor body, and are distributed tures were measured, are the basis for determining the
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 203

FIGURE 7 Reactive capability curve for a 150-MVA conventionally cooled hydrogen-cooled turbine generator.
(Courtesy of the General Electric Co.)

negative-sequence capability of a generator, both for the entire turbine generator shaft system. If the frequency
steady-state conditions and for brief transients. of one component of alternating torque is identical to the
torsional natural frequency of any mode of vibration of the
complex shaft system, destructive vibration could result,
G. Off-Frequency Currents
depending on the mode shape and the level of the current
There are sources in the generator and the power system and the damping present.
of currents at frequencies other than that of the power sys- At the present state of art, it is not possible to calculate
tem. Current components at higher frequencies would be the higher natural frequencies accurately. Hence, design-
produced by transformer saturation and by incompletely ing to avoid higher stimulating frequencies may not be
filtered harmonic currents from rectifiers or inverters, for feasible. However, since the resonances tend to be sharp
example. Current components at frequencies lower than (due to low damping), the likelihood of matching stimulus
that of the power system have been produced by reso- and response frequencies is low, but the consequences of
nance between power-factor compensating series capac- a match may be severe.
itors (used to increase the power handling capability of The frequency of the torque due to subsynchronous res-
long ac transmission lines) and the inductance of genera- onance is variable, depending on the level of series capacit-
tors and transformers. This is commonly known as “sub- ance compensation being used at the time. It is necessary to
synchronous resonance.” avoid those frequencies that would stimulate a rotor torsio-
Off-frequency currents interact with the useful flux in nal natural frequency, or to block the current when at a po-
the generator to produce alternating torques that are felt by tentially damaging frequency from reaching the generator.
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

204 Turbine Generators

H. Unexcited Operation rent, with the generator operating at rated speed. At low
levels of flux, and hence low voltage, the only significant
Operation with no applied field current is potentially dan-
reluctance in the magnetic circuit is the air gap. In this
gerous, and can occur under a number of circumstances,
condition, flux is proportional to the excitation current,
two of which will be discussed.
and as a result the lower portion of the open-circuit satu-
Without excitation, the machine acts as an induction
ration curve is linear, and is commonly called the “air-gap
generator, if delivering electric power. The rotor oper-
line.” At higher voltages, as the flux level increases, vari-
ates at a speed slightly higher than synchronous speed
ous components of the iron portion of the magnetic circuit
and slip-frequency currents are developed that penetrate
saturate to increasing degrees, and additional excitation is
deeply into the rotor body. Severe rotor heating may re-
required to drive the flux through the iron. Thus the upper
sult. (See the discussion in Section V.F about the phe-
portion of the curve deviates from the air-gap line.
nomenon of rotor body currents.) The ends of the stator
core also experience heating due to stray fluxes in the end
region, more severely than for operation at underexcited 2. Short-Circuit Saturation Curve
power factor. (See the discussion in Section V.C.) Protec-
It is common to present the short-circuit saturation curve
tion is commonly provided to prevent or minimize the
on the same sheet as the open-circuit saturation curve
duration of this mode of operation. For completeness,
(Fig. 8). This is a plot of the armature current as a function
however, it should be noted that limited unexcited op-
of field current with the armature winding continuously
eration is permitted in some countries, but even there, it is
short circuited, the generator operating at rated speed (al-
controversial.
though small changes in speed do not affect this curve).
If a generator is at rest and a three-phase circuit breaker
This characteristic tends to be linear because the flux levels
is accidentally closed, connecting it to the power system, it
throughout the generator are below the level at which iron
will start up as an induction motor, causing very high cur-
saturates. This is also called the “synchronous impedance
rents, initially at the power-system frequency, throughout
curve” because the synchronous impedance of the gener-
the surface of the rotor body. The initial armature current
ator determines the level of the armature current, and the
will also be very high, but the most vulnerable part of the
curve can be used to obtain a test value for it.
generator is the rotor. As the rotor speed rises, stresses
increase at the same time that the temperatures of the
stressed regions also increase due to circulating rotor body 3. Load Excitation Curves
currents. Generators have been destroyed in this process,
Figure 6 shows the load excitation curves that plot appar-
as the strength of the component materials is reduced by
ent power as a function of field current at constant power
extreme temperatures to values inadequate to support the
factor. These curves are discussed in Section V.
applied loads, causing the rotor to lose wedges and field
“Vee” curves are commonly used to describe syn-
coils, filling the air gap with debris, and jamming the ro-
chronous machine characteristics and are plotted on the
tor to an abrupt stop. Thus, protection is needed for the
same sheet. These are curves of constant power output,
generator even when it is out of service, to prevent or at
shown on Fig. 6 for three values of power (127, 103, and
least limit motoring from rest.
73 MW).

VI. CHARACTERISTICS B. Electrical Characteristics


A turbine generator is an important part of the power sys-
A. Performance Characteristic Curves
tem it supplies, not only because of its function of pro-
A group of curves is widely used to describe many of viding electric power, but also because of its electrical
the important characteristics of any synchronous machine. characteristics. A power system is a dynamic organism
These are useful in applying a turbine generator to a power and its successful or unsuccessful performance is the con-
system and in operating the machine. Three of these curves sequence of the interaction of all of its parts.
will be discussed.
1. Moment of Inertia
1. Open-Circuit Saturation Curve
The moment of inertia of the turbine-generator rotor sys-
Figure 8 shows an open-circuit saturation curve for the tem appears as a mass in the power system network,
turbine generator of Fig. 6. It is the characteristic of the and though it is a mechanical characteristic, it is treated
open-circuit armature voltage as a function of field cur- here for convenience. The masses of all the synchronous
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 205

FIGURE 8 Open-circuit and short-circuit saturation curves for a 150-MVA turbine generator. (Courtesy of the General
Electric Co.)

machines in the power system are connected to one an- “rotor iron circuit”), all magnetically coupled. Its electri-
other through their torque-angle characteristics, as though cal characteristics when it is operating in a steady-state
there were springs making the connections. Generators fashion are very different from those when conditions
with their prime movers and control systems are not just are changing. It has different characteristics under slow
passive elements in the interconnected system, but may changes than it does under rapid changes.
either promote vibrations (torsional oscillations) or may For many conditions, a turbine generator can be rep-
help to dampen them. Sudden changes, such as dropping resented as a reactance in an electrical network. That re-
or adding a large block of load, or a fault somewhere, can actance takes on different values for different operating
initiate oscillations of machines relative to one another, or conditions.
relative to the system as a whole. In addition to the familiar concept of a reactance as
it functions in an electric circuit, there are magnetic
considerations that are useful in describing the operation
2. Electric Circuit Considerations
of a synchronous machine. An inductance (which is mul-
A turbine generator is a nonlinear combination of wind- tiplied by the angular frequency ω to obtain the reactance)
ings and the electrically conductive mass of the rotor body can be defined as the flux linkages produced by one am-
(which acts as a distributed winding which we will call the pere of current
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

206 Turbine Generators

L = λ/i (2) 5. Subtransient


This term is used to describe a rapidly changing condition
where L is inductance (henries), λ flux linkages (weber
that may last one to four cycles (0.015–0.07 sec). Here,
turns), and i current (amperes).
the mmf of the armature winding changes so rapidly that
Thus, the reactance is a measure of the ease with which
it causes currents to arise in the rotor body as well as in the
current produces flux in the machine.
field winding, all of these in a sense to oppose the change
Because of its complex nature, it has been necessary
in armature current. This restricts the armature-produced
to study each of the important operating situations that
flux to the armature leakage paths and to the very surface
require quantitative analysis. Some of the most commonly
of the rotor. Therefore, the generator appears as a smaller
used approaches will be discussed.
reactance, in the range of 0.10–0.25 per unit. This is called
the “subtransient reactance” X d .
The subtransient reactance is commonly used to calcu-
3. Steady State
late the maximum current following a nearby sudden short
When the generator is operating in a steady load-carrying circuit.
condition, it appears to the power system as a voltage sou-
rce separated from the generator terminals by the genera-
tor’s synchronous impedance. The generator resistance is 6. Sudden Short Circuit
negligible, and it is common to consider only the genera- If a short circuit should occur suddenly in the power
tor’s reactances, in this case the “synchronous reactance” system near a turbine generator, a high-current transient
X d . would ensue which is of interest for several reasons. In the
In a steady condition, a component of flux is produced design of the turbine generator set, itself, winding forces
by the armature current, and passes through the same mag- and torques experienced by the stator and torques on the
netic circuit as that for the useful field-winding-produced rotor system must be adequately accommodated. Also,
component of flux. This is an effective flux path, and a external buses and circuit breakers which must carry and
relatively high value of reactance may be expected, in the interrupt the current must be adequately specified. A dis-
range of 1.5–2.1 per unit. The per unit synchronous re- cussion of such a sudden short circuit is also useful in
actance is approximately equal to the reciprocal of the helping to understand how a turbine generator behaves
short-circuit ratio. electrically.
We will consider a sudden short circuit at the armature
terminals. The exciter is assumed to be a source of constant
4. Transient voltage in this discussion, that is, it is not controlled by
In synchronous machine analysis, the term “transient” a voltage regulator. Also, the generator is assumed to be
may take on a special significance (in distinction from the linear.
topic to be treated next), namely, to describe a slowly vary- Each winding in the generator traps the flux linking it
ing condition, lasting perhaps a half of a second or more. at the instant of short circuit. This is in accordance with
Under these conditions, the changing flux produced by the following equation relating flux linkages, current, and
the changing armature current in the direct axis induces a voltage in a short-circuited winding, which shows that
voltage in the field winding, resulting in a field current that the flux linking such a winding cannot change instanta-
opposes the change in flux and hence the change in arma- neously, since dλ/dt cannot be infinite:
ture current. This makes it more difficult for the armature- dλ/dt + iR = E T = 0 (3)
produced magnetic flux to pass through the generator than
in the steady condition. Under the transient condition, only where λ is flux linkages in a winding, t time, i current, R
the leakage flux paths of the armature and field windings winding resistance, and E T terminal voltage.
are available, meaning fewer flux linkages per armature A large direct current suddenly appears in each phase
ampere. The result is that the generator “looks” like a re- of the armature winding in proportion to the flux linking it
actance in the range of 0.15–0.35 per unit, much smaller at the instant of short circuit, in order to sustain that flux.
than the synchronous reactance. This is called the “tran- Since there is no source of direct current in the armature
sient reactance” X d . winding, it decays exponentially to zero in accordance
The transient reactance is important in studying tran- to the armature time constant τa (in the range of 0.14–
sient stability, which is the ability of the power system 0.5 sec).
to recover from a short circuit that has been interrupted, Large direct currents also arise in the field winding and
perhaps by circuit-breaker action. in the rotor iron circuit to sustain the flux trapped in them
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 207

at the time of the short circuit. The field current decays


exponentially according to the transient time constant τd
(in the range of 0.4–1.6 sec), to the steady value supplied
by the exciter. The rotor iron current decays in accordance
with the subtransient time constant, τd (of the order of
0.01–0.02 sec), to zero, since there is no source for direct
current in the rotor iron circuit.
Thus we have a decaying trapped flux in the stator and
a decaying trapped flux rotating with the rotor. Because
of relative motion, the stator flux produces a decaying
alternating current of power-system frequency, in all ele-
ments of the rotor, and the rotor flux produces a decaying
alternating current of the same frequency in the armature
winding. The initial value of the accomponent of armature
current may be calculated by the following equation:
FIGURE 9 Instantaneous armature currents following a terminal
I0 = E 0 / X d (4) sudden short circuit. (Courtesy of the General Electric Co.)

where E 0 is armature voltage (line-to-neutral) prior to the


sudden short circuit (rms). in the generator. If the generator is in a power station with
The above equation may be evaluated with all quantities many other comparable generators, or is tied to the system
in physical units (volts, amperes, and ohms), or with all by a strong transmission-line tie, infinite-bus voltage may
quantities in the commonly used per unit system (pu). be considered to be on the output side of the unit step-up
In the latter, each physical quantity is divided by a base transformer.
quantity to obtain the per unit value. The base value√for The maximum power which can be transmitted, then
voltage is the rated line-to-line voltage divided by 3, corresponds to a load angle of 90◦ . As is mentioned in
that for current is the rated armature current, and that for Section VIII, a modern control system can extend this
reactance is the quotient of the other two base quantities. limit.
At the instant of short circuit, the value of the dc com-
ponent of current in each phase is equal and opposite to
the instantaneous value of the ac component, so that there VII. REQUIREMENTS
is no sudden change in current.
Figure 9 shows the currents of each of the three phases Numerous industry standards have been developed, both
of a large turbine generator following a test in which a nationally and internationally, that specify the required
simultaneous three-phase sudden short circuit was applied performance of a turbine generator. These standards de-
to the terminals of the armature winding. It is a plot of a fine limiting temperatures at rating, required character-
digital record of the test. istics, and steady and transient conditions that must be
successfully tolerated.
In addition to industry standards, users commonly have
7. Power-Angle Characteristics
special requirements to meet special needs. For example,
The power that is transmitted in an ac system between any it is common to require that the built-in instrumentation
two points, be it along a transmission line or through the that is provided be compatible with the facilities of the
reactance that defines a cylindrical-rotor generator electri- power station for acquiring data.
cally, is proportional to the sine of the phase angle between
the sending-end voltage and the receiving-end voltage.
A. To Be Provided by the Generator
This is called the load angle δ. In a synchronous machine,
sending-end voltage is the voltage that is generated in the The primary requirement of a turbine generator is to
armature winding by that component of air-gap flux that provide electric power continuously or for relatively
is produced by the field current. This voltage appears in short peak-load periods as needed, and to do so reliably
the quadrature axis, and in the steady state it is sometimes and economically. A generator is also normally required
called the “voltage behind synchronous reactance.” The to provide voltage support to the system by supplying
receiving-end voltage is at that location in the power sys- the needed reactive power. See the discussion in Sec-
tem that can be said to be an “infinite bus,” where the tion VIII.B. The rated power factor assures that the gener-
voltage is unperturbed by changes in operating conditions ator will have adequate ability to carry out this function.
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

208 Turbine Generators

The rating normally defines the continuous duty re- A disturbance may occur on one phase of the power sys-
quired of the generator. A temperature class is assigned tem which is then isolated by circuit breakers. The event
to the generator, which defines the thermal capability of may subject turbine generators in the vicinity to a large
the electrical insulation systems of the armature and field negative-sequence current for a brief period. Again, recog-
windings. Turbine generators are generally class B or class nizing the economics of providing tolerance for the rotor
F, which implies a hot-spot capability of 130 or 155◦ C, re- heating that would result from such an event, the indus-
spectively, as prescribed in industry standards which also try standards require that a turbine generator be capable
specify limiting observable temperature rises over cold of withstanding a prescribed value of I22 t, where I22 is the
coolant temperatures for each class. square of the per unit value of the negative-sequence com-
ponent of current, integrated over the period of exposure
t in seconds.
B. Required Characteristics
The wave shape of the armature voltage must be very 3. Overcurrent
nearly sinusoidal so as to avoid such environmental con-
cerns as telephone interference. To this end, it is common Brief periods of overcurrent may exist in the armature
to specify a limiting “telephone influence factor” (TIF) and field windings. For example, if the system voltage
that is calculated from the harmonic content of the volt- drops for a brief period, the excitation system may be
age, using a weighting-factor curve that reflects the fre- called upon to apply ceiling voltage to the field winding.
quency response characteristics of the telephone systems. The field current will rise according to its time constant
A limiting “deviation factor” may also be specified. This from the value corresponding, perhaps, to rated load. The
is a measure of the maximum deviation that the armature higher than normal current in both windings would result
voltage has relative to a sine wave. in a brief excursion to higher than normal temperatures.
A voltage response ratio is specified for the excitation Accordingly, industry standards require that a generator
system, to be compatible with the stability needs of the be capable of operating at specified levels of overcurrent
power system. in the armature and field windings for a prescribed period
of time.
C. Required Capabilities
4. High-Current Transients
A turbine generator must be able to operate successfully in
a real power system where the ideal is not always achiev- High-current transients may occur in a power system due,
able. The following are the principal conditions that may for example, to a sudden short circuit or due to switch-
be experienced by a turbine generator, with comments re- ing where the voltages of the circuits to be connected are
garding required capability. unequal in magnitude or phase angle. The high currents
produce high electromagnetic forces in the armature wind-
ing in the end regions and in the slots. They also result in
1. Voltage and Frequency Variation transient torques felt by the rotor and the stator. To assure
A generator must be able to deliver rated apparent power that the turbine generator has the necessary ruggedness,
at terminal voltages deviating from the rated value by up United States industry standards require that it be capa-
to ±5%, according to current United States standards. ble of withstanding, without mechanical injury, a three-
These standards also specify that the frequency range over phase terminal sudden short circuit while at load at 105%
which rated output can be delivered will be provided by voltage.
the manufacturer.
5. Overspeed
2. Negative-Sequence Current A turbine generator is required to be able to withstand a
The three phases of a power system are not perfectly bal- brief overspeed test to 120% of rated speed to assure that
anced in voltage and impedance. Accordingly, a small the rotor system is mechanically sound.
amount of steady negative-sequence current is unavoid-
able. The standards specify a maximum steady negative- D. Reliability and Availability
sequence current that must be tolerated. This value, which
1. Reliability
varies among the various types and sizes of turbine gener-
ators, is based on an economic evaluation of system needs Reliability is a measure of a generator’s freedom
and generator rotor heating characteristics. from forced outages (nondiscretionary periods when the
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 209

generator cannot carry rated load). When an electric util- natively, judgment and experience may indicate that repair
ity has constructed a power plant and the power lines to work may be done at any chosen time within the next two
transmit the power to its network and ultimately to its years. Then it can be planned for a time compatible with
customers, and when that power plant is among the most the system operation.
cost-efficient in the system, it is of the utmost importance Ordinarily, planned outages are scheduled during pe-
for the turbine generators in that plant to produce electric riods of predicted low demand for electric power. This
power when and as required. The cost of having a turbine has become more difficult in recent years because of two
generator shut down for any reason when it is needed is seasons of peak load, one in winter with cold weather and
very high indeed, ranging to $300,000/day and even much short days, and a second, perhaps higher system demand in
higher, depending on the size of the generator and the cost the summer due to an air-conditioning load. The planned
of alternative power. outages are scheduled for a number of machines having
System designs and system operating procedures can a total power rating that can be tolerated to be out of ser-
and must minimize the severity of a forced outage. How- vice at the same time, with a margin of available turbine
ever, such designs and procedures can be costly and if generators to accommodate a forced outage of a selected
the generators have poor reliability records, that cost number of the system’s largest units.
would be increased. For example, reserve margins, hav- The importance of availability places a strong incentive
ing more generating capacity than is needed to meet for designing for ease of inspection and for quick and easy
peak loads, would need to be increased to back up poor maintenance. However, a design to achieve high reliabil-
performers. ity may of necessity produce a generator that is difficult
Medium and large turbine generators are among the to repair (e.g., remove an armature bar). But if that de-
electric machines with the highest reliability. The present sign has resulted in high reliability, the repair may never
designs of turbine generators are the result of evolution be required. Here again, a successful design is a careful
over the past 80 years, during which advancement in all compromise of all the critical issues.
of the critical parameters leading to today’s designs has
taken place relatively slowly and based on extensive expe-
rience. Growing pains have been felt at times during this VIII. EXCITATION SYSTEM
period, but they have led to the high reliability of succes-
sive generations of designs, as important new things have The exciter together with its control system is called the
been learned and new features introduced as a result. “excitation system.” It is an important part of the generator
A recent industry-wide survey of turbine generators in system. A synchronous generator must have an exciter in
service in the United States has indicated that they have order to function.
reliability in the range of 98.5–99.6%, considering eight
size ranges as groups, for the years 1973–1982.
A. Exciter
The exciter supplies direct current to the field winding of
2. Availability
the generator, at whatever voltage is required to overcome
High generator availability is important to the economic the resistance of the winding. The rating of the exciter
health of the power system of which it is a part. is specified as its output power, current, and voltage cor-
Forced outages are covered in Section VII.D.1. The responding to the rating (or maximum capability, if dif-
other cause of unavailability is planned outages. These ferent) of the generator, recognizing the temperature of
are provided to improve reliability and prolong the use- the generator’s field winding. The exciter rating may have
ful life of the generator. Planned outages are arranged some margin over this requirement, as defined when the
so that the generator can be inspected to ascertain generator is designed.
whether deterioration is either taking place or is immi- Over the years, many types of exciters have been used,
nent. Such inspections every 3–5 years are commonly but the type most commonly used was the comutator-type
recommended by the various manufacturers. Great care dc generator. This is very rarely used for new genera-
and experience are required to carry out these inspections tors today. A new turbine generator is usually supplied
effectively. with one of the following types of exciter: (1) shaft-driven
When the maintenance inspection requires removal of alternator with solid-state diode rectifiers, (2) solid-state
the rotor, a period of many days is required. If repair work thyristor rectifiers supplied by a transformer deriving its
is recommended, it may need to be carried out as an ex- power from the power system or from within the generator
tension of the inspection outage, and being unplanned, the (the latter is a form of self-excitation), or (3) shaft-driven
extension may be considered to be a forced outage. Alter- alternator with its output winding on the rotor, its output
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

210 Turbine Generators

rectified by rotating solid-state rectifiers, commonly called “Volts-per-hertz” protection is commonly provided to
a “brushless exciter.” prevent the level of the magnetic flux in the generator
In addition to its normal function of providing the proper and in the unit step-up transformer from exceeding safe
level of direct current to the generator’s field winding as re- levels. A volts-per-hertz control is occasionally specified
quired for the apparent power being supplied, the terminal to adjust generator excitation so as to avoid overfluxing.
voltage, and power factor of the generator load, the exciter The steady-state power output of a cylindrical-rotor
must also be able to produce a ceiling voltage (which is generator, such as a turbine generator, is theoretically lim-
higher than rated exciter voltage) and to operate at that ited to the power at which the load angle reaches 90◦ . It
condition for a specified brief period, as required by the is beneficial to the steady-state stability characteristics of
voltage response ration which is part of the excitation sys- a generator that a continuous-acting voltage regulator can
tem specification. The voltage response ratio is a measure enable a generator to operate stably beyond 90◦ . While a
of the change of exciter voltage in 0.5 sec when a change generator may not actually be operated in this region, this
in this voltage is suddenly demanded. characteristic does permit a generator to be operated in
When the exciter is a rotating machine driven by the the low-excitation range needed to charge the capacitance
generator shaft, it becomes part of the turbine generator of long ac transmission lines at night, for example, while
shaft system and must be designed to accommodate axial maintaining reasonable margins from the stability limits.
motions due to thermal expansion of the turbine and gener-
ator rotors, and vertical motions of the generator shaft due
2. Transient Control
to bearing oil film and thermal expansion of the generator
bearing support. The ability of the excitation system to change the gen-
erator field voltage rapidly may be important to system
stability. When supplying a system that has relative high
B. Control System
reactance, as for example when a long transmission line
The excitation system of each turbine generator unit is one separates a generator from its load, stability may be diffi-
of the few places where a control function can be intro- cult to achieve. Providing an excitation system with a high
duced in a power system. Both steady and transient control voltage response ratio may help in system design in such
functions are important, and these will be considered in a situation. It can help reduce major expense in additional
turn. transmission-line construction.
A relatively new concept made possible in part by the
use of thyristor power rectifiers is the high-initial-response
1. Steady Control
excitation system. In such a system, the output voltage of
With the turbine governor fixed, and the power output of the exciter changes almost instantly on command, enhanc-
the generator thus fixed, and with the configuration of the ing system stability.
power system fixed, an increase in exciter output, that is Another relatively new concept in excitation control
in generator field current, causes the armature voltage to function is the power system stabilizer. It operates to en-
rise. This changes the power factor and causes the reactive hance stability in situations where one power system may
power delivered by the generator to increase. Thus, while swing at low frequency relative to another.
the turbine governor responds to provide the power needed
by the system, the exciter enables the generator to provide
the needed reactive power and thus to help provide the IX. ELECTROMAGNETIC DESIGN
needed voltage support in the system.
The control system includes a voltage regulator that Some of the major aspects of the electromagnetic design
causes the generator field current to be at whatever level are presented. These are highlights of the process and it
is required to maintain the armature terminal voltage at a must be recognized that many important considerations,
selected value. The control system also can be instructed naunces, and implications are beyond the scope of this
to hold the generator field current at a desired value, when article. Nonetheless, what is presented here may help to
voltage-regulator action is not needed. This is commonly gain an understanding of turbine generators.
called “manual control.”
A lower limit is provided so that the field current is not
A. Design Characteristics
reduced to the point where stator core end heating becomes
excessive, or stability margins are compromised. An upper Some of the basic interactions that shape the overall con-
limit is provided so that the capability of the exciter and siderations in the design of a turbine generator will be
that of the generator field winding is not exceeded. discussed very briefly.
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 211

1. Flux Versus Armature Reaction the technical and economic compromise that represents a
good design.
The rated apparent-power output of a generator is propor-
tional to the product of the flux and the armature reaction
in accordance with the following equation: 2. Conductor Cooling
U = KMa P f (5) Conductor cooling has greatly increased the capability for
where U is rated apparent power, K proportionality con- armature reaction, making it possible to reduce the flux
stant, Ma armature reaction, the mmf due to armature cur- and hence the physical size of the generator [see Eq. (5)].
rent, at rating,  magnetic flux per pole, at rated voltage, It has made it possible to build generators beyond the ap-
P number of poles, and f frequency of armature voltage. proximately 300-MVA limit for conventional generators,
This is analogous to the product of current and voltage. to 1600 MVA and possibly above.
The armature current is proportional to the armature re- All of the discussion of reducing flux level in the pre-
action. The armature voltage is proportional to the flux. It vious paragraphs applies to conductor-cooled generators.
will be useful later in this discussion to note also that the While conventionally cooled generators tend to be
field winding mmf at rating is directly related to the level temperature-limited, conductor-cooled machines have ef-
of armature reaction. ficiency as an important controlling parameter. To this end,
To achieve a specified apparent-power rating, the de- many compromises are possible only with conductor cool-
signer can provide for a relatively high value of flux and a ing, to benefit both cost and efficiency, by providing very
low level of armature reaction, or vice versa, or any combi- little space for the cooling medium so that more space is
nation in between. In the process, the designer determines available for the active materials, iron and copper.
many of the electrical and mechanical characteristics of Current densities in a conductor-cooled winding tend
the generator. to be higher than in a conventionally cooled winding, tak-
Providing a high level of flux requires a relatively large ing advantage of the improved cooling. As a result, tran-
volume of iron to carry the flux and relatively little copper sients involving higher than rated currents tend to heat the
to carry the armature and field currents. Such a machine winding more quickly. This is partially handled by de-
tends to be large, more costly to build, and more difficult signing with temperature margins to permit the transient
to ship. The fixed core, fan, and windage losses tend to be overcurrents specified in industry standards. The standards
high, and the variable winding I 2 R losses tend to be low, themselves prescribe shorter high-current transients for
with the efficiency at rating generally relatively high. conductor-cooled machines, while satisfying the require-
Providing a low level of flux requires a relatively small ments of power systems.
volume of iron to carry the flux, but a relatively large Because at the higher armature reaction achieved in a
volume of copper and added emphasis on winding heat conductor-cooled generator a longer air gap (in the range
removal, to carry the armature and field currents. Such a of 3–4 in., 7–10 cm or more) is required than in a conven-
machine tends to be small, less costly to build, and easier tionally cooled machine to produce the same short-circuit
to ship, but vibratory winding forces tend to be higher, and ratio.
a more highly rated, more costly exciter is required. The
fixed core, fan, and windage losses tend to be low, and the
B. Air Gap
variable winding I 2 R losses tend to be high. Maintaining
high efficiency may be more challenging. The length of the air gap is selected to provide the speci-
The per unit transient and subtransient reactances, fied short-circuit ratio. The longer the air gap, the higher
which play a significant role in the electrical performance the short-circuit ratio. Also, the greater the mmf required
of the generator in the power system, tend to be low with to cause the required level of magnetic flux to cross the
high flux levels. The higher flux generator will, therefore, air gap. Thus, more field current is required. A larger gen-
tend to have a somewhat better inherent transient stability. erator is required for a given apparent power rating for a
It will also tend to have higher per unit transient currents higher short-circuit ratio because a larger rotor is required
during severe disturbances, and therefore higher winding to handle the extra field mmf, and because of the extra
forces and torques, than a lower flux machine. space occupied by the air gap.
Mechanically, the larger high-flux generator will have One mechanical consideration: the air gap needs to be
a larger, likely longer rotor perhaps requiring more care in large enough to permit assembly of the rotor through the
balancing. The moment of inertia of the larger rotor will stator bore with sufficient clearance for safe handling,
help limit over-speed on loss of load. recognizing the diameter of the retaining rings. This may
As can be seen by the above, the design engineering set the minimum feasible short-circuit ratio in some con-
job is a project of fine tuning many factors in achieving ventionally cooled generators.
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

212 Turbine Generators

C. Rotor rent United States standards require that the field winding
pass a high-potential test when new of 10 times rated field
1. Rotor Body
voltage, up to 5000 V for a 500-V field, and for higher
The magnetic flux carried by the rotor is normally steady, voltages, the test voltage is incremented 2 V for each volt
not alternating. Hence, only the static magnetic saturation of rated-voltage increment.
characteristics of the material need to be considered in the The turn-to-turn voltage is normally only a few volts.
magnetic design of the rotor body. Even with brief exposures to higher voltages, it is gener-
There are two critical areas in the design to carry flux ally sufficient to provide mechanical separation between
(see Fig. 2): (1) the region under the field-winding slots turns.
and (2) the base of the poles. Increasing the cross-section Rotation imposes a centrifugal acceleration on the in-
area in either of these decreases the space available for sulation in the range of 2000–5000 of more times that of
the field winding. Both of these regions carry not only the gravity. Temperature changes in the winding which oc-
useful flux which crosses the air gap to the stator, but also cur when the generator is excited and picks up load, and
the extra burden of the cross-slot leakage flux of the field during each load cycle, cause the conductors to attempt
winding. to expand or contract. The degree to which the conduc-
tors are locked in place by centrifugal force affects the
actual motions that the insulation must be designed to
2. Field Winding
accommodate.
a. Design. The magnetomotive force, expressed in
ampere-turns, is a measure of the capability of the field
winding. The total cross-section area in each slot avail- D. Stator
able for copper is subdivided into turns, all of which are 1. Stator Core
connected in series to form a “coil.” The number of field
turns per pole multiplied by the current in the winding Figure 2 shows the cross section of the stator core. The
equals the total mmf. The current density in the copper annulus occupied by the teeth and armature winding is
determines the total loss to be dissipated and hence the very valuable space. In order to provide maximum room
temperature of the winding. For constant current density, for the winding, the tooth flux densities are set at a high
as the designer would change the number of turns, the level, determined generally by losses and heating.
copper area per turn and hence the current per turn would The radial depth of the yoke (outside the slots) in a
be changed inversely, but the total mmf per pole would two-pole generator is governed by two considerations, the
remain unchanged. Since field-winding voltage is propor- proper level of magnetic saturation and mechanical vi-
tional to the number of turns, its selection does not affect bration. In generators of small outer core diameter, the
the mmf available. yoke depth is ordinarily flux limited. In large-diameter
A major determiner of the mmf capability of the field two-pole generators, a minimum yoke depth may be set
winding is the temperature of the conductors. Increas- to limit “ovalizing” core vibration.
ing this capability may be done through (1) insulation Magnetic flux in the end region of the generator im-
capable of higher temperature, (2) more effective cool- pinges on the ends of the stator core, perpendicular to the
ing systems, and (3) methods of increasing total area punchings and to the mechanical structure that clamps the
in the rotor cross section, available for copper. In large core axially. It produces eddy currents in the punchings
machines, higher temperature may cause increased ther- and structures. The level of consequent losses is deter-
mal stresses in the field-winding conductors, which must mined in part by the level of armature reaction mmf.
be accomodated. Careful attention to many important With conductor cooling, the armature reaction is high
details is essential to the successful design of a field enough to require special design features to minimize the
winding. losses in the core ends and the resulting temperatures. In
essence, the designs provide a current-carrying shielding
b. Insulation. The electrical insulation of the field barrier or a flux-carrying shield for the structures. The
winding must isolate the conductors from the rotor body ends of the teeth are contoured and further subdivided to
which is at ground potential, must separate adjacent turns reduce eddy currents.
within a coil, and must be designed to do this while suc-
cessfully handling a severe mechanical duty, particularly
2. Armature Winding
in large generators.
Rated field voltage ranges from 125 V on small turbine a. Design. Once the total flux per pole is estimated
generators to 600 V or higher on large machines. Cur- [see the discussion of Eq. (5)], the armature voltage is
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 213

proportional to the number of turns in series in each cir- mechanical aspects of the design of a modern machine are
cuit of a phase. The number of turns in series is usually of importance, which is hard to overemphasize. A few of
determined by the following equation: the important considerations will be discussed briefly.
Na = Ns Nt /3Nc (6)
A. Rotor
where Na is the number of armature turns in series per
circuit, Ns the number of armature slots, Nt the number of Basic to the design of the rotor is a good definition of
turns per coil, and Nc the number of parallel circuits per the properties of the materials that are used for the rotor
phase. forging, retaining rings, coil-slot wedges, and other crit-
The capability of the armature winding is dependent ical components. The key properties include (1) ultimate
on the effectiveness of the removal of heat (I 2 R losses) strength, (2) yield strength, (3) the parameters of ductility
produced in the conductors. In a conventionally cooled and toughness, (4) high-cycle fatigue characteristics, and
winding, this is enhanced when the insulation can be made (5) low-cycle fatigue characteristics.
thin and the area for heat flow made large. These two
characteristics of the thermal circuit are achieved by using
1. Rotor Body
a relatively low rated voltage (if acceptable), and a large
number of slots, respectively. The design of the rotor body requires proper consideration
In a conductor-cooled winding, cooling effectiveness of (1) the stresses at speed, (2) stress cycling between
and efficiency are addressed in the arrangement of the standstill and speed, (3) overspeed, and (4) the appropriate
components within the ground insulation, and particularly material properties.
in the relative cross-section areas set aside for coolant and The teeth must hold the field winding, wedges, and
for conductors. the load of the teeth themselves against centrifugal
force.
b. Insulation. Three functions of electrical insulation The stresses at the surface of the axial bore hole (if
of the armature winding need to be addressed. These are used) are also critical and may determine the minimum
(1) ground insulation between the conductors and the sta- diameter to the bottom of the slots or subslots. A bore
tor core and other grounded objects, (2) turn insulation, hole is often used to machine out the central portion of
between the turns of a multiturn coil, and (3) strand insu- the forging where impurities and porosity tend to con-
lation, between the strands within a turn. centrate, particularly in the large forgings for four-pole
The ground insulation must be designed to withstand al- rotors.
ternating line-to-ground voltage over the generator’s life- The wedges that hold the field winding against rotati-
time, with the possibility of a few momentary overvoltages onal forces are complex in shape and experience a com-
from system-imposed surges. If a point on the bus between plex pattern of stresses. Appropriate design methods and
the generator and the step-up transformer, or within the ar- limits must be established and followed in the design
mature winding itself, is grounded, parts of the winding process.
would see a brief overvoltage of up to full line-to-line volt- The inboard end of a retaining ring (end bell) is com-
age, depending on the location of the fault. The turn insu- monly shrunk onto a shoulder on the rotor body. The stress
lation must withstand normal coil voltage over its lifetime, level at the inboard end varies only slightly due to the ra-
with substantial momentary overvoltage in the event of a dial expansion of the body as the rotor comes up to speed.
steep-front voltage surge. Strand insulation is exposed to The outboard end may be only lightly stressed at standstill,
only a few volts with brief overvoltages during occasional but is fully stressed at speed. Hence both at standstill and
high-current transients. at speed the retaining rings experience a complex pattern
A voltage grading system is applied to the ground insu- of hoop stress and bending. Each start-stop cycle causes
lation to control the voltage distribution over the surface many changes in complex high stresses. Design stresses
in the slots and in the end regions to prevent destructive must consider all of these effects. The retaining rings must
electrical discharges. be locked against axial movement that would be caused
by very high axial forces due to the expansion of the field
winding conductors.
X. MECHANICAL DESIGN Overspeed must also be considered. Test at 120% speed
as specified by industry standards is intended to assure that
While a turbine generator is thought of as an electric the speed to which the rotor would accelerate on loss of
machine, which it is, the mechanical engineering that load can be safely handled. That speed will generally not
brought it to the state of development that it enjoys and the exceed 120%. The shrink fit in all parts of the rotor needs
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

214 Turbine Generators

to be such that parts will not move, changing the balance quency and twice that frequency is part of such a design
condition of the rotor, when operated at the maximum strategy.
expected overspeed (including test).
B. Stator
2. Shaft System 1. Frame
The entire shaft system, including the turbine rotors and The stator frame is the outer shell of the generator. In many
the exciter rotor, if used, and the slender shafts connect- ways, it is the mechanical interface with the power station.
ing the larger diameter masses, acts as an interconnected It includes feet for mounting the generator to the founda-
system in lateral vibration. The vertical and horizontal tion. The feet must accommodate not only the weight of
stiffness of the bearing supports and of the oil films af- the generator but also the downward and upward loads of
fects the critical speeds and mode shapes. Experience and the overturning torque of a sudden short circuit, which, for
modern computer techniques are the foundation of shaft a four-pole generator, may actually appear as a momentary
system design, regarding critical speeds. net upward force on one side.
Each rotor, and the shafts between each pair of bear- The frame provides support for the stator core. In large,
ings in what can be 12-bearing set in a large steam tur- medium, and many small two-pole generators, its mechan-
bine generator, has an appreciable sag. The elevation of ical design, in conjunction with the spring supports of
each bearing is established by design, but finally de- the core, determines how well the core vibration is iso-
termined at the time of installation so that bolting the lated from the foundation. Here, the frame stiffness and
couplings together does not introduce bending into any natural frequencies of vibration play important parts, rec-
shaft. ognizing that the primary stimulating frequency is twice
The minimum shaft diameters are at the bearings and the power-system frequency. The frame must also be de-
are determined by acceptable torsional stresses under rated signed to avoid resonance at the mechanical frequency of
load, with margin for brief high torques during severe elec- rotor vibration (the power-system frequency for a two-pole
trical transients. The shaft diameter and bearing length machine, and one-half of that frequency for a four-pole
are also selected to place the pressure in the oil film in machine).
the range of stable bearing operation. The larger the shaft In a hydrogen-cooled generator, the frame is designed
diameter, the higher the bending stress due to rotor mis- and tested not only to contain rated hydrogen pressure,
alignment and the higher the bearing losses that must be but an overpressure which could result from a variety of
considered in the efficiency (or heat rate) of the turbine- causes. The steel plate and weld materials are selected
generator set. In very large turbine generators, the periph- based on strength and low-temperature ductility to con-
eral speed of the bearing journal may exceed that at which tain the internal pressure. Coolers are provided within the
turbulent flow develops in the bearing. This causes a large frame to transfer the heat absorbed by the hydrogen to the
increase in bearing loss. station water system.
Shaft torsional vibration is of concern in designing The outer surface of the frame is generally cylindri-
and operating a turbine generator. These are totally unde- cal, although that of certain air-cooled generators have
tected without special methods. Whenever a high-current a square cross section. To provide the needed stiffness,
electrical transient is experienced by the armature wind- annular “section plates” are welded at selected axial posi-
ing, a complex transient torque is felt by the rotor. A tions inside the outer “wrapper.” The radial depth and the
three-phase sudden short circuit, for example, exposes thickness of the section plates are chosen to achieve a suit-
the rotor to a large decaying alternating torque at the able stiffness and a natural frequency in the desired range.
power-system frequency, and a decaying unidirectional Passages are provided to connect the various elements of
torque whose initial value may be one-third of the ini- the ventilation circuit: (1) the fans (blowers), (2) the cool-
tial peak alternating torque. A single-phase sudden short ers, (3) the stator core, (4) the air gap, (5) the rotor, and
circuit would add a decaying alternating torque at a fre- (6) other components requiring forced gas cooling. The
quency twice that of the power system. Being suddenly size of these passages is selected so that an acceptably low
applied, these torques would stimulate a number of tor- pressure drop is required to move the gas on its appointed
sional natural frequencies. If the stress in any shaft ex- journey. The outer diameter of the frame is determined by
ceeds the torsional endurance limit of the shaft mate- adding the required diametrical depth of the frame to the
rial, it is likely that many cycles will exceed that limit outer diameter of the core.
since the overall torsional damping is very low. This The shipment of the stator of a large steam-turbine gen-
must be considered in shaft design. Avoidance of tor- erator is a project of significant proportions. The weight
sional natural frequencies near the power-system fre- may significantly exceed 800,000 lb (360,000 kg). A large
P1: GNH/GWT P2: GPB Final Pages
Encyclopedia of Physical Science and Technology EN017A-794 August 2, 2001 17:1

Turbine Generators 215

generator requires a specially constructed railroad car to slots simplifies the support of the highest forces experi-
handle the weight and size of the stator and to spread the enced in any part of the armature coils. The ground-wall
load out along the tracks. The cross-section dimensions of insulation is an important part of the support system.
the stator, mounted on the railroad car, must be designed The pattern of electromagnetic forces on the end regions
to provide clearance to railroad bridges, tunnels, station of an armature winding is complex in both distribution
platforms, and other obstructions along the railroad right and phase-angle timing. The geometry is not amenable to
of way. simple support, as perhaps can be seen in Fig. 3. Strong
The frame must be designed to be handled, lifted, and electric fields in the end region require that nonconducting
moved during manufacture and during installation at des- support structures be used. Vibratory forces in the end
tination. Trunnions are bolted onto heavy plates built into winding of a large turbine generator under normal load are
the frame so that cables can be attached for use of overhead such that no rubbing or impacting contacts can be tolerated
cranes. because of consequent wear, with increasing motion and
damage.
2. Stator Core Following a sudden short circuit or other high-current
transient, high forces are developed in the armature wind-
The support of the core must accommodate the torques that ing and are an important consideration in the design of the
are experienced. Steady load appears as a steady torque to winding supports.
the core. High-current transients impose the same torques There is a great variety in the design and construction
on the core as are described in Section X.A. Dovetail slots of the armature end winding support systems provided
punched in the outer surface of the core, matching dovetail by the various manufacturers. Most systems use blocks,
key bars, or an equivalent design, is provided to transmit tension devices, and rings, which together with the bars
these torques to the frame. Spring mounting, if used, must themselves, form quite a rigid structure. In order to
be designed to experience these torques with no adverse retain the integrity of this structure, some manufacturers
affects to itself or to other parts of the stator. permit the entire end-winding and support system to
Radial ventilation passages (“ducts”) are commonly move (only) axially so as not to impede axial thermal
provided in the core for the cooling gas. These ducts sub- expansion of the slot section of the winding.
divide the core into packages. The core loss generated in
each package is dissipated to the cooling medium at the
surface of the radial ducts. The width of the ducts and the SEE ALSO THE FOLLOWING ARTICLES
thickness of the core packages are chosen as required by
the ventilation needs of the machine and the temperature ELECTRIC MACHINES, ROTATING • GAS-TURBINE POWER
permitted in the core. PLANTS • JET AND GAS TURBINE ENGINES • POWER
TRANSMISSION, HIGH VOLTAGE • THERMODYNAMICS
3. Armature Winding
The slot section of an armature bar “feels” significant BIBLIOGRAPHY
steady vibratory forces at a frequency twice that of the
power system, due to cross-slot flux produced by the nor- Beck, D., and Wilson, D. (1996). “Gas-Turbine Regenerators,” Kluwer
mal load current. It has been found that an armature bar of Academic, Dordrecht.
a turbine generator will not survive if it is permitted any British Electricity International, ed. (1993). “Modern Power Sta-
motion as a result of these forces. A variety of support sys- tion Practice. Vol. C. Turbines, Generators and Associated Plants,”
tems is provided in the slots by the various manufacturers. Pergamon, Elmsford, New York.
Gonzalez, A. J., and Baldwin, M. S. (1995). “Monitoring and Diagnostics
The objectives are to provide no room for motion, and, in of Turbine Driven Generators,” Prentice Hall, New York.
certain ranges, to apply positive forces to restrain the bars. Grigsby, L., ed. (2001). “The Electrical Power Engineering Handbook,”
Thermal expansion and contraction of the bar cross section IEEE Press, New York.
on load variation must not lead to clearances that would Kerszenbaum, I. (1996). “Inspection of Large Synchronous Machines:
permit motion. The wedging and support system must not Checklists, Failure Identification, and Troubleshooting,” IEEE Press,
New York.
be compromised by a tendency of the slot opening to vary Sill, U., and Zorner, W. (1996). “Steam Turbine Generators: Process
in a vibratory fashion at a frequency twice that of the power Control and Diagnostics: Modern Instrumentation for the Greatest
system. Nonetheless, the geometry of straight rectangular Economy of Power Plants,” John Wiley & Sons, New York.

You might also like