You are on page 1of 9

A & M TECHNOLOGIES

Ref: A&M/SCL/342266/R0
16th July, 2014

M/s. SHESHASAI CHEMICALS LTD,


Visakhapatnam,
Andhra Pradesh

KIND ATTN: Mr. R.B.Sekhar

Dear Sir,

Sub: Requirement of LDO-HSD fired Thermic Fluid Heater

Thank you very much for your above said enquiry.

Based on the same, we are pleased to submit our offer for your kind perusal.

Our detailed offer for THERMOPAC Thermic Fluid Heater Model TPCM - 02 capable of
generating heat output of 2,00,000 KCal/hr, at a temperature of 280°C when fired
with HSD/LDO.

We trust the above is in line with your requirement and incase of any further
clarifications, please feel free to contact us

Thanking you and assuring you of our prompt attention at all times,

Yours faithfully,
For A & M TECHNOLOGIES

(M.RAMA KRISHNA)
9848186200

Encl.:As above

## 49-54-4, B.S.Layout, Seethammadhara, Visakhapatnam - 13.


Tel :(0891)2535041 Fax: 0891:2536234 E-Mail:am_ramakrishna@rediffmail.com
For more information about Thermax,Visit us at :www.thermaxindia.com
INDEX

SCOPE OF SUPPLY ........................................................................................................


BATTERY LIMITS ...........................................................................................................
PERFORMANCE CRITERIA .............................................................................................
EXCLUSIONS .................................................................................................................
SCOPE OF SUPPLY

HEATER
One Heat exchanger consisting of two closely wound helical concentric coils
arranged to give three passes on flue gas side made out of ERW tubes
confirming to BS: 3059 Part I suitable for high temperature

One Single jacketed to enclose the heat exchanger coil dully insulated with
mineral wool and coated with color coated sheets

AUXILIARIES

One Dust protected, prewired wall mounted air cooled control panel housing a
Burner Management System, Switch gear consisting of contactors,
Overload relays, fuses/ MCB etc…

One Centrifugal Thermic fluid circulating pump suitable for high temperaure
operation, directly to an electric motor, mounted on a common base frame

One Deaerator-cum-expansion tank consisting of expansion, Deaerator and buffer


vessels, gauge glass assembly and level switch. Nozzles are provided for inlet &
outlet on deaerator, for drain on buffer vessel and for overflow,air vent & top
up on expansion vessel

One Monobloc Pressure Jet spill return ON/OFF burner suitable for light
oil(HSD) with inbuilt combustion blower assembly along with motor and
high voltage spark ignition for burner light up. The blower will be mounted
with fuel oil pump

MOUNTINGS AND FITTINGS


One Set Isolating needle valves for pressure indicating instruments.

FUEL

Oil Line

One Fuel oil filter suitable for light oil


THERMIC FLUID

One spring loaded flow relief valve for mounting on Thermic outlet line.

INSTRUMENTS, CONTROLS AND SAFETIES


One Burner programmer with matching flame sensor

One Hooter mounted on control panel for audible safety alarm.

THERMIC FLUID

One Temperature indicator-cum- switch for burner ON-OFF cycle, on Thermic fluid
inlet of the heater

One Temperature indicator-cum-switch for high Thermic fluid temperature


alarm & interlock with burner, on Thermic fluid outlet of the heater

One Pressure gauge at Thermic fluid inlet of the heater

One Pressure gauge at Thermic fluid outlet of the heater

One Differential pressure switch connected across Thermic fluid inlet and
outlet of the heater for low flow alarm & interlock with burner

One Gauge glass on deaerator-cum-expansion tank

One Level switches for low level alarm & interlock with burner, on deaerator-
cum- expansion tank

FLUE GAS

One Temperature indicator-cum-switch for high stack temperature alarm

BATTERY LIMITS

FUEL

Oil Line

Inlet/Outlet of oil filter

Inlet/Outlet of burner
THERMIC FLUID

Inlet and Outlet flanges of Thermic fluid circulating pump

Inlet and outlet flanges of headers of the heater

Inlet and outlet of flow relief valve

Inlet and outlet connections of Deaerator vessel

Inlet of expansion tank for topping up

Vent connection on expansion tank

Overflow connection on expansion tank

Drain connection on buffer vessel

AIR AND FLUE GAS

Suction of blower

Flue gas outlet flange on the heater


PERFORMANCE CRITERIA

THERMIC FLUID
Shell Heat Transfer Oil S2 for bulk oil temperature up to 300 Deg C

Diesel Oil (HSD)

Net Calorific Value - 10,500 Kcal/Kg


Flash Point - 32ºC
Water Content - 0.05% Vol.(Max.)
Kinematic Viscosity - 2.5 cst @ 50ºC
Pour Point - 5ºC
Sediment - 1% Wt Max.
Sulphur - 1 % Wt Max.

ELECTRICAL

415 Volts±6%, 50 Hz±3%, 3 phase, 4 wire system and 240 Volts6%, 50 Hz±3%, 1 phase
for control circuit

AMBIENT CONDITIONS

Ambient/Room temperature – minimum 20ºC, Altitude – maximum 600 meter above


sea level

* Note: Fuels to confirm to enclosed IS specification.


EXCLUSIONS

1. Chimney and flue gas duct between THERMOPAC and chimney.

2. Storage, Service tanks for Fuel Oil/Gas, Thermic Fluid etc. and piping
required up to THERMOPAC.

3. Thermic fluid storage tank and topping up pump.

4. All user equipment, their heat exchangers, automatic and manual valves and
temperature controllers etc.

5. All types of lagging of pipelines, combined deaerator-cum-expansion


tank and insulation wherever required.

6. All civil and structural work for installing the THERMOPAC.

7. CO2 for smothering and CO2 line up to our battery limits (stop valve).

8. Thermic fluid, Fuel oil/gas, water, power, compressed air, Labour, tools
and tackles, consumables etc. required for assembly, erection,
commissioning and operation of THERMOPAC.

9. All electrical wiring such as from Thermic fluid pump motor and from level switch
in deaerator-cum-expansion tank up to control panel, main supply cable to control
panel etc.

10. Any other items not specifically mentioned in our offer.


Commercial Terms & Conditions

1. OPERATING PARAMETERS:

- Model : TPCM - 02

- Heat output ( Kcal/hr) : 2,00,000

- Maximum unit outlet temperature : 280°C

- Fuel : HSD/LDO

- Thermal Efficiency (based on NCV) : 87 ± 2 %

- Electrical supply : AC 3 phase, 415 ± 6%,


50 Hz., ± 3%,4 wire system

2. PRICE SCHEDULE: Ex-Works, Pune

- Price of 1 No. of unit : Rs. 4, 49,000/-

- Packing & forwarding charges : 3 % extra

- Supervision of Erection & Commissioning shall be done “Free of Cost” as part of


our services to the customer.

3. PRICE BASIS:

The prices mentioned above are ex-works, Pune and shall exclude the
following charges:

- Excise duty @ 12.36% extra and CST @ 2% against Form-C


- Octroi, transit Insurance and freight from our works to your site extra.

NOTE: The above mentioned taxes and levies shall be charged as per the rates
prevailing at the time of delivery.

Statutory Variation
“ Any additional taxes, duties and levies/imposition of new taxes, duties and levies at
the time of execution of this contract (till the time of final invoice) either due to
change in law or due to any interpretations of Tax authorities, shall be extra to
Purchaser’s account and shall be paid to Supplier.”
4. PAYMENT TERMS

40% advance along with the order.


Balance payment along with taxes and duties against Proforma invoice prior to
dispatch.

5. DELIVERY PERIOD

The equipment shall be ready for delivery at our works in 9 Weeks from the
date of technically and commercially clear order with requisite advance.

6. VALIDITY

The offer is open for acceptance for a period of 30 days from this date.

*** Note: we request you to release your purchase order on M/s. Thermax Limited,
Hyderabad

For A & M Technologies