You are on page 1of 5

Storage Tank Analysis Report

Page |1

REPORT NO. IQMS/BPCL/NDT/21/146/UG TANK-32

Non-Destructive testing Report.


Bharat petroleum Corp. Limited.
Client:
Bijwasan installation
Location:
-------------
Tender No. :
----------------
P.O. No.:
Ethanol
Product Detail
Inspection
30.12.2021
Date
Next
Inspection 29.12.2026
Due Date:

Ultrasonic thickness measurement equipment

Test Equipment Sona Testing INC.


Sr. No. XBCHY20092401010
Calibration Validity. 09.12.2022
Probe Type/Sr. No. N05/ S456

Prepared By Signature Reviewed By Signature


Name M S Hussain S K Agrawal

Designation ASNT Level II ASNT Level III


Storage Tank Analysis Report
Page |2
1.0 Introduction:
Bharat Petroleum Corporation Limited (BPCL) has awarded job to International Quality
Management services (P) Ltd Faridabad (IQMS) for carrying out Underground tank inspection
Bijwasan Location in India as scope provide by BPCL and OISD STD 129 guidelines. IQMS
carried out tank inspection (i.e. visual inspection & NDT) based on communication received from
BPCL.

Underground Horizontal cylindrical storage tank inspection for the tank no. 32 was performed at
BPCL Bijwasan on dated 30.12.2021 Visual inspection & NDT for the tank was performed as per
the requirement of scope of work.

1.1 References:

Std. Reference:
 OISD 129 Edition Nov. 2006

Reference Documents:

 Previous Inspection Report : Not Available


 G.A Drawing : Not available
 Previous NDT Report : Not Available

Prepared By Signature Reviewed By Signature


Name M S Hussain S K Agrawal

Designation ASNT Level II ASNT Level III


Storage Tank Analysis Report
Page |3
1.2 Basis of Analysis:
 Visual Inspection Findings
 NDT Inspection Findings
 Previous Inspection Report not available
 The analysis has been performed for a specific tank as per requirement of the IQMS
Client/contractor within the scope of the contractor, documents submitted and does
not perpetuate into compliance to any statutory regulations and /or codes of any
country/region.

1.3 Assumptions:
 This report made on the basis of information made available by the client.
 Present report is based on the reference documents mention in clause no 1.3 of this
report.
 On request, BPCL should provide more information to IQMS time to time. We will
happy to revise our report based on the same.
 Condition assessment of tank, determine corrosion rate is based on the details made
available to IQMS, present visual inspection and NDT results.

Prepared By Signature Reviewed By Signature


Name M S Hussain S K Agrawal

Designation ASNT Level II ASNT Level III


Storage Tank Analysis Report
Page |4

ULTRASONIC THICKNESS TESTING OF UG TANK NO.32


BHARAT PETROLEUM CORPORATION LIMITED.
BIJWASAN INSTALLATION NEW DELHI

MODE OF INSPECTION:- ULTRASONIC THICKNESS TESTING


ACCEPTANCE CRETERIA:- OISD STD 129 (ASTM E 797)

Thickness measurement of the UG Tank no. 32 has been carried out at BPCL
Bijwasan on dated 30.12.2021 Measurement thickness has been taken with the
Calibrated Ultrasonic Thickness Gauge.

Horizontal underground cylindrical tank at both dish end plate observed


thickness is acceptable limit. Dish end average thickness is 9.8 mm against
minimum required thickness 9.5 mm.

All Shell plate average thickness 9.4 mm has been taken within area 16 times of
original thickness as per clause no. 12 of OISD STD 129 on top & bottom shell of
Horizontal cylindrical Tank.

Minimum acceptable thickness tolerance is 5 % of nominal wall thickness as per


IS 1852 clause no. 7.3, (Reference of IS 1852 is given in IS 2062)
OISD STD 129 refers to IS 10987 for code of practice for design, fabrication,
testing and installation of underground /above ground horizontal cylindrical steel
storage tank for petroleum products. IS 10987 refer to IS 2062 for material.

Advice:- In overall views, horizontal cylindrical tank is found satisfactory & fit for
further use in similar application.

Prepared By Signature Reviewed By Signature


Name M S Hussain S K Agrawal

Designation ASNT Level II ASNT Level III


Storage Tank Analysis Report
Page |5
THICKNESS MEASUREMENT SURVEY REPORT OF SHELL
Sr. Shell No. Reading ( Thickness in mm)
Remarks
No. R-1 R-2 R-3 R-4 R-5 R-6 R-7 R-8 R-9 R-10
1 1 9.2 9.5 9.7 9.1 9.3 9.2 9.5 9.7 9.1 9.3
2 1 9.5 9.2 9.4 9.6 9.7 9.5 9.2 9.4 9.6 9.7
3 2 9.1 9.6 9.2 9.4 9.1 9.1 9.6 9.2 9.4 9.1
4 2 9.6 9.4 9.6 9.2 9.5 9.6 9.4 9.6 9.2 9.5
5 3 9.4 9.7 9.1 9.7 9.2 9.4 9.7 9.1 9.7 9.2
6 3 9.5 9.7 9.1 9.3 9.2 9.5 9.7 9.5 9.7 9.1
7 4 9.2 9.4 9.6 9.7 9.5 9.2 9.4 9.2 9.4 9.6
8 4 9.6 9.2 9.4 9.1 9.1 9.6 9.2 9.6 9.2 9.4
9 5 9.4 9.6 9.2 9.5 9.6 9.4 9.6 9.4 9.6 9.2
10 5 9.7 9.1 9.7 9.2 9.4 9.7 9.1 9.7 9.1 9.7
11 6 9.5 9.7 9.1 9.3 9.2 9.5 9.7 9.5 9.7 9.1
12 6 9.2 9.4 9.6 9.7 9.5 9.2 9.4 9.2 9.4 9.6
13 7 9.6 9.2 9.4 9.1 9.1 9.6 9.2 9.6 9.2 9.4
14 7 9.4 9.6 9.2 9.5 9.6 9.4 9.6 9.4 9.6 9.2
15 8 9.7 9.1 9.7 9.2 9.4 9.7 9.1 9.7 9.1 9.7
16 8 9.5 9.7 9.1 9.3 9.2 9.5 9.7 9.5 9.7 9.1
17 9 9.2 9.4 9.6 9.7 9.5 9.2 9.4 9.2 9.4 9.6
18 9 9.6 9.2 9.4 9.1 9.1 9.6 9.2 9.6 9.2 9.4
19 10 9.4 9.6 9.2 9.5 9.6 9.4 9.6 9.4 9.6 9.2
20 10 9.7 9.1 9.7 9.2 9.4 9.7 9.1 9.7 9.1 9.7
21 11 9.5 9.7 9.1 9.3 9.2 9.5 9.7 9.5 9.7 9.1
22 11 9.2 9.4 9.6 9.7 9.5 9.2 9.4 9.2 9.4 9.6
23
24
25 Dish end 01 10.0 9.9 9.8 10.0 9.7 10.2 9.8 9.7 9.8 10.0
26 Dish end 01 9.5 10.0 9.9 9.7 9.6 9.9 10.0 9.9 9.7 9.5
27 Dish end 01 9.9 9.9 10.0 9.7 9.7 10.1 9.7 9.9 9.8 10.0
28 Dish end 02 9.7 10.0 9.5 9.7 10.2 9.8 10.0 9.7 10.1 9.9
29 Dish end 02 10.0 9.9 9.7 10.0 9.9 10.0 9.9 10.0 9.9 9.7
30 Dish end 02 9.8 10.0 10.1 9.9 9.8 9.5 9.9 9.8 10.0 9.6
25
Man hole inlet nozzle thickness: 8.0, 8.4, 8.5, 8.1
Man hole Outlet nozzle thickness: 8.3, 8.2, 8.1, 8.3

Prepared By Signature Reviewed By Signature


Name M S Hussain S K Agrawal

Designation ASNT Level II ASNT Level III