REPUBLIC OF THE PHILIPPINES CAMARINES SUR

POLYTECHNIC COLLEGES NABUA,


CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

CHAPTER 2
EXECUTIVE SUMMARY

DESIGN
The procedure followed in the load calculation for the design of Air Conditioning System
was based on the following reference books: ASHRAE GRP 158, ASHRAE 1981
FUNDAMENTALS, Hand book of Air conditioning systems Design by Carrier Air conditioning
Company and Trane Air Conditioning Manual

A. Equipment Selected
1. Air Conditioning System
ACCU Selection/ Specification
Make/Model No.

Cooling Capacity 9.63 TONS

Compressor Power Input


2. Air Handling Units
A. Ground Floor
Sensible Cooling Capacity 57816.74 BTU/HR
Latent Cooling Capacity 9225.57 BTU/HR
Supply Air Flow 2664.4 CFM
Ventilation/ Fresh air CFM
Entering Air Temperature 92 F DB, 82 F WB
Leaving Air Temperature 75 F DB, 50% RH
Air Handling Unit Mounting Vertical
Air Handling Unit Type Draw Throw Up-Blast Front
Fan Type Centrifugal Forwards Curve
Electrical Power Supply 220 V/3-PH/60HZ

Make/Model No.

2/Second Floor
Sensible Cooling Capacity 52,667.38 BTU/HR
Latent Cooling Capacity 10,655.07 BTU/HR
Supply Air Flow 1522.4 CFM
Ventilation/ Fresh Air CFM
Entering Air Temperature 92 F DB, 82 F WB
Leaving Air Temperature 75 F DB, 50% RH
Air handling Unit Type Draw Throw Up-Blast Front
Fan Type Centrifugal Forward Curve
Electrical Power Supply 220 V/3-PH/60HZ

Make/ Model No.


Note: Only one AHU will be used and riser will added for second floor supply
Time table:
The project if ever constructed should be started during summer to minimize the
difficulties encountered in the rainy period of the year and shoul last by 10 working days.

References:

1. Cooling and Heating Load Calculation Manual – ASHRAE GRP 158

2. Handbook of Air Conditioning System Design – Carrier Air Conditioning Co.

th
3. Trane Air Conditioning Manual (57 printing December 1981)

4. ASHRAE 1981 Fundamentals Handbook


HVAC Design Criteria:

1. Project Location : Baao, Camarines Sur, PHILIPPINES

*
2. Latitude : 13° - 27’22 N

3. Altitude/Elevation : 17.3 Feet (above sea level)


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

4. Outdoor Design Conditions (1 % exceeded values)

4.1 Summer : 94°F DB, 82°F WB

4.2 Winter : 74°F DB

5. Indoor Design Conditions (ASHRAE GRP 158, Art. 2.1 page 2.1)

5.1 Summer : 78°F DB, 50% RH

5.2 Winter : 72°F DB, 50% RH

6. Mean Daily Range : 20°F

I – Determination of Heat Transfer Coefficient, U (BTU/HR-FT²-°F)

A. Roof (Pitched Metal Roof)

① ②

Figure 1
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

SI MATERIAL RESISTANCE

1 Outside Surface (@7.5 mph wind) 0.25

2 GI Sheet Roofing (corrugated) 0.00

3 Expanded polystyrene, molded 3.57


beads.

4 Air space 0.90

5 Plywood ¼ “ thick 0.31

6 Inside Surface (still air) 0.92

Total Resistance, RT = 5.95

UROOF = 1/RT = 1/5.95

UROOF = 0.168 BTU/HR-FT²-F

B. Exterior Wall

1 5

Figure 2
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

SI MATERIAL RESISTANCE (R)

1. Outside Air @ 7.5 Mpa 0.25

2. Cement 5/8” Plaster 0.39

3. CHB (4” thick) 0.71

4. 5/8 Plaster 0.39

5. Inside Surface (Still Air) 0.68

Total Resistance, RT = 2.42

UWALL = 1/RT =1/2.42

UWALL = 0.296 BTU/HR-FT²-°F

C. Glass (ASHRAE GRP 158; Table 3.14A, page 3.24)

UGLASS = 1.04 BTU/HR-FT²-°F (No indoor shade)

D. Door (ASHRAE GRP 158; Table 3.6, page 3.14)

UDOOR = 0.47 BTU/HR-FT²-°F (for 1.5” thick)


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

II – Determination of Month and Time for Peak

Load Observations & Finding

1. Latitude-Month correction from ASHRAE GRP 158 Table 3.12 shows maximum value for

the month of June (i.e., N=6; E & W = -1; S = -7; Horizontal=0 for 16° N Latitude).

2. Fenestration load in this calculation is very minimal since exterior glasses in the North

wall are shaded and not exposed to direct sunlight. East & West walls do not contain

exterior glasses since locations are in the property lines and are fire rated walls.

3. Roof (A=1291FT²) & East Wall (A=254.2FT²) constitute the biggest areas for external

loads. Roof #1 (Table 3.7 page 3.18, ASHRAE GRP158) without suspended ceiling has

maximum CLTD @ 14:00 HRS (Table 3.8 page 3.19, ASHRAE GRP158). Group E (Table 3.9

page 3.20, ASHRAE GRP 158) East Wall has maximum CLTD @ 13:00 HRS (Table 3.10

page 3.21, ASHRAE GRP 158). The value of Group E East Wall CLTD @ 14:00 HRS is only

one (1) unit less than the CLTD value @ 13:00 HRS.

4. From the above analysis, TIME & MONTH for peak load shall be @ 14:00 HRS in JUNE.

III – Determination of Cooling Load Temperature Differences, CLTD

Note: Items that require CLTD evaluation are; Roof, Exterior Walls & Fenestration

Areas (Glass).
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

A. Pitched Metal Roof (Roof #1)

From ASHRAE GRP 158 Table 3.8 page 3.19, corrected CLTD for Roof

is: CLTDCORR = [(CLTD + LM) x K + (78 - TR) + (TO – 85)] x f

Where:

CLTD = 79 (ASHRAE GRP 158, Table 3.8)

LM=0 (ASHRAE GRP 158, Table 3.12)

K=1 color adjustment factor (dark colored roof)

(78-TR) = 0 (ASHRAE GRP 158, Table 3.13)

(TO – 85) ; Where: TO = Outside Mean Temperature

TO = Design Outside DB – ½ Daily Range (Note no.2)

TO=94°F–½(20°F)=94–10=84

(TO–85)=84–85=-1 (ASHRAE GRP 158, Table 3.13)

f = 1.0 no attic fan (page 3.19) @ note “c”

CLTDCORR = [(79 + 0) x 1 + 0 + (-1)] x 1

CLTDCORR = 78 °F (for Roof)

A. Exterior Walls (Group E)

From ASHRAE GRP 158 Table 3.10 page 3.21, corrected CLTD for Wall is:

CLTDCORR = (CLTD + LM) x K + (78 - TR) + (TO – 85)

Where: K=1 color adjustment factor (dark colored wall)


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

(78–TR)=0 (ASHRAE GRP 158, Table 3.13)

(TO – 85) = -1 (ASHRAE GRP 158, Table 3.13)

CLTDCORR = (CLTD + LM) x 1 + 0 + (-1) = (CLTD + LM) - 1 = CLTD + LM - 1

@ 16°N latitude, 14:00 HRS in June & Group E wall; CLTD CORRare as follows:

Orientation CLTD + LM - 1 = CLTDCORR

N 13 + 6 - 1 = 18

S 24 + -7 - 1 = 16

E 37 + -1 - 1 = 35

W 14 + -1 - 1 = 12

B. Fenestration Areas (Glass)

From ASHRAE 1981 Fundamentals Handbook, Table 10 page 26.16, corrected CLTD

for Glass @ 14:00 HRS is:

CLTDCORR = CLTD + (78-TR) or CLTDCORR = CLTD + (TO – 85)

Where: CLTD = 16 (ASHRAE 1981 Fund., Table 10 page 26.16)

(78–TR)=0 (ASHRAE GRP 158, Table 3.13)

(TO – 85) = -1 (ASHRAE GRP 158, Table 3.13)


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

Therefore;

CLTDCORR = 16+ 0 or CLTDCORR = 16 + (-1)

CLTDCORR = 16 °F or CLTDCORR = 15 °F

Use, CLTDCORR =16°F (for Glass)

IV – Solar Load:

q = A x SC x SHGF x CLF

Where;

q = Glass Solar Load, BTU/HR

A = Area, Net Glass Area Calculated from Plans, FT²

SC = Shading Coefficients (ASHRAE GRP 158, Table 3.18)

SC = 0.94 (¼” to ½” Clear Glass w/o Interior shading)

SHGF = Maximum Solar Heat Gain Factor for Specific Orientation of Surface.

From ASHRAE GRP 158 Table 3.26 page 3.37, for externally shaded glass & @ 16°N

latitude month of June, the SHGF (in BTU/HR-FT²) for the following orientations are:

N=45 S=40 E=46 W=46


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

CLF = Cooling Load Factor (ASHRAE GRP 158, Table 3.27)

For Glass without interior shading, medium room construction, north latitudes & @ 14:00 HRS,

the CLF for the following orientations are:

N = 0.75 S = 0.58 E = 0.31 W = 0.29

V – Internal Loads

A. People

A. Sensible Load

q = No. x Sens. H.G. x CLF

Where:

No. = Number of People in Space (From Survey or Table 5.3)

No. = 20 - 30 persons/1000 FT² floor area (ASHRAE GRP 158, Table 5.3)

Sens. H.G. = 315 BTU/HR/person (ASHRAE GRP 158, Table 4.5)

Sens. H.G. = 255 BTU/HR/person (ASHRAE GRP 158, Table 4.5)

CLF = 0.85 (ASHRAE GRP 158, Table 4.6)


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

B. Lights

q = INPUT x CLF

Where :

CLF = Cooling Load Factor based on total hours of operation & time

“a” Classification for Lights (vented or free hanging lights)

“a” = 0.75 (ASHRAE GRP 158, Table 4.2)

“b” Classification for Lights

“b” = C (ASHRAE GRP 158, Table 4.3)

For 14 hours operation with “a”=0.75 & “b” = C and 14 number of hours after light

are turned on, CLF is:

CLF = 0.93 (ASHRAE GRP 158, Table 4.4D)

VI – Ventilation & Infiltration Air

A. Sensible

qs= 1.1 x CFM x Δt

Where :

CFM = Ventilation & Infiltration Air, Standard CFM

CFM = 10 to 15 CFM/person (ASHRAE GRP 158, Table 5.3)

Δt = I

nside – Outside Air Temperature Difference, °F


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

Δt = 94 °F – 78 °F = 16 °F

B. Latent

ql= 4840 x CFM x

ΔW Where:

ΔW = Inside – Outside Air Humidity Ratio Difference, lbs H2O/lb dry air

Using Psychrometric Chart;

WINSIDE = 0.0102 lbs H2O/lb dry air (@ 78°F DB & 50% RH)

WOUTSIDE = 0.021 lbs H2O/lb dry air (@ 94°F DB, 82°F WB)

ΔW = 0.021 - 0.0102

ΔW = 0.0108 lbs H2O/lb dry air

SEQUENCE OF COOLING LOAD CALCULATION TYPICAL FOR EVERY ROOM


(Room considered in this example is Bedroom 4)
I – External Conduction Load

A. Roof

q = U x A x CLTD

Where :

U = 0.160 BTU/HR-FT²-°F (previously calculated)

A = 131.8FT² (Area calculated from Plan/Drawing)

CLTD = 78.00 °F (previously calculated)


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

q = 0.160 x 131.8 x 78

q = 1644.864BTU/HR

B. Walls

q = U x A x CLTD

Where :

U = 0.47BTU/HR-FT²-°F (previously calculated)

A = Net Wall Area calculated from Plan/Drawing, FT²

CLTD = Cooling Load Temp. Difference for a particular wall orientation

B.1 North Wall

q = 0.47 x90.6 x 18

q = 766.48BTU/HR

C. Glass

q = U x A x CLTD

Where :

U = 1.04 BTU/HR-FT²-°F (previously calculated) A

= Glass Area calculated from Plan/Drawing, FT²

CLTD = 16 °F (previously calculated)

q = 1.04 x 48.4 x 16

q = 805.38BTU/HR
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

D. Total External Conduction Load

qCONDUCTION =766.48 + 510.98 + 548.25 +

805.38 qCONDUCTION =2,631.08 BTU/HR

II – External Solar Load

q = A x SC x SHGF x CLF

Where:

A = Net Glass Area calculated from Plan/Drawing

SC = 0.94 (Shading Coefficient previously calculated)

SHGF = Max. Solar Heat Gain Factor for Specific Orientation of


Surface (in BTU/HR-FT²)

CLF = Cooling Load Factor for a particular Glass Orientation.

A. North Glass

q =24.2 x 0.94 x 45 x 0.75

q = 767.75 BTU/HR

B. Total External Solar Load

qSOLAR =1,071.20BTU/HR
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

III – Internal Loads

A. People

A. Sensible Load

qS = No. x Sens. H.G. x CLF

Where:

Sens. H.G. = 255 BTU/HR/person (ASHRAE GRP 158, Table 4.5)

CLF = 0.85 (ASHRAE GRP 158, Table 4.6)

qS = 2 x 255 x 0.85

qS = 433.50BTU/HR

B. Light

q = 3.41 x Watts x Bal. and use factor

Where:

A = Net Glass Area calculated from Plan/Drawing

Watts = 244 watts

Bal. and use factor = 1

q = 3.41 x 263.58 x 1

q = 898.81BTU/HR
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

C. Total Internal Loads

qS-INTERNAL = 433.5BTU/HR + 898.81.04BTU/HR

qS-INTERNAL = 1,332.31 BTU/HR

IV – Infiltration Air

A. Sensible

QS = 1.10 x CFMOA x Δt

Where:

CFMOA = No. of persons x

CFM/person CFMOA = 2 x 9 cfm

CFMOA = 18

Δt = 16 °F (Outside – Inside Air Temp. Difference, 94°F – 78 °F)

QS = 1.10 x 18 x 16

QS=316.8 BTU/HR

V – Total Sensible & Latent Load

QS = qCONDUCTION +qSOLAR + qS-INTERNAL + qS-INFILTRATION

QS = 3,727.58 BTU/HR +1,071.2BTU/HR +1,332.31 BTU/HR + 316.8BTU/HR

QS = QL6447.89BTU/HR
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

VI – Cooling Load Summary

A. Net Room Sensible (NRS) = Total Sensible (QS) + Duct Heat Gain (%

QS) Net Room Sensible (NRS) = 6447.89+ (6447.89 x 2%)

Net Room Sensible (NRS) = 6576.85BTU/HR

B. Net Room Latent (NRL) = Total Latent (QL) + Duct Heat Gain (% QL)

Net Room Latent (NRL) = 1450.89 + (1450.89 x 2%)

Net Room Latent (NRL) = 1479.91 BTU/HR

C. Total Load = NRS + NRL

Total Load = 6576.85BTU/HR + 1479.91 BTU/HR

Total Load = 8056.76 BTU/HR

D. Sensible Heat Ratio (SHR)

SHR = NRS / Total Load

SHR = 6576.85 / 8056.76

SHR = 0.816

E. Supply Air Temperature, TS = 53 °F (Psychrometric Chart value)

F. Room Design Temperature, TR = 78 °F

G. ΔTS=TR - TS

ΔTS = 25 °F
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

H. Supply CFM = NRS / 1.1 x ΔTS

Supply CFM = 6576.85/ (1.1 x 25)

Supply CFM = 239cfm

VII – Cooling Equipment Load

A. Sensible = NRS + % Return Duct Gain + Ventilation Air (VS)

Sensible = 6576.85 + (6576.85 x 2%) + 0

Sensible = 6708.39 BTU/HR

SENS (Equipment) = Sensible + % Safety Factor

SENS (Equipment) = 6708.39 + (15% x 6708.39)

SENS (Equipment) = 7714.65 BTU/HR

B. Latent = NRL + % Return Duct Gain + Ventilation Air (V L)

Latent = 1479.91 + (1479.91 x 2%) + 0

Latent = 1509.51 BTU/HR

LAT (Equipment) = Latent + % Safety Factor

LAT (Equipment) = 1509.51+ (15% x 1509.51)

LAT (Equipment) = 1736 BTU/HR


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

C. Total Equipment Load = SENS (Equipment) + LAT (Equipment)

Total Equipment Load = 7714.65 BTU/HR +1736 BTU/HR

Total Equipment Load = 9450.65 BTU/HR

D. Tonnage = Total Equipment Load (BTU/HR) /

12,000 Tonnage = 9450.65 / 12,000

Tonnage = 0.79 TR
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

SUMMARY OF LOADS AND LOAD CALCULATION SHEET FOR EVERY ROOM:


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008
Misc.

LOADCALCULATION FORGROND FLOOR


QS = 1.10 x _18
QL = 4840 x

LOAD CALCULAIONS SHEET

March 20, 2018

Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 Dream House
Latitude 13° - 27' N DB daily range 20°F Day June Engr. Joeffrey D.
Q

Summer Month r Date COOLING (Sen.)

Outside 94
Inside 78
Differ. 16 1,598.94
I em
SHG = Sensible Heat Gain
LIVINGROOM

LHG = Latent Heat Gain (per item) 1,888.46

Wall
Wall
IO N

Wall
LOADS

NDU C

Wall
Roof
COOLING

CO

Glass
EXTERNA

Partition
L

Ceiling
Floor

Item

Glass
SOLAR

Glass
Glass 1,669.20
Glass
INTERNA

COOLINGLOAD

People
L

Elect'l. Eqpt.

Lights
Motors

Gas Eqpt.
IS
O
9001:

2008
S
2,319.4
5
Total Heating Qs x Safety
EL. HTR. = --------------------------------------------
316.80
3413
ROOMSUBTOTAL Q
S'
7,294.80 QL'
EL. HTR. = KW

VEN T.
VS = 1.10 x CFMOA x ΔT -------------------------------------------------------------------------------------------------------

VL = 4840 x CFMOA x 0.0108 ΔW It is recommended to use ASHRAE tables with this form.
IS
O
9001:

Design conditions for Baao, Cam. Sur, Philippines Hour14:00 LOAD CALCULAT IONS SHEET COOLING LOAD SUMMARY 2008
Latitude 13° -27' N DB daily range 20 °F Day June Sensible (BTU/HR) Latent (BTU/HR)
Q &Q
Summer Month Winte r
Date March 20, 2018 Sheet No. of S' L' → 4,803.15 1,450.90
DB °F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 96.06 29.02
Outside 94 82 0.0210 74 vapor per Building Name : Dream Home Room :
Study Room Blower Motor Input ….………%
Inside 78 50% 0.0102 72 lb dry air Computed by : Joeffrey D. Bustinera Checked by : JDB Net Room Sensible (NRS) (Total of above) 4,899.21
Differ. 16 0.0108 2 Approved by : Net Room Latent (NRL) (Total of above) 1,479.91
Q
SHG = Sensible Heat Gain (per item) = Sensible Load
S Total Load = NRS + NRL 6,379.13

POLYTECHNICREPUBLIC
LHG = Latent Heat Gain (per item) QL Latent Load
= COOLING (Sen.) HEATING SHR = NRS / Total Load 0.768
Orien- Area, Temp. Diff. QS Supply Air Temp., °F (TS) 55.00
Item U
tation FT² (Corrected) BTU/HR. Room Design Temp., °F (TR) 78.00
STUDY

Wall N 90.60 0.470 18.00 766.48 TR-TS = ΔTS 23.00


Q

OF GR P
Wall S 16.00 Temp. S Supply CFM = NRS / 1.1 x ΔTS 194
ON

Diff. BTU/HR.

AD
CONDU
CT I

Wall E 35.00 - - COOLING EQUIPMENT LOAD


RY

LI

M
R

O
O
R
A

Wall W 90.60 0.470 12.00 510.98 - NRL 1,479.91


Roof NRS 4,899.21 % Return Duct Gain 29.60
% Return Duct Gain 97.98
Glass 48.40 1.040 ΔT 16 805.38 - Vs - VL - Total
Partition 16 - - Total above 4,997.20 above 1,509.51

S
ΔT
- % Safety Factor 749.58 % Safety Factor 226.43

SCHOOLURNCAMARINES
Ceiling ΔT 16 -
Floor ΔT 16 - - SENS (Equipt.) 5,746.78 LAT (Equipt.) 1,735.94
ROO

Infilt. & Vent. - Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)
M

SUM (CONDUCTION) 2,082.84


Total Equipt. Load = 7,482.72 BTU/HR
Orien- Area, Max.

ABUA,
Item Shade Coef. CLF Total Tonnage = Total BTU/HR ÷ 12000 = 0.62 TR

tation FT² SHG


Glass 24.20 0.94 45 0.75 767.75 -------------------------------------------------------------------------------------------------------
N

SUR
SO LAR

HUMIDIFICATION
Glass S 0.94 40 0.58 -
Steam/Vapour Required = M lb/hr
Glass E 0.94 46 0.31 - COOLING (Latent)
M = 60/v x CFMOA x ΔW
Glass W 24.20 0.94 46 0.29 303.46 QL (BTU/HR)
CF
Where : CFMOA = Outside Air CFM = M
SUM (SOLAR) 1,071.20 No. x LHG = QL
=Room Volume x Air Changes per HR / 60
People No. 2 x _255 SHGX 0.85 CLF 443.50 2 255 510.00
v = Specific Air Volume
COOLINGL

Lights 2 Wt. x 131.79 x 1_ Bal. & use factor 898.81 -


OADS

3.41 x
Misc.
Use minimum one air change per hour.
Motors 3600 x HP
-------------------------------------------------------------------------------------------------------
Elect'l. Eqpt. 3.41 x Wt. x CLF -
ELECTRIC HEATER SIZING
Gas Eqpt. No. x SHG x CLF -

Total Heating Qs x Safety Factor


SUM (INTERNAL LOADS) 1,332.31 -
EL. HTR. = ----------------------------------------------
QS = 1.10 x _18 CFMOA x _16 ΔT 316.80 3413
QL = 4840 x CFMOA x 0.0108 ΔW
Q EL. HTR. = KW
S' 4,803.15 QL' -------------------------------------------------------------------------------------------------------
T.

VS = 1.10x CFMOA x ΔT It is recommended to use ASHRAE tables with this form.


VL = 4840 x ΔW
VEN

CFMOA x 0.0108
IS
O
9001:

2008
Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 COOLING LOAD SUMMARY
LOAD CALCULATIONS SHEET
Latitude 13° - 27' N DB daily range 20 °F Day June Sensible (BTU/HR) Latent (BTU/HR)
Summer Month r Date March 20 2018 Sheet No. of QS' & QL' → 1,450.90
DB °F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 29.02
Outside 94 82 0.0210 74 vapor per Building Name : Dream Home Room Breakfast Room Blower Motor Input ….………%
:

Inside 78 50% 0.0102 72 lb dry air Computed by : Joeffrey D. Bustinera Checked by : JDB Net Room Sensible (NRS) (Total of above)
Differ. 16 0.0108 2 Approved by : Net Room Latent (NRL) (Total of above) 1,479.91

POLYTECHNICREPUBLIC
Q
SHG = Sensible Heat Gain (per item) S = Sensible Load Total Load = NRS + NRL 6,771.45
LHG = Latent Heat Gain (per item) QL = Latent Load COOLING (Sen.) Temp. HEATINGQS SHR = NRS / Total Load 0.781
Orien- Are, Temp. Diff. QS Diff. BTU/HR. Supply Air Temp., °F (T ) 55.00
Item U
S

tation FT² (Corrected) BTU/HR. - Room Design Temp., °F (TR) 78.00


Wall TR-TS = ΔTS 23.00
T I N

N 74.20 0.470 18.00

OF GR P
Wall - Supply CFM = NRS / 1.1 x ΔTS 209
O

S 32.80 0.470 16.00


BREAKFASTR OOM

W 246.66 - NRL

AD
Wall E 123.40 0.470 3512.00 695.-98 COOLING EQUIPMENT LOAD 1,479.91
LOAD
S

Gain

Roof NRS 5,291.54 % Return Duct 29.60


V
COOLING

ΔT 16 805.38 - % Return Duct 105.83 -


CO

Glass 48.40 1.040 L

Partition ΔT 16 - - Vs - Total above 1,509.51


Ceiling ΔT 16 - - Total above 5,397.37 % Safety Factor 226.43
EXTERNA

Floor Item Shade Coef. ΔT 16 - Total - % Safety Factor 809.61 LAT (Equipt.) 1,735.94
L

- SENS (Equipt.) 6,206.98


CLF

Infilt. & Vent.


SUM (CONDUCTION) 2,375.74 Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)

S
Orien- Area, Max. Total Equipt. Load = 7,942.91 BTU/HR
0.66 TR

SCHOOLURNCAMARINES
Tonnage = Total BTU/HR ÷ 12000 =
R

tation FT² SHG


SOL

N 0.94 45 0.75 767.75 -------------------------------------------------------------------------------------------------------


A

Glass
S
Glass 0.94 40 0.58 - HUMIDIFICATION

ABUA,
Glass E 0.94 46 0.31 - COOLING (Latent) Steam/Vapour Required = M lb/hr
Glass W 0.94 46 0.29 303.46 QL (BTU/HR) M = 60/v x CFMOA x ΔW
Q

SUR
SUM (SOLAR) 1,071.20 No. x LHG = L Where : CFMOA = Outside Air CFM = CFM
People No. 2 x _255 SHG X 0.85 CLF 433.50 2 255 510.00 = Room Volume x Air Changes per HR / 60
INTERNAL
COOLINGL

Lights 3.41 x 2 Wt. x 145.24 x 1 Bal. & use factor 990.54 v = Specific Air Volume
OADS

Motors 3600 x HP Use minimum one air change per hour.


Elect'l. Eqpt. 3.41 x Wt. x CLF - -------------------------------------------------------------------------------------------------------
Gas Eqpt. No. x SHG x CLF - ELECTRIC HEATER
SIZING Misc. -
INFILT

SUM (INTERNAL LOADS) 1,424.04 - Total Heating Qs x Safety Factor


QLS = 4840 x _18 CFMOAOA x _0.0108 ΔW EL. HTR. = 3413
.

Q = 1.10 x _18 CFM x 16 ΔT 316.80 --------------------------------------------


Q Q
S' 5,187.78 L' EL. HTR. = KW
T.

VS = 1.10 x CFMOA x ΔT - - - - - - - - - - - - - - - - -----------------------------------------------------------------------


V
VEN

L = 4840 x CFMOA x 0.0108 ΔW It is recommended to use ASHRAE tables with this form.
Glass
Glass

People
Lights

COOLINGLOA
Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 COOLING LOAD SUMMARY

DS
Misc.

LOAD CALCULATIONS SHEET


Motors
Elect'l. Eqpt.
Gas Eqpt.
Latitude 13 °
-27'N DB daily range 20 °F Day June Sensible (BTU/HR) Latent (BTU/HR)

Q &Q
Summer Month Winter Date March 20, 2018 Sheet No. of S' L' → 8,928.31 2,515.90
KITCHENAND DINNINGROOM

DB °F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 178.57 50.32

vapor per Building Name : Dream Home Room : Kitchen & Dining
Outside 94 82 0.0210 74
Inside 78 50% 0.0102 72

Differ. 16 0.0108

SHG = Sensible Heat Gain (per item)


LHG = Latent Heat Gain (per item)

Item Orien- Area,

tation
Wall N

Wall S
T IO N

Wall E
LOADS

Wall
NDUC

W
COOL
ING

CO

Roof
EXTER

Glass
NAL

Partition

Door

Floor ΔT

SUM

Orien-
Item
R

tation
OLA

Glass N
Glass S
S
IS M = 60/v x CFMOA x ΔW

O Where : CFMOA = Outside Air CFM = CFM


90
01
:

20
08

G
R
A
D
U
A
T
E

P
O
L
Y
T
E
C
H
N
I
C
O
F
C
THE
Q
S = 1.10 x 18 CFMOA x 16 ΔT 316.80 EL. HTR. = ----------------------------------------------
Q 3413
L = 4840 x _18 CFMOA x 0.0108 ΔW
Q S'
8,928.31 QL' EL. HTR. = KW
V

VEN T.
S = 1.10 x CFMOA x ΔT -------------------------------------------------------------------------------------------------------

V It is recommended to use ASHRAE tables with this form.


L = 4840 x CFMOA x ΔW
IS
O
9001:

Design conditions for Calabanga, Camarines Sur, Philippines Hour 14:00 LOAD CALCULAT IONS SHEET COOLING LOAD SUMMARY 2008
Latitude 14° -35' N DB daily range 20 °F Day June Sensible (BTU/HR) Latent (BTU/HR)
Summer Month Winter Date March 20, 2018 Sheet No. of QS' & QL' → 4,190.81 1,450.90
DB °F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 83.82 29.02
Outside 94 82 0.0210 74 vapor per Building Name : Dream Home Room : Bedroom 1 Blower Motor Input ….………%
Inside 78 50% 0.0102 72 lb dry air Computed by :Joeffrey D. Bustinera Checked by : JDB Net Room Sensible (NRS) (Total of above) 4,274.62
Differ. 16 0.0108 2 Approved by : Net Room Latent (NRL) (Total of above) 1,479.91
SHG = Sensible Heat Gain (per item) QS = Sensible Load Total Load = NRS + NRL 5,754.54

POLYTECHNICREPUBLIC
Q
LHG = Latent Heat Gain (per item) L = Latent Load COOLING (Sen.) HEATING SHR = NRS / Total Load 0.743
Orien- Area, Temp. Diff. QS Supply Air Temp., °F (TS) 54.00
Item U
tation FT² (Corrected) BTU/HR. Temp. QS Room Design Temp., °F (TR) 78.00
Wall N 98.40 0.470 18.00 832.48 Diff. BTU/HR. TR-TS = ΔTS 24.00
Wall S 16.00 - Supply CFM = NRS / 1.1 x ΔTS 162

OF GR P
Wall E 74.20 0.470 35.00 1,220.59 COOLING EQUIPMENT LOAD
CON D U C T I O N

Wall 12.00 - - 1,479.91

AD
W NRL

Roof - NRS 4,274.62 % Return Duct Gain 29.80


OADS
COOL
RNAL
EXTE

INGL

Glass 24.20 1.040 ΔT 16 402.69 % Return Duct Gain 85.49 VL


1BEDR
OOM

Partition ΔT 16 - Total - Vs Total above 1,509.51


Ceiling ΔT 16 - - Total above 4,360.12 % Safety Factor 226.43
Floor 129.10 ΔT 16 - - % Safety Factor 654.02 LAT (Equipt.) 1,735.94
- SENS (Equipt.) 5,014.13
SUM (CONDUCTION) 2,455.74 Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)

S
Infilt. & Vent.
Item Orien- Area, Max. CLF Total Equipt. Load = 6,750.07 BTU/HR
Sha de Coef.

SCHOOLURNCAMARINES
tation FT² SHG Tonnage = Total BTU/HR ÷ 12000 = 0.56 TR

Glass N 0.94 45 0.75 - -------------------------------------------------------------------------------------------------------


SO L R

Glass S 0.94 40 0.58 - HUMIDIFICATION


A

ABUA,
Glass E 24.20 0.94 46 0.31 324.39 COOLING (Latent) Steam/Vapour Required = M lb/hr

Glass W 0.94 46 0.29 - QL (BTU/HR) M = 60/v x CFMOA x ΔW

SUR
SUM (SOLAR) 324.59 No. x LHG = QL Where : CFMOA = Outside Air CFM = CFM
People No. 2 x 255 SHG X 0.85 CLF 433.50 2 255 510.00 = Room Volume x Air Changes per HR / 60
GLOADS
COOLIN

Lights 3.41 x 2 Wt. x 96.83_ x 1 _ Bal. & use factor 660.38 - v = Specific Air Volume
Misc.

Motors 3600 x HP Use minimum one air change per hour.


Elect'l. Eqpt. 3.41 x Wt. x CLF - -------------------------------------------------------------------------------------------------------
Gas Eqpt. No. x SHG x CLF - ELECTRIC HEATER SIZING

SUM (INTERNAL LOADS) 1,093.88 Total Heating Qs x Safety Factor


QS = 1.10 x 18 CFMOA x _16 ΔT 316.80 EL. HTR. = ----------------------------------------------
QL =4840 x 18 CFMOA x 0.0108 ΔW 3413
Q
S' 4,190.81 QL' EL. HTR. = KW
T.

VS = 1.10x CFMOA x ΔT -------------------------------------------------------------------------------------------------------


VEN

VL =4840 x CFMOA x 0.0108 ΔW It is recommended to use ASHRAE tables with this form.
IS
O
9001:
Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 COOLING LOAD SUMMARY
LOAD CALCULAT IONS SHEET
Latitude 13° - 27' N DB daily range 20 °F Day June Sensible (BTU/HR) Latent (BTU/HR)
2008
Summer Month Winte r Date March 20, 2018 Sheet No. of QS' & QL' → 2,890.20 1,195.89
DB°F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 57.80 23.92
Outside 94 82 0.0210 74 vapor per Building Name : Dream Home Room :
Maid's Room Blower Motor Input ….………%
Inside 78 50% 0.0102 72 lb dry air Computed by : Joeffrey D. Bustinera Checked by : JDB Net Room Sensible (NRS) (Total of above) 2,948.00
Differ. 16 0.0108 2 Approved by : Net Room Latent (NRL) (Total of above) 1,219.81
SHG = Sensible Heat Gain (per item) QS = Sensible Load Total Load = NRS + NRL 4,167.81
LHG = Latent Heat Gain (per item) Q
L = Latent Load COOLING (Sen.) HEATING SHR = NRS / Total Load 0.700
Supply Air Temp., °F (TS) 53.00

POLYTECHNICREPUBLIC
Item Orien- Area, U Temp. Diff. QS
(Corrected) BTU/HR. Room Design Temp., °F (TR) 78.00
FT²
131.20 Temp. QS TR-TS = ΔTS 25.00
Wall tationN 0.470 18.00 1,109.95
Diff. BTU/HR.
Wall S 60.22 0.470 16.00 452.85 Supply CFM = NRS / 1.1 x ΔTS 107
-
Wall E 35.00 - COOLING EQUIPMENT LOAD
IO

Wall 1,219.81

OF GR P
W 12.00 - NRL
S DU
LOAD

ΔT
CT

Glass 5.38 1.040 16 89.52 -


Roof NRS 2,948.00 % Return Duct Gain 24.40

AD
- 58.96
COOLING

% Return Duct Gain VL


CON

Partition 16 Total above 1,244.20


MAID’S ROOM

ΔT -
Vs

- 3,006.96 186.63
Ceiling ΔT 16 - Total above % Safety Factor
Floor ΔT 16 - % Safety Factor 451.04 LAT (Equipt.) 1,430.83
-
- SENS (Equipt.) 3,458.00
EXTERNA

SUM (CONDUCTION) 2,040.38 Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)
-
Orien- Area, Max. Total Equipt. Load = 4,888.84 BTU/HR
Item Sha de Coef. CLF Infilt. & Vent. Tonnage = Total BTU/HR ÷ 12000 = 0.41 TR
FT²

S
tation SHG

SCHOOLURNCAMARINES
Total
-------------------------------------------------------------------------------------------------------
Glass N 0.94 45 0.75 -
SO LA

Glass 5.38 0.94 40 0.58 117.33 HUMIDIFICATION


S

Glass E 0.94 46 0.31 - COOLING (Latent) Steam/Vapour Required = M lb/hr

ABUA,
Glass W 0.94 46 0.29 - QL (BTU/HR) M = 60/v x CFMOA x ΔW

SUM (SOLAR) 117.33 No. x LHG = QL Where : CFM OA = Outside Air CFM = CFM

SUR
People No. 1 x 255 SHG X 0.85 CLF 216.75 1 255 255.00
= Room Volume x Air Changes per HR / 60
Lights 2 Wt. x Bal. & use factor 586.99
INTERN

3.41 x 86.07 x 1 -
Gas Eqpt. No. x SHG x CLF
v = Specific Air Volume
L
A

Motors 3600 x HP
Use minimum one air change per hour.
Elect'l. Eqpt. 3.41 x Wt. x CLF -
-------------------------------------------------------------------------------------------------------

ELECTRIC HEATER SIZING


Misc. -

(INTERNAL LOADS)
SUM
803. 74
Total Heating Qs x Safety Factor
QS = 1.10 x 18 CFMOA _16 xΔT 316. 80 EL. HTR. = ----------------------------------------------

QL = 4840 x 18 CFMOA x 0.0108 ΔW 3413

V
L = 4840 x CFMOA x 0.0108 ΔW
Q S' 2,890.20 QL' EL. HTR. = KW

-------------------------------------------------------------------------------------------------------
V
S = 1.10 x CFMOA x ΔT It is recommended to use ASHRAE tables with this form.
ROOM SUBTOTAL
VS = 1.10 x ΔT

T.
CFMOA x
VL = 4840 x CFMOA x ΔW

VEN
0.0108

C
Design conditions for Baao, Camarines Sur, Philippines Hour 14:00
O
O
L
LOAD CALCULATIONS SHEET
I
Latitude 13° -27' N DB daily range 20 °F Day June N
G

L
Summer Month
O
DB °F WB °F RH W A
Outside 94 82 D
Inside 78 50%
Differ. 16 S
U
SHG = Sensible Heat Gain (per item)
M
LHG = Latent Heat Gain (per item) M
A
TOILET1

Item Orien-
tation R
Wall N Y
Wall S Sens

Wall E QS' & QL' →


N

Wall Supply Duct .…..% Leak + ..….% Heat Gain


TIO

W
Roof Blower Motor Input ….………%
LOADS

NDU C

Net Room Sensible (NRS) (Total of above)


Glass
Net Room Latent (NRL) (Total of above)
COOLIN

Partition
Total Load = NRS + NRL
CO
G

Ceiling
SHR = NRS / Total Load
Floor
Supply Air Temp., °F (TS)
ERN
EXT

AL

Room Design Temp., °F (TR)


Orien-
Item TR-TS = ΔTS
tation
Supply CFM = NRS / 1.1 x ΔTS
COOLING EQUIPMEN
Glass
SO LA R

Glass S
NRS 1,248.48 % Re
Glass E
% Return Duct Gain 24.97
Glass W
Vs -
Total above 1,273.46 %
People No. 0 % Safety Factor 191.02 L
COOLINGLOADS

Lights SENS (Equipt.) 1,464.48


INTERNAL

3.41 x Total Equipt. Load = SENS (Equipt.) + LAT ( Eq

Motors 3600 x Total Equipt. Load = 2


Elect'l. Eqpt. 3.41 x Tonnage = Total BTU/HR ÷ 12000 =

Gas Eqpt. No. x


Misc. --------------------------------------------------------------
HUMIDIFICATIO
(INTERNAL LOADS) 1,471.48
INFILT.

QL = 4840 x _18 SUM


x CFMOA _0.0108 ΔW
Steam/Vapour Required
QS = 1.10 x 18 CFMOA x _16 ΔT 316.80 M = 60/v x CFMOA x
Use minimum one air change per hour. IS
Where : CFMOA = Outside Air CFM = ------------------------------------------------------------------------------------------------------- O
= ELECTRIC HEATER SIZING 9001:
R
o
Total Heating Qs x Safety Factor
o 2008
m EL. HTR. = ----------------------------------------------

3413
EL. HTR. = KW
V
----------------------------------------------------------------------------------------
o
l It is recommended to use ASHRAE tables with this form.
u
m
e
x

POLYTECHNICREPUBLIC
A
ir
C
h
a

OF GR P
n
g

AD
e
s
p
e
r
H
R
/

S
6
0

SCHOOLURNCAMARINES
v =
S
p
e

ABUA,
c
i
fi

SUR
c
A
ir
V
o
l
u
m
e
Te .
A m as 9
Or r p. s 4 575
e
ie a Di Q
n- , ff.

O
S

53. (Co BT
00 rre U/
Gl S
Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 Ite as 0. 4 0.
tati cte HR
LOAD CALCULAIONS SHEET s 94 0 58
m on FT²U

S
Latitude DB daily range 20 °F Day June d) .
18 Gl
W .0 as 0.
Su all N 0 Tem Q s E 94
p. S
m M 1
m arc Sh 6

er
. 0
h ee 0

M
Wall S 0
.
20, t Gl
on Da 20 No as 9 4 0.
th r 13° 18 N. of
te- 27' 4 s W 4 6 29
6 SUM
2 3 People No. _0 x 255
W in 8. 35 .

COOLINGLOADS
DB °F WB °F RH W DB °F W lb Client Job Number _______ W 2 0.4 .0 8 Lights 3.41 x 2 Wt. x
Outside 82 0.0210 74
vapor per Dream House all E 0 70 0 9

N
94 Hallway

INTER NAL
:

lb dry
Building Name : Joeffrey D. Room by : M
Inside 78 0.0102 air Computed by : Engr. Checked JDB
COOLING

50% 72
ot
12
or 360
W .0 s 0x HP
HALLWAY

all W 0

IO
Ap
pr
Di Elec
ff 0.0 ov Ro t'l.
er 1 10 ed C
Eqp 3.4 Wt L

T
. 6 82 by : of
t. 1 x . x F -

S Ga SH

LOADS
H Gl 16

NDU C
s
G as Δ .0 Eq N G
= s T 0 pt. o. x x CLF
Se SIZI
ns Pa
NG
ibl rti Mis
e tio Δ c.
H n T16
ea (
= 1 I
t S
G e 5 N
ai ns 2 7 T
n ib D 1. . E
(p le oo 0 Δ 9 R

COOLING
0.4
er L N

CO
r 0 70 T16 2
ite o A
mQ a 1
Floor ΔT L
) S d ,

EXTER
S UM (CONDUCTION)

NAL
LH C Item Shade Coef. CLF
L 1
G O 5
O Infilt O
= M .& A 5
La L
I Ori a Vent D .
te .
nt N en- x. SU S 6
He G M) 5
at Are
Ga = ( H a,
Lat S Tot
in EA S QS = _18 CFM x _16 Δ
(p en e tati FT al
TI H 1. OA T
er t n on ²
N G 1
ite Lo .
m) QL ad ) G Gl N 0 4 0. 0
x
IS
= O
Q
48 CFM 9001:
L 40 x _18 OA

2008
COOLING LOAD SUMMARY
Sensible (BTU/HR) Latent (BTU/HR)
QS' & QL' → 940.89
VS Supply Duct .…..% Leak + ..….% Heat Gain 18.82
T.

= CF
Blower Motor Input ….………%
1. MO Net Room Sensible (NRS) (Total of above)
10 A x Net Room Latent (NRL) (Total of above) 959.71
x Total Load = NRS + NRL

POLYTECHNICREPUBLIC
= 3,095.85
VEN

CFM SHR = NRS / Total Load 0.700


V 48
L 40 x OA
Supply Air Temp., °F (TS)
Room Design Temp., °F (T )
TR-TS = ΔTS 25.00

OF GR P
Supply CFM = NRS / 1.1 x ΔTS 78
EQUIPMENT LOAD

AD
NRL 959.71
% Return Duct 19.19
NRS 2,136.15 V
L
% Return Duct 42.72
Total above 978.90
Vs
% Safety Factor 146.84
Total above 2,178.87
LAT (Equipt.) 1,125.74
% Safety Factor 326.83
Total Equipt. Load = SENS (Equipt.) LAT (Equipt.)

S
SENS (Equipt.) 2,505.70

SCHOOLURNCAMARINES
Total Equipt. Load = 3,631.44 BTU/HR
Tonnage = Total BTU/HR ÷ 12000 = 0.30 TR

ABUA,
-------------------------------------------------------------------------------------------------------
HUMIDIFICATION
Steam/Vapour Required = M lb/hr
M = 60/v x CFMOA x ΔW

SUR
Where : CFMOA = Outside Air CFM = CFM
=Room Volume x Air Changes per HR / 60
v = Specific Air Volume
Use minimum one air change per hour.
-------------------------------------------------------------------------------------------------------

ELECTRIC HEATER
-
Total Heating Qs x Safety Factor
EL. HTR. =
--------------------------------------------3413

EL. HTR. = KW
-------------------------------------------------------------------------------------------------------
It is recommended to use ASHRAE tables with this form.
IS
O
9001:

2008
Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 LOAD CALCULATIONS SHEET
COOLING LOAD SUMMARY
Latitude 13° -27' N DB daily range 20 °F Day June Sensible (BTU/HR) Latent (BTU/HR)
Summer Month Winter Date March 20, 2018 Sheet No. of QS' & QL' → 2,890.31 940.89
DB °F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 57.81 18.82
Outside 94 82 0.0210 74 vapor per Building Name : Dream House Room :
Mechanical Room Blower Motor Input ….………%
Inside 78 50% 0.0102 72 lb dry air Computed by : Engr. Joeffrey D. Bustinera Checked by : JDB Net Room Sensible (NRS) (Total of above) 2,948.12
Differ. 16 0.0108 2 Approved by : Net Room Latent (NRL) (Total of above) 959.71
SHG = Sensible Heat Gain (per item) QS = Sensible Load Total Load NRS + NRL 3,907.83

POLYTECHNICREPUBLIC
=

LHG = Latent Heat Gain (per item) QL = Latent Load COOLING (Sen.) HEATING SHR = NRS / Total Load 0.800
Q
Orien- Area, Temp. Diff. S Supply Air Temp., °F (TS) 57.00
Item U
tation FT² (Corrected) BTU/HR. Room Design Temp., °F (TR) 78.00
Wall N 18.00 TR-TS = ΔTS 21.00
Wall S 82.33 0.470 16.00 619.12 Supply CFM NRS / 1.1 x ΔTS 128

OF GR P
=
MECHANICALROOM

Wall E 35.00 Temp. QS COOLING EQUIPMENT LOAD


NDU C T I O N

AD
Wall 618.60 Diff. BTU/HR. 959.71
W 109.68 0.470 12.00 NRL
Roof NRS 2,948.12 % Return Duct Gain 19.19
COOLIN LOADS

V
Glass 21.52 1.040 ΔT 16.00 358.09 % Return Duct Gain 58.96 L

Partition ΔT 16 - Vs Total above 978.90


CO

Door 16.07 0.470 ΔT 16 120.86 Total above 3,007.08 % Safety Factor 146.84
Floor ΔT 16 - % Safety Factor 451.06 LAT (Equipt.) 1,125.74
3,458 . 14
EXTERN

SUM (CONDUCTION) 1,716.67 - = SENS (Equipt .) + LAT (Equipt.)


AL

TotalSENSEquipt(Equipt.Load.)

S
-
Item Orien- Area,
Sha de Coef.
Max. CLF Total Equipt. Load = 4,583.88 BTU/HR

SCHOOLURNCAMARINES
-
tation FT² SHG Tonnage = Total BTU/HR ÷ 12000 = 0.38 TR

Infilt. & Vent.


Glass 0.94 45 0.75
S LA R

N --- ---- ------------ ---- ------------ ---- ------------ ---- ------------ ---- ------------ ---- ------------ ----

0.94 40 -

ABUA,
Glass S 0.58 Total HUMIDIFICATION
O

Glass E 0.94 46 0.31 - COOLING (Latent) Steam/Vapour Required = M lb/hr

SUR
Glass W 21.52 0.94 46 0.29 269.85 QL (BTU/HR) M = 60/v x CFMOA x ΔW

SUM (SOLAR) 269.85 No. x LHG = QL Where : CFMOA = Outside Air CFM = CFM
L COOLING
INTERNA

People No. _0 x 255 SHG X _0.85 0 315


LOADS

CLF - = Room Volume x Air Changes per HR / 60


Gas Eqpt. No. x SHG x CLF ELECTRIC HEATER SIZING

Lights 3.41 x 2 Wt. x 86.07 x 1 Bal. & use factor 586.99 v = Specific Air Volume
Motors 3600 x HP Use minimum one air change per hour.
Elect'l. Eqpt. 3.41 x Wt. x CLF - -------------------------------------------------------------------------------------------------------

Misc. -
SUM (INTERNAL LOADS) 586.99 Total Heating Qs x Safety Factor
Q
S = 1.10 x _18 CFMOA x _16 ΔT 316.80 EL. HTR. = ----------------------------------------------

QL = 4840 x _18 CFMOA x _0.0108 ΔW 3413


Q Q
ROOM SUBTOTAL S' 2,890.31 L' EL. HTR. = KW
T.

VS = 1.10 x CFMOA x ΔT ----- ------------ ------- ------------ ------- ------------ ------- ------------ ------- ------------ ----------

VL = 4840 x ΔW It is recommended to use ASHRAE tables with this form.


VEN

CFMOA x 0.0108
IS

LOADCALCULATION FORSECOND FLOOR


O
9001:

2008

Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 COOLING LOAD SUMMARY
LOAD CALCULATIONS SHEET
Latitude 13° - 27' N DB daily range 20 °F Day June Sensible (BTU/HR) Latent (BTU/HR)
Summer Month Winte r Date March 20, 2018 Sheet No. of QS' & QL' → 7,903.60 1,570.89
DB °F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 158.07 31.42
Outside 94 82 0.0210 74 vapor per Building Name : Dream House Room : Family Living Room Blower Motor Input ….………%
Inside 78 50% 0.0102 72 lb dry air Computed by : Engr. Joeffrey D. Bustinera Checked by : JDB Net Room Sensible (NRS) (Total of above) 8,061.68

POLYTECHNICREPUBLIC
Differ. 16 0.0108 2 Approved by : Net Room Latent (NRL) (Total of above) 1,602.31
SHG = Sensible Heat Gain (per item) Area, Q = Sensible Load Q SupplyTotalLoadAir Temp=.,NRS°F (T+S) NRL 9,66357..0098
Item Orien- US Temp. Diff. S
SHR = NRS / Total Load 0.800
LHG = Latent Heat Gain (per item) QL = Latent Load COOLING (Sen.) HEATING
tation FT² (Corrected) BTU/HR. Room Design Temp., °F (TR) 78.00

Wall N 189.00 18.00 1,598.94


FAMILYLIVING ROOM

OF GR P
0.470 TR-TS = ΔTS 21.00
Wall S 16.00 Supply CFM = NRS / 1.1 x ΔTS 349
TIO N

AD
Wall E 114.80 0.470 35.00 1,888.46 COOLING EQUIPMENT LOAD
Wall W 12.00 Diff. BTU/HR. NRS 8,061.68 NRL 1,602.31
AD
LO

ND
UC
S

Temp. QS % Return Duct Gain 161.23


Vs % Return Duct Gain 32.05
Roof 144.75 0.160 78.00 1,806.48
COOLING

Total above 8,222.91


V
% Safety Factor 1,233.44 L
CO

Glass 24.2 1.040 ΔT 16.00 402.69


SENS (Equipt.) 9,456.34
EXTERN

S
Door ΔT 16
AL

- Total above 1,634.35


Partition ΔT 16

SCHOOLURNCAMARINES
% Safety Factor 245.15
LAT (Equipt.) 1,879.51
Floor ΔT 16 - -
Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)
SUM (CONDUCTION) 5,696.57 -

ABUA,
-
Total Equipt. Load = 11,335.85 BTU/HR
Orien- Area, Max. Infilt. & Vent.
Item Shade Coef. CLF
0.9
Total

SUR
Tonnage = Total BTU/HR ÷ 12000 = 4
tation FT² SHG TR

Glass N 24.20 0.94 45 0.75 767.75 -------------------------------------------------------------------------------------------------------


SOLA R

HUMIDIFICATION
Glass S 0.94 40 0.58 -

Steam/Vapour Required = M lb/hr


Glass E 0.94 46 0.31 - COOLING (Latent)

M = 60/v x CFMOA x ΔW
Glass W 0.94 46 0.29 QL (BTU/HR)
COOLINGLOADS
INTERNAL

Where : CFMOA = Outside Air CFM = CFM


No. x SUM (SOLAR) 767.75 No. x LHG = QL
Gas Eqpt. SHG x CLF -
= Room Volume x Air Changes per HR / 60
People No. _2 x 316 SHG X _0.85 CLF 535.50 2 315 630.00
v = Specific Air Volume
Lights 3.41 x 2 Wt. x 244 x 1 Bal. & use factor 586.99
Use minimum one air change per hour.
Motors 3600 x HP
-------------------------------------------------------------------------------------------------------
Elect'l. Eqpt. 3.41 x Wt. x CLF -
ELECTRIC HEATER SIZING

Misc. -

SUM (INTERNAL LOADS)


QS = 1.10 x _18 CFMOA x _16 ΔT
QL = 4840 x _18 CFMOA x _0.0108 ΔW
ROOM SUBTOTAL
149,122.00
Total Heating Qs x Safety Factor
316.80 EL. HTR. =

VEN T. INFILT.
----------------------------------------------

3413
Q
S' 7,903.60 QL' EL. HTR. = KW
VS = 1.10 x CFMOA x ΔT -------------------------------------------------------------------------------------------------------

VL = 4840 x CFMOA x 0.0108 ΔW It is recommended to use ASHRAE tables with this form.
IS
O
9001:

2008
Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 LOAD CALCULATIONS SHEET COOLING LOAD SUMMARY

Latitude 13° - 27' N DB daily range 20 °F Day June


Summer Month Winter Date March 20, 2018 Sensible (BTU/HR) Latent (BTU/HR)
Q &Q →
Sheet No. of S' L' 2,382.08 940.89
DB °F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 47.64 18.82
Outside 94 82 0.0210 74 vapor per Building Name : Dream House Room : Hallway 2 Blower Motor Input ….………%

POLYTECHNICREPUBLIC
Inside 78 50% 0.0102 72 lb dry air Computed by : Engr. Joeffrey D. Bustinera Checked by : JDB
Net Room Sensible (NRS) (Total of above) 2,429.72

Differ. 16 0.0108 2 Approved by : Net Room Latent (NRL) (Total of above) 959.71
SHG = Sensible Heat Gain (per item) QS = Sensible Load Total Load = NRS + NRL 3,389.43
LHG = Latent Heat Gain (per item) QL = Latent Load COOLING (Sen.) HEATING SHR = NRS / Total Load 0.700
Orien- Area, Temp. Diff. QS Supply Air Temp., °F (TS) 53.00

OF GR P
Item U Temp. QS
tation FT² (Corrected) BTU/HR. Diff. BTU/HR. Room Design Temp., °F (TR) 78.00

AD
Wall N 18.00 TR-TS = ΔTS 26.00
Wall S 16.00
Supply CFM 87
HALLWAY

= NRS / 1.1 x ΔTS


Wall E 35.00
NRS 2,429.72
COOLING EQUIPMENT LOAD
NDU C T I O N

Wall W 12.00 % Return Duct Gain 48.59 NRL 959.71


Roof 96.83 0.160 78.00 1,206.44 Vs % Return Duct Gain 19.19
COOLIN LOAD

Glass ΔT 16.00 - Total above 2,478.32 VL


S

Partition ΔT 16 % Safety Factor 371.75 Total above 978.90


CO

- % Safety Factor 146.84

S
SENS (Equipt.) 2,850.08
G

Door ΔT 16
- LAT (Equipt.) 1,125.74

SCHOOLURNCAMARINES
Floor ΔT 16 -
EXTERNA

S UM (CONDUCTION) 1,208.44 Infilt. & Vent. Total Equipt. Load =


SENS (Equipt.) + LAT ( Equipt.)
Item Shade Coef. CLF Total
L

Orien- Area, Max.

ABUA,
Total Equipt. Load = 3,975.80 BTU/HR
tation FT² SHG Tonnage = Total BTU/HR ÷ 12000 = 0.33 TR
Glass N 0.94 45 0.75 -------------------------------------------------------------------------------------------------------
SOL A R

SUR
Glass S 0.94 40 0.58 - HUMIDIFICATION

Glass E 0.94 46 0.31 - COOLING (Latent) Steam/Vapour Required = M lb/hr

Glass W 21.52 0.94 46 0.29 269.85 QL (BTU/HR) M = 60/v x CFMOA x ΔW


COOLINGLOADS
INTERNA

SUM (SOLAR) 269.85 No. x LHG = QL Where : CFMOA = Outside Air CFM = CFM
Gas Eqpt. No. x
L

SHG x CLF -

People No. _0 x 316 SHG X _0.85 CLF 0 315 = Room Volume x Air Changes per HR / 60
Lights 3.41 x 2 Wt. x 86.07 x 1 Bal. & use factor 586.99 v = Specific Air Volume
Motors 3600 x HP Use minimum one air change per hour.
Elect'l. Eqpt. 3.41 x Wt. x CLF - -------------------------------------------------------------------------------------------------------
ELECTRIC HEATER SIZING
Misc. -
SUM (INTERNAL LOADS) 586.07 Total Heating Qs x Safety Factor
QS = 1.10 x _18 CFMOA x _16 ΔT 316.80 EL. HTR. = ----------------------------------------------

QL = 4840 x _18 CFMOA x _0.0108 ΔW 3413


Q Q EL. HTR. = KW
ROOM SUBTOTAL S' 2.382.08 L'
T

INFI LT .
.

VS = 1.10 x CFMOA x ΔT -------------------------------------------------------------------------------------------------------


It is recommended to use ASHRAE tables with this form.
N
V
E

VL = 4840 x CFMOA x 0.0108 ΔW


IS
O
9001:

2008

Design conditions for Baao, Camarines Sur, Hour 14:00 LOAD CALCULATIONS COOLING LOAD SUMMARY
Philippines SHEET

Sensible (BTU/HR) Latent (BTU/HR)


Latitude 13° - 27' N DB daily range 20 °F Day June
Q &Q →
DB °F WB °F RH W DB °F W W in lb Client March 20, 2018 Sheet No. of S' L' 8,266.98 1,450.89
Summer Month Winter
Outside 94 Date82 0.0210 Building Name : Dream Job Number Supply Duct .…..% Leak + ….% Heat Gain.. 165.34 29.02
74
vapor per Room : Hallway 2 Blower Motor Input ….………%

POLYTECHNICREPUBLIC
Inside 78 50% 0.0102 72 lb dry air Computed by Engr. Joeffrey D. Bustinera Checked by JDB
Net Room Sensible (NRS) (Total of above)
8,432.32

Differ. 16 0.0108 2
Approved by Net Room Latent (NRL) (Total of above) 1,479.91

SHG = Sensible Heat Gain (per item) QS = Sensible Load Total Load = NRS + NRL 9,912. 23

OF GR P
LHG = Latent Heat Gain (per item) QL = Latent Load COOLING (Sen.) HEATING SHR = NRS / Total Load 0.900

AD
Orien- Area, Temp. Diff. QS Temp. QS Supply Air Temp., °F (TS) 57.00
Item U
tation FT² Diff. BTU/HR.
BEDROOM2

Wall N 65.80 0.470 (Corrected) BTU/HR. Room Design Temp., °F (TR) 78.00
Wall S 18.00 554.98 TR-TS = ΔTS 21.00
ION

16.00 Supply CFM = NRS / 1.1 x ΔTS 365


NRS 8,432.32
LOAD

2,029.93 COOLING EQUIPMENT LOAD


Wall 123.40 0.470 35.00
NDUC

E
S

% Return Duct 168.65


NRL 1,479.91
Wall W 12.00 2,716.89 Vs % Return Duct Gain 29.60

S
Roof 217.86 0.160 78.00 - Total above 8,600.97
COOLI

CO

402.69 VL
NG

SCHOOLURNCAMARINES
Partition ΔT

Glass 24.20 1.040 ΔT 16.00 - % Safety Factor 1,290.15


Total above 1,509.51
EXTERN

- SENS (Equipt.) 9,891.11 % Safety Factor 226.43


Door ΔT 16
- LAT (Equipt.) 1,735.93
AL

Infilt. & Vent.


Floor ΔT 16 5,706.49 Total Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)

ABUA,
SUM (CONDUCTION)
Total Equipt. Load = 11,627.05 BTU/HR
Item Orien- Area, Shade Coef. Max. CLF
Tonnage = Total BTU/HR ÷ 12000 = 0.97 TR
S O LA R

tation FT² SHG


---------------------------------------------------------------------------------------------------

SUR
Glass N 0.94 45 0.75 HUMIDIFICATION
-
Glass S 0.94 40 0.58
324.39 COOLING (Latent) Steam/Vapour Required = M lb/hr
Glass E 24.20 0.94 46 0.31
QL (BTU/HR) M = 60/v x CFMOA x ΔW
Glass W 0.94 46 0.29 324.39 No. x LHG = Q
L Where : CFMOA = Outside Air CFM = CFM
SUM (SOLAR) 433.50 2 255 510. = Room Volume x Air Changes per HR / 60
00

People No. _2 255 SHG X _0.85 CLF


COOLINGLOADS

1,485.81 v = Specific Air Volume


x

Lights 3.41 x Wt. x 217.86 x 1 Bal. & use factor


INTERN

2
Use minimum one air change per hour.
AL

Motors 3600 x HP
- -------------------------------------------------------------------------------------------------------
Elect'l. Eqpt.
- ELECTRIC HEATER
Gas Eqpt. No. x SHG x CLF -
SIZING Misc.
1,919.31 Total Heating Qs x Safety Factor
SUM (INTERNAL
LOADS) 316.80 EL. HTR. = ----------------------------------------------

QS = 1.10 x _18 CFMOA x _16 ΔT 3413


Q Q
8,266.98 EL. HTR. = KW
NT.
INFILT.

S' L'
VE

QL = 4840 x _18 CFMOA x _0.0108 ΔW


VL = 4840 x CFMOA x 0.0108 ΔW ------------------------------------------------------------------
VS
= 1.10 x CFMOA x ΔT It is recommended to use ASHRAE tables with this form.
Design conditions for Baao, Camarines Sur, Hour 14:00 LOAD CALCULATIONS COOLING LOAD SUMMARY
Philippines SHEET

Latitude 13° - 27' N DB daily range 20 °F Day June Sensible (BTU/HR) Latent (BTU/HR)
Summer Month Winter March 20, 2018 Sheet No. of QS' & QL' → 4,056.06 1,450.89
Date

DB °F WB °F RH W DB °F W W in lb Client _ Job Number Supply Duct .…..% Leak + ..….% Heat Gain 81. 10
29.02

Outside 94 82 0.0210 74 vapor per Building Dream House Room :


BedRoom 3 Blower Motor Input ….………%
Name :

Inside 78 50% 0.0102 72 lb dry air Computed by Engr. Joeffrey D. Bustinera Checked JDB Net Room Sensible (NRS) (Total of above) 4,136. 16

: by :

Differ. 16 0.0108 2 Approved by : Net Room Latent (NRL) (Total of above) 1,479. 91

SHG = Sensible Heat Gain (per item) QS = Sensible Load Total Load = NRS + NRL 5,616. 91
LHG = Latent Heat Gain (per item) QL = Latent Load COOLING (Sen.) HEATING SHR = NRS / Total Load 0.700

Orien- Area, Temp. Diff. QS Temp. QS Supply Air Temp., °F (TS) 53.00
Item U
Diff. BTU/HR.
tation FT² (Corrected) Room Design Temp., °F (TR)
BTU/HR.
78.00

Wall 18.00 TR-TS = ΔTS 25.00


N

Wall S 16.00 Supply CFM = NRS / 1.1 x ΔTS


DS U C I O

150
Wall E 35.00 -
COOLING EQUIPMENT
EXTERNA COOLING LOAD

- LOAD
T

-
418.49 NRL 1,479.91
Wall W 74.20 0.47 12.00 Infilt. &
CON

Total
Roof 112.96 0.160 1,409.74 % Return Duct Gain 29.60
78.00
NRS 4,136.16 V
402.69
L

L
Glass 24.20 1.040 ΔT 16.00 % Return Duct 82.72
Vs
Total above 4,218.89 Total above 1,509.51
Partition ΔT 16
Door ΔT 16 % Safety Factor 632.83 % Safety Factor 226.43
Floor ΔT 16 - SENS (Equipt.) 4,815.72 LAT (Equipt.) 1,735.93
SUM (CONDUCTION) Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)
2,230.92 Total Equipt. Load = 6,587.65 BTU/HR
Tonnage = Total BTU/HR ÷ 12000 = 0.56 TR

Item Orien- Area, Shade Coef. Max. CLF

tation FT² SHG


Glass Glass 0.94
Glass N
SO L A

Glass S 0.94
IS
O
E 45 0.75
9001:
0.94 ----------------------------------------------------------
W ---------------------------------------------
25.20 40 0.58 -
2008
0.94 HUMIDIFICATION
46 0.31
COOLING (Latent)
Steam/Vapour Required = M lb/hr
46 0.29
QL (BTU/HR)
M = 60/v x CFMOA x ΔW
SUM (SOLAR) 303.46 No. x LHG = QL Where : CFMOA = Outside Air CFM = CFM

POLYTECHNICREPUBLIC
433.50 2 255 510.00 = Room Volume x Air Changes per HR /
People No. _2 x 255 SHG X _0.85 CLF
770.39 60 v = Specific Air Volume
Use minimum one air change per hour.
Lights 3.41 x 2 Wt. x 112.96 x 1 Bal. & use factor
- -------------------------------------------------------------------------------------------------------

- ELECTRIC HEATER SIZING

OF
-
Motors 3600 x HP

Elect'l. Eqpt.

Gas Eqpt. No. x SHG x CLF

Misc.

SUM (INTERNAL
LOADS) QS = 1.10 x _18 CFMOA x _16 C
1,203.39 Total Heating Qs x Safety
VEN T. INFILT.
BEDROOM3

ΔT 316.80 EL. HTR. = -------------------------------------------- THE


Q

P
L = 4840x _18 CFMOA x _0.0108 ΔW 3413
ROOM SUBTOTAL QS' 4,056.06 QL' EL. HTR. = KW
VS = 1.10 x CFMOA x ΔT -------------------------------------------------------------------------------------------------------
VL = 4840x CFMOA x 0.0108 ΔW It is recommended to use ASHRAE tables with this form.

SCHOOLURNCAMARINES
ABUA,
SUR
IS
O
9001:

2008
Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 LOAD CALCULATIONS SHEET COOLING LOAD SUMMARY

Latitude 13° - 27' N DB daily range 20 °F Day June Sensible (BTU/HR) Latent (BTU/HR)
Summer Month Winter Date March 20, 2018 Sheet No. of Q &Q →
S' L' 6,447.88 1,450.89
DB °F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 128.96 29.02

REPUBLIC
Outside 94 82 0.0210 74 vapor per Building Name : Dream House Room :
BedRoom 4 Blower Motor Input ….………%

Inside 78 50% 0.0102 72 lb dry air Computed by : Engr. Joeffrey D. Bustinera Checked by : JDB
Net Room Sensible (NRS) (Total of above) 6,576.84 GRADUATE

Differ. 16 0.0108 2 Approved by :


Net Room Latent (NRL) (Total of above) 1,479.91 POLYTECHNICOF

SHG = Sensible Heat Gain (per item) QS = Sensible Load


C
Total Load = NRS + NRL 8,056.74
LHG = Latent Heat Gain (per item) QL = Latent Load COOLING (Sen.) HEATING SHR = NRS / Total Load 0.800 THE
Orien- Area, Temp. Diff. QS Temp.

SCHOOLAMARINESCOLLEGESPHILIPPINES
QS Supply Air Temp., °F (TS) 57.00
Item U
BEDROOM4

Diff. BTU/HR.
tation FT² (Corrected) BTU/HR. Room Design Temp., °F (TR) 78.00

Wall N 90.60 0.470 18.00 766.48 TR-TS = ΔTS 21.00

SUR
Wall S 16.00 Supply CFM = NRS / 1.1 x ΔTS 285
CO ND CTIO N

Wall E 35.00 COOLING EQUIPMENT LOAD


-
EXTERNA COOLING LOADS

-
Wall W 90.60 0.470 12.00 510.98 NRL 1,479.91

N
-

ABUACAMARINES
Infilt. & Vent.
Roof 131.79 0.160 78.00 1,644.74 % Return Duct Gain 29.60
Total 6,576.84
NRS

,
Glass 48.40 1.040 ΔT 16.00 805.38 % Return Duct Gain 131.54 VL

SUR
Vs
Total above 6,708.37
L

Partition ΔT 16 Total above 1,509.51


Door ΔT 16 % Safety Factor 1,006.26
% Safety Factor 226.43
Floor ΔT 16 - SENS (Equipt.) 7,714.63
LAT (Equipt.) 1,735.93

SUM (CONDUCTION) 3,727.58

ING LOADS
TERNAL
Orien- Area, Max.
Item Shade Coef. CLF

tation FT² SHG


R

Glass N 24.20 0.94 45 0.75 767.75


SO LA

Glass S 0.94 40 0.58 -

Glass E 0.94 46 0.31 COOLING (Latent)

Glass W 24.20 0.94 46 0.29 303.46 QL (BTU/HR)

SUM (SOLAR) 303.46 No. x LHG = QL


Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)

Total Equipt. Load = 9,450.56 BTU/HR

Tonnage = Total BTU/HR ÷ 12000 = 0.79 TR


-------------------------------------------------------------------------------------------------------

HUMIDIFICATION

Steam/Vapour Required = M lb/hr

M = 60/v x CFMOA x ΔW

Where : CFMOA = Outside Air CFM = CFM


People No. _2 x 255 SHG X _0.85 CLF 433.50 2 255 510.00 = Room Volume x Air Changes per HR / 60
Lights 3.41 x 2 Wt. x 131.79 x 1 Bal. & use factor 898.80 v = Specific Air Volume
Motors 3600 x HP Use minimum one air change per hour.
Elect'l. Eqpt. - -------------------------------------------------------------------------------------------------------

Gas Eqpt. No. x SHG x CLF - ELECTRIC HEATER SIZING


Misc. -
SUM (INTERNAL LOADS) 1,332.3 Total Heating Qs x Safety Factor
0
QS = 1.10 x _18 CFMOA x _16 ΔT EL. HTR. = ----------------------------------------------
316.80
VEN T. INFILT.

QL = 4840 x _18 CFMOA x _0.0108 ΔW 3413


ROOM SUBTOTAL Q 6,447.88 QL' EL. HTR. = KW
S'
VS = 1.10 x CFMOA x ΔT -------------------------------------------------------------------------------------------------------
VL = 4840 x CFMOA x 0.0108 ΔW It is recommended to use ASHRAE tables with this form.
IS
O
9001:

2008
Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 COOLING LOAD SUMMARY
LOAD CALCULATIONS SHEET

Latitude 13° - 27' N DB daily range 20 °F Day June Sensible (BTU/HR) Latent (BTU/HR)
Summer Month Winter Date Q &Q
March 20, 2018 Sheet No. of S' L' → 7,163.50 1,450.89

DB °F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 143.07 29.02

POLYTECHNICREPUBLIC
Outside 94 82 0.0210 74 vapor per Building Name : Dream House Room : MasterBedroom Blower Motor Input ….………%
Inside 78 50% 0.0102 72 lb dry air Computed by : Engr. Joeffrey D. Bustinera Checked by : JDB Net Room Sensible (NRS) (Total of above) 7,296.57
Differ. 16 0.0108 2 Approved by : Net Room Latent (NRL) (Total of above) 1,479.91
SHG = Sensible Heat Gain (per item) QS = Sensible Load Total Load = NRS + NRL 8,776.48
LHG = Latent Heat Gain (per item) QL = Latent Load COOLING (Sen.) HEATING SHR = NRS / Total Load 0.800

OF GR P
Orien- Area, Temp. Diff.
Item U QS Temp. QS Supply Air Temp., °F (TS) 57.00
MASTERBEDROOM

Diff. BTU/HR.

AD
tation FT² (Corrected)
BTU/HR. Room Design Temp., °F (TR) 78.00

Wall N 79.74 0.470 18.00 674.60 TR-TS = ΔTS 21.00

Wall S 147.6 0.47 16.00


1,109.95 Supply CFM = NRS / 1.1 x ΔTS 316
CO N DUCTIO N

Wall E 35.00 -
LOADS

COOLING EQUIPMENT LOAD

S
-

SCHOOLURNCAMARINES
Wall W 12.00 -
COOLI

NRL 1,479.91
NG

Roof 193.65 0.160 78.00 Infilt. & Vent.


EXTERN

2.416.75 % Return Duct Gain 29.60


Total
AL

ABUA,
Glass 12.10 1.040 ΔT 16.00
201.34 VL

Partition ΔT 16 NRS 7,298.57 Total above 1,509.51

SUR
% Return Duct Gain 145.93

Vs
Door 39.36 0.470 ΔT 16
295.99 Total above 7,442.50 % Safety Factor 226.43
% Safety Factor1,116.38
Floor ΔT 16
- SENS (Equipt.) 8,558.88 LAT (Equipt.) 1,735.93
SUM (CONDUCTION) 4,698.64 Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)

Orien- Area, Max. Total Equipt. Load = 10,294.81 BTU/HR


Item Shade Coef. CLF

tation FT² SHG Tonnage = Total BTU/HR ÷ 12000 = 0.86 TR


Glass N 12.10 0.94 45 0.75
383.87
-------------------------------------------------------------------------------------------------------
LA R

Glass S 0.94 40 0.58


- HUMIDIFICATION
Glass E 46 0.31
SO

0.94
COOLING (Latent) Steam/Vapour Required = M lb/hr
Glass W 0.94 46 0.29 QL (BTU/HR) M = 60/v x CFMOA x ΔW

SUM (SOLAR) 383.87 No. x LHG = QL Where : CFMOA = Outside Air CFM = CFM
= Room Volume x Air Changes per HR / 60
v = Specific Air Volume
COOLING LOADS

Use minimum one air change per hour.


INTERNAL
People No. _2 x 255 SHG X _0.85 CLF 433.50 2 255 510.00

Lights 3.41 x 2 Wt. x 193.65 x 1 Bal. & use factor 1,320.69

Motors 3600 x HP
Elect'l. Eqpt. - -------------------------------------------------------------------------------------------------------

Gas Eqpt. No. x SHG x CLF - ELECTRIC HEATER SIZING


Misc. -
SUM (INTERNAL LOADS) 1,754.1 Total Heating Qs x Safety Factor
9
QS = 1.10 x _18 CFMOA x _16 ΔT EL. HTR. = ----------------------------------------------
316.80
QL = 4840 x _18 CFMOA x _0.0108 ΔW 3413
Q
ROOM SUBTOTAL S' 7,163.50 QL' EL. HTR. = KW

VS = 1.10 x CFMOA x ΔT - - - - - - - - - - - - - - - - -----------------------------------------------------------------------


VEN T.

VL = 4840 x CFMOA x 0.0108 ΔW It is recommended to use ASHRAE tables with this form.
IS
O
9001:

2008
Design conditions for Baao, Camarines Sur, Philippines Hour 14:00 COOLING LOAD SUMMARY
LOAD CALCULATIONS SHEET

Latitude 13° - 27' N DB daily range 20 °F Day June


Summer Month Winter Date March 20, 2018 Sensible (BTU/HR) Latent (BTU/HR)
Sheet No. of Q &Q →
S' L' 3,144.03 940.89
DB °F WB °F RH W DB °F W W in lb Client Job Number
Supply Duct .…..% Leak + ..….% Heat Gain 62.88 18.82
Outside 94 82 0.0210 74 vapor per Building Name : Dream House Room : Toilet 2

R
Inside 78 50% 0.0102 72 lb dry air Computed by : Engr. Joeffrey D. Bustinera Checked by : JDB Blower Motor Input ….………%
Net Room Sensible (NRS) (Total of above) 3,206.91

EPUBLICOF
Differ. 16 0.0108 2 Approved by Net Room Latent (NRL) (Total of above) 959.71
SHG = Sensible Heat Gain (per item) : Total Load = NRS + NRL 4,166.62
LHG = Latent Heat Gain (per item) Q S
COOLING (Sen.) HEATING SHR = NRS / Total Load 0.800
Orien- QS Temp. QS
Area, = Sensible Load QL =
Item Supply Air Temp., °F (TS) 57.00
Latent Load Diff. BTU/HR.

GRADUATECPOLYTECHNIC THE
tation FT² BTU/HR.
U Temp. Diff. Room Design Temp., °F (TR) 78.00

AMARINESCOLLEGESPHILIPPINES
Wall N TR-TS = ΔTS 21.00
TOILET2

(Corrected)

18.00
Wall S Supply CFM = NRS / 1.1 x ΔTS 139
NDUC TIO N

16.00
-
Wall E COOLING EQUIPMENT LOAD
EXTERNAL COOLING LOADS

S
35.00 -
Wall W 45.17 0.470 12.00 254.76

SCHOOLURNCAMARINES
Infilt. & Vent. NRL 959.71
Roof 56.46 0.160 78.00 2,069.82 % Return Duct Gain 19.19
CO

Total
NRS 3,206.91
Glass 4.03 1.040 ΔT 16.00 67.06 % Return Duct Gain 64.14 VL

ABUA,
Vs
Total above 3,271.05
Partition ΔT 16 Total above 978.90
% Safety Factor 490.66
Door ΔT 16 % Safety Factor 146.84

SUR
SENS (Equipt.) 3,761.71
Floor ΔT 16 - LAT (Equipt.) 1,125.74

SUM (CONDUCTION) 2,391.64 Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)
Total Equipt. Load = 4,887.45 BTU/HR
Max. Tonnage = Total BTU/HR ÷ 12000 = 0.41 TR
Orien- Area,
Item Shade Coef. CLF

tation FT² SHG


Glass N 0.94 45 0.75 -------------------------------------------------------------------------------------------------------
R

Glass S
SO LA

0.94 40 0.58 - HUMIDIFICATION


Glass E 0.94 46 0.31 COOLING (Latent) Steam/Vapour Required = M lb/hr
Glass W 4.03 0.94 46 0.29 50.53 M = 60/v x CFMOA x ΔW
Q L (BTU/HR)

SUM (SOLAR) No. x LHG =


COOLINGLOADS

50.53 QL
INTERNAL

People No. _0 x 315 SHG X _0.85 CLF 0 255


Lights 3.41 x 2 Wt. x 56.46 x 1 Bal. & use factor 385.06
Motors 3600 x HP
Elect'l. Eqpt. -
Gas Eqpt. No. x SHG x CLF
- Whe
- re :
CFM
OA =
Outsi
de
Air
CFM
=
= Room
Volume x Air
Changes per
HR / 60
v =
Specific
Air
Volume
Use minimum
one air change
per hour.
---------
---------
---------
---------
---------
---------
---------
---------
---------
---------
---------
----
ELECTRIC HEATER
SIZING
385.06 Total Heating Qs x Safety Factor
316.80 EL. HTR. = ----------------------------------------------
QL = 4840 x _18 CFMOA x _0.0108 ΔW 3413
ROOM SUBTOTAL 3,144.03 QL' EL. HTR. = KW
Q S'
VS = 1.10x CFMOA x ΔT -------------------------------------------------------------------------------------------------------
VL = 4840 x CFMOA x 0.0108 ΔW It is recommended to use ASHRAE tables with this form.
Design conditions for Baao, Camarines Sur, Hour 14:00 LOAD CALCULATIONS COOLING LOAD SUMMARY
Philippines SHEET

Latitude DB daily range 20 °F Day Sensible (BTU/HR) Latent (BTU/HR)


13° -27'N June
Q &Q →
Summer Month Winter March 20, 2018 Sheet No. of S' L' 4,921.89 940.89
Date

DB °F WB °F RH W DB °F W W in lb Client Job Number Supply Duct .…..% Leak + ..….% Heat Gain 98.44 18.82

Outside 94 82 0.0210 74 vapor per Building Dream Room : Toilet 3 Blower Motor Input ….………%
Name : House

Inside 78 50% 0.0102 72 lb dry air Computed by Engr. Joeffrey D. Bustinera Checked JDB Net Room Sensible (NRS) (Total of above) 5,020.33
: by :

Differ. 16 0.0108 2 Approved by : Net Room Latent (NRL) (Total of above) 959.71
SHG = Sensible Heat Gain (per item) QS = Sensible Load Total Load = NRS + NRL 5,980.04
LHG = Latent Heat Gain (per item) QL = Latent Load COOLING (Sen.) HEATING SHR = NRS / Total Load 0.800
Item Orien- Area, U Temp. Diff. QS Temp. QS Supply Air Temp., °F (TS) 57.00
Diff. BTU/HR.
tation FT² (Corrected) Room Design Temp., °F (TR) 78.00
BTU/HR.

Wall N 18.00 TR-TS = ΔTS 21.00

Wall S 114.8 0.47 863.30 Supply CFM = NRS / 1.1 x ΔTS 217
DUCT IO

16.00 -
EXTERNAL COOLING LOADS

-
Wall E 35.00 - COOLING EQUIPMENT LOAD
Infilt. & Vent.
CON

Wall W 127.17 0.470 717.24 Total NRL 959.71


Roof 12.00 1,879.74 % Return Duct Gain 19.19
150.62 0.160
78.00

NRS 5,020.33
Glass 4.03 1.040 ΔT 16.00 67.06 VL
% Return Duct 100.41
Vs
Partition ΔT 16 Total above 5,120.74 Total above 978.90
Door ΔT 16 % Safety Factor 768.11 % Safety Factor 146.84
Floor ΔT 16 - SENS (Equipt.) 5,888.85 LAT (Equipt.) 1,125.74
SUM (CONDUCTION) Total Equipt. Load = SENS (Equipt.) + LAT (Equipt.)
3,527.33

Item Orien- Area, Shade Coef. Max. CLF Total Equipt. Load = 7,014.59 BTU/HR

tation FT² SHG Tonnage = Total BTU/HR ÷ 12000 = 0.58 TR


Glass Glass Glass Glass N 0.94
A
SOL
IS
O
S 45 0.75
9001:
0.94 ----------------------------------------------------------
E ---------------------------------------------
0.94 40 0.58 -
2008
W HUMIDIFICATION
4.03 46 0.31
0.94 COOLING (Latent)
Steam/Vapour Required = M lb/hr
46 0.29 50.53
QL (BTU/HR)
M = 60/v x CFMOA x ΔW
SUM (SOLAR) 50.53 No. x LHG = QL Where : CFMOA = Outside Air CFM = CFM

POLYTECHNICREPUBLIC
People No. _0 x 315 SHG X _0.85 CLF 0 255 =Room Volume x Air Changes per HR /
Lights 3.41 x 2 Wt. x 150.62 x 1 Bal. & use factor 1,027.23 60 v = Specific Air Volume
Motors 3600 x HP Use minimum one air change per hour.
Elect'l. Eqpt. - -------------------------------------------------------------------------------------------------------
Gas Eqpt. No. x SHG x CLF - ELECTRIC HEATER SIZING
Misc. -

OF GR P
SUM (INTERNAL

AD
LOADS) QS =1.10 x _18 CFMOA x _16
1,027.23 Total Heating Qs x Safety
ΔT 316.80 EL. HTR. = --------------------------------------------
TOILET3

QL = 4840 x _18 CFMOA x _0.0108 ΔW 3413


VEN T.

4,921.89 QL'
ROOM SUBTOTAL QS' EL. HTR. = KW
VS = 1.10 x CFMOA x ΔT -------------------------------------------------------------------------------------------------------
VL = 4840 x CFMOA x 0.0108 ΔW It is recommended to use ASHRAE tables with this form.

SCHOOLURNCAMARINES
ABUA,
SUR
IS
O
9001:
SUMMARYOFLOAD CALCLATIONINCENTRALIZE TWOSTORY BUILDING
2008

FIRST FLOOR TONNAGE CFM SENS Total LoadTotal CFM DIFFUSER SIZE RECTANGULAR DUCT
Livng Room 0.9 307 8,727.08 10,768 334.08 9" x 9" 9" x 6"
Hallway 0.3 78 2,505.70 3,361.44 84.88 6" x 6" 6" x 6"
Study Room 0.62 194 5,746.78 7,482.72 211.11 9" x 9" 9" x 6"

POLYTECHNICREPUBLIC
Bedroom 1 0.56 162 5,014.13 6,750.07 176.29 9" x 9" 9" x 7"
Maid's Room 0.41 107 3,458.00 4,888.84 116.44 6" x 6" 6" x 6"

OF GR P
Toilet 1 0.22 29 1,464.48 2,590.22 31.56 6" x 6" 6" x 6"

AD
Breakfast Room 0.66 209 6,206.98 7,942.91 227.44 9" x 9" 9" x 9"
Kitchen & Dinning Room 1.14 360 10,682.37 13,692.54 391.76 12" x 12" 12" x 7"
Mechanical Room 0.38 128 3,458.14 4,583.88 139.29 6" x 6" 6" x 6"

S
SECOND FLOOR

SCHOOLURNCAMARINES
Family Living Room 0.94 349 9,456.34 11,335.85 379.79 9" x 9" 9" x 6"
Hallway 0.33 87 2,850.06 3,975.80 94.67 6" x 6" 6" x 6"

ABUA,
Bedroom 2 0.97 365 9,891.11 11,627.05 397.2 12" x 12" 12" x 6"

SUR
Bedroom 3 0.55 150 4,851.72 6,587.65 163.23 9" x 9" 9" x 6"
Bedroom 4 0.79 285 7,714.63 9,450.56 270.97 9" x 9" 9" x 7"
Master Bedroom 0.86 316 8,558.88 10,294.81 343.88 12" x 12" 12" x 7"
Toilet 2 0.41 139 3,761.71 4,887.45 151.26 6" x 6" 6" x 6"
Toilet 3 0.58 217 5,888.85 7,014.59 236.14 9" x 9" 9" x 6"
TOTAL 10.62 3482 100,236.96 127,234 3749.99
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

CHAPTER II

EQUIPMENT SELECTION & PSYCHROMETRIC ANALYSIS

I –DX – TYPE AIR HANDLING UNITS

Units selected are based on CARRIER AIR CONDITIONING CATALOGUE:

Total Load: 127.23 MBH

Sensible: 100.24 MBH

Supply Air Flow: 3,483 CFM = 3,750 CFM

Fresh Air: 120 CFM

Total Tonnage: 10.62 TR

Outside Air: 94℉ DB, 82℉ WB

Inside Design: 78℉ DB, 50% RH


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

Calculation:
a.) Determine the supply air temperature (� ):
��

: By Energy Balance:

��=3,482

CFM
78℉ DB
�� =6303

��
CFM
�=?

��= 120

94℉ DB
CFM

3483(78) + 120(94) = � (3603)


��
�= 75.67 = ��℉ ��

By Ashrae Formula:

�= � + � ��������
� � (� − �)

���� ��� �

120 �

�=78+ 3750 �
(94 − 78)

�= ��. � ����℉ ��( �66 ℉ � �ychometric


Chart)
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

Equipment Selection and/or Cooling Capacity of AHU & ACCU:


@ 94℉ DB & 3750 CFM supply air Entering Air @ 79℉& 66℉
WB

Solve for Total Heating Capacity (THC) for 79℉ DB &66 ℉ WB Entering air @ 79℉ DB and 62℉ WB
Total Heating Capacity @ 79℉& 62 WB

Total Heating Capacity = 137.3 MBH


Total Heating Capacity @ 79℉& 67 WB

Total Heating Capacity = 148.6 MBH


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008
Total Heating Capacity (THC) @ 79℉ DB & 66℉ WB

62 ----------------137.3

66 ------------- THC

67--------------- 148.6

THC = 146.27 MBH


Sensible Heating Capacity @ 79℉ DB & 62 ℉ WB

75 -------------- 109.1

79 -------------- SHC

80 -------------- 124.6

SHC = 121.33 MBH

Sensible Heating Capacity @ 79℉ DB & 67 ℉ WB

75 --------------- 88.4

79 --------------- SHC

80 -------------- 103.9

SHC = 100.60 MBH


Sensible Heating Capacity @ 79℉ DB & 66℉ WB

62 ------------- 121.33

66 ----------
���

67 ------------- 100.60

� = ���. �� �
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

Use model: 38AUD14-40RUA14

ACCU: 38AUDA14A0A5 – 0A0A0

AHU: 40RUAA14AIA5-0AIA0
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

APPENDICES
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

Appendix 1A DUCTING

DESIGN LAYOUT

SCHEMATIC DIAGRAM OF DUCTING DESIGN


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

SCHEMATIC DIAGRAM OF DUCTING DESIGN


REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

Appendix 1B

SUPPLY AIR TERMINAL DEVICES

TALBLE 1
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

Appendix 1C

DUCT SIZER
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

Appendix 1D
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

Appendix 1E
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

APPENDIX 2A

ASHRAE GRP 158 ARTICLES AND TABLES

Article 1
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

TABLE 2
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

TABLE 3
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

TABLE 4
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

TABLE 5
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

TABLE 6
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

TABLE 7
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

TABLE 8
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

TABLE 9
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

TABLE 10
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

ADVANCE AIR CONDITIONING

DESIGN OF
CENTRALIZED AIR CONDITIONING SYSTEM
FOR A TWO STORY RESINDENTIALHOUSE
AT
BAAO, CAMARINES SUR

Prepared by;

Engr. Joeffrey D. Bustinera

2018
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

CENTRALIZED AIR CONDITIONING


SYSTEM FOR A TWO STORY
RESINDENTIAL HOUSE AT
BAAO, CAMARINES SUR

A Design Project
Presented to
The Faculty of Graduate School
Camarines Sur Polytechnic Colleges Nabua,
Camarines Sur, In Partial Fulfillment of the
Requirements for the Degree
Master of Engineering

Prepared by:

Engr. Joeffrey D. Bustinera

2018
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

CURRICULUM VITAE

NAME : JOEFFREY D. BUSTINERA


NATIONALITY : FILIPINO
HOME ADDRESS : Agdangan, Baao, Camarines Sur
Camarines Sur, Philippines
MOBILE PHONE NUMBER : 09294013118
E-Mail ADDRESS : Joeffrey.bustinera@gmail.com
DATE OF BIRTH : 17 May. 1978

EDUCATIONAL QUALIFICATION : B.S. in Mechanical Engineering,


Camarines Sur Polytechnic
Colleges

: 18 units, Methods of Teaching,


University of Northeastern
Philippines

: 30 units, Master of Engineering


Camarines Sur Polytechnic
Colleges

SUMMARY OF WORK EXPERIENCES :


At present faculty member of College of Engineering in Camarines Sur Polytechnic
Colleges, Nabua, Camarines Sur; College of Education and College of Engineering &
Architecture in University of Northeastern Philippines, Iriga City. Thirteen (13) years and nine (9)
months of experience in the field of Construction Management, Design, Mechanical, Structural
and Piping related works in Peñafrancia Sugar Mill, Inc. Eleven(11) months chief mechanic in
United Containers Corporation, Caloocan City. Four (4) months maintenance and engineering
staff in W.L Foods, Valenzuela City.

CAMARINES SUR POLYTECHNIC COLLEGES


San Miguel, Nabua, Camarines Sur
POSITION: Part Time Course Instructor (College of Engineering)
June 21, 2016 up to present
REPUBLIC OF THE PHILIPPINES CAMARINES SUR
POLYTECHNIC COLLEGES NABUA,
CAMARINES SUR
GRADUATE SCHOOL
ISO 9001:2008

UNIVERSITY OF NORTHEASTERN
PHILIPPINES Iriga City
POSITION: Part Time Course Instructor (CEA & College of Education)
June 21, 2016 up to present

COMPANY: PEÑAFRANCIA SUGAR MILL, INC.


Himaao, Pili, Camarines Sur
POSITION: Shift Supervisor (Mill and Boiler
Department)
October 1, 2002 to June 2016

COMPANY : W.L FOOD PRODUCT ( Llano Plant )


Llano Road, Caloocan City
POSITION: Maintenance and Engineering Staff
May 2002–September 2002

COMPANY: UNITED CONTAINERS CORPORATION (TIN BOX)


(Llano Plant) Llano Road, Caloocan City
POSITION: Chief Mechanic
May 2001 – April 2002

You might also like