Professional Documents
Culture Documents
TQ ENVIRONMENTAL PLC
TECHNICAL MANUAL
FINAL DRAWINGS
TQ4400 BALLAST TANK AND UPPER STOOL
GAS DETECTION SYSTEM
This manual must not be copied or reproduced in part without the express written permission of TQ
Environmental PLC. All information contained herein is subject to modification.
Filename: 5799/TM
Issue: 20-05-04
Author: J Tolson
MODIFICATION RECORD
CONTENTS
SECTION DESCRIPTION
1.0 Introduction
1.1 Information Specific to this Application
3.0 Drawings*
1.0 Introduction
The Flammable Gas Detection System supplied to SHINA SHIPPING CO.LTD. for
Hulls 427 / 428 / 434 / , consists of a Twenty point TQ4400 Fixed Gas Detection
Systems for monitoring flammable gases in ballast/water ballast pump trunk and
upper stool spaces.
Please See Section one within the TQ4400 Operating Manual for more details.
1.1 Information Specific to this Application.
TQ4400 TANKSCAN
GAS SAMPLING SYSTEM
OPERATING MANUAL
CONTENTS
1.0 INTRODUCTION 3
2.0 SYSTEM DESCRIPTION 6
2.1 Pneumatics: 6
2.2 Sensors 13
2.3 Control and Display Electronics. 14
2.4 Power Supply Change Over Unit 17
2.5 Watchdog 17
2.6 Outputs. 18
2.7 Technical Specification 19
3.0 OPERATION 20
3.1 System Start-up 20
3.2 Normal Operation 20
3.3 Panel Controls 21
3.4 Alarm Conditions 23
4.0 INSTALLATION 26
4.1 TQ4400 Analysing Unit 26
4.2 Display Unit 26
4.3 Power supply Change Over Unit 26
4.4 Manual Shut Off Valves 26
4.5 Sample Line Equipment 27
4.6 Sample Lines 32
4.7 Cable Segregation 32
5.0 COMMISSIONING 34
5.1 Installation. 34
5.2 System Power Up. 34
5.3 Setting the Flow Rate 35
5.4 Sample Location Set-Up Test 35
5.5 Testing Gas Concentration Alarms 36
5.6 Testing Analysing Unit Cabinet Gas Detector 36
6.0 SCHEDULED MAINTENANCE 37
6.1 System Confidence Test Sequential Sampling Part 37
6.2 Filter Check 37
6.3 Sensor Optics Cleanse (GD-10 Only) 38
6.4 System Calibration (All Sensors) 38
6.5 Pump Service 38
6.6 Inspecting and Cleaning Snorkel Valves 38
6.7 Testing and Calibrating the TQ126F 39
7.0 PARTS LIST 40
Appendix A 43
1.0 INTRODUCTION
The TQ4400 Tankscan extracts a gas sample from a desired location, via
transport lines to an analysing unit where the sample is monitored for
‘Flammable’, ‘Toxic’ or ‘Oxygen’ gases. This is a cost effective method of
gas detection, as only one sensor is required per gas detected.
Table 1
Typical explosive and toxic gas sensors, which can be installed within the
TQ4400, can be seen in table 2, (other gases are available on request.)
Explosive Toxic
Table 2
With the ability to monitor for the gases indicated above, the system can be
configured to allow a ‘Pump Room Gas Monitoring System’ to be
integrated into the TQ4400, thus eliminating the need for two separate
systems.
The TQ4400 Display Unit can be mounted within the cabinet or in a remote
location, if for instance the analysing unit is installed in an un-manned area.
The operator interface is via four push buttons and a backlit LCD. During
normal operation the LCD display will provide the ‘location’, ‘gas type’ and
sample ‘concentration’ for each individual location.
N.B. A separate SET UP Manual and ‘button box’ for changing ‘sample
line’ No’s., ‘gas range’ and ‘alarm levels’ is available. These are factory set
to the customer’s requirements, but can be altered on commissioning by a
TQ Environmental Engineer.
B.E Trunk WB
T1
Port P OR
T
Bulkhead
Ships Air Supply
Cleaning
F.W.T
Sample Lines Penetrate
PORT
Pipe Trunk
into Main Control Unit in
Cargo Control Room Cleaning
(See Detail 'A') F.W.T
Lower
Stool Aft
Lower
Stool Fwd
STB
Vent Drain
Bulkhead
WBT 5 STB WBT 4 STB WBT 3 STB WBT 2 STB
HYDRAULIC ROOM
BULKHEAD
ANALYSING UNIT
SAMPLE LINE #1
SAMPLE LINE #2
SAMPLE LINE #3
SAMPLE LINE #4
POWER SUPPLY CCR
SAMPLE LINE #5 CHANG-OVER UNIT
TQ Environmental Plc
SAMPLE LINE #6
SAMPLE LINE #7
SAMPLE LINE #8
DETAIL 'A'
SAFE AREA System Schematic
BULKHEAD
Page 5 of 43
TQ Environmental Plc
♦ Pneumatics
♦ Sensors
♦ Control & Display Unit
♦ Power Supply Change Over Unit
♦ Sample Line Accessories
♦ Outputs
♦ Technical Specification
2.1 Pneumatics:
Please refer to Fig 2, 3, 4 and 5, pages 9, 10, 11 and 12 respectively.
Every Sample Line from the relevant Location is firstly connected to its
respective external ‘Shut-off Valve’ to provide sample line isolation. The
sample then passes through a flame arrestor mounted externally on either side of
the cabinet, and into the Analyser Unit.
♦ Solenoid Valves
♦ Catch pot - water trap
♦ Particulate Filter
♦ Double Ended Pump
♦ Coalescing Filter
♦ Flow Meter
♦ Reverse Purge
♦ Leak Detection
2.1.1 The Solenoid Valves are mounted in blocks of eight onto a common
manifold. The manifolds are fitted in pairs to a gland plate, which allows
direct external connection to the input port of each valve.
Fitted onto each pair of manifolds is a Solenoid Driver Board. This board
receives data from the BTC board to operate the solenoid valves.
Each valve is complete with a 24V dc coil, and connection to each coil is
via 3 pole connector containing an LED and snubbing diode.
2.1.2 The Catch pot is fitted with a poly-carbonate bowl allowing visual
inspection of the water levels. In the event of the bowl becoming full a
float assembly will block the outlet, firstly to prevent water entering the
system and secondly to create a Flow Fail Alarm.
To empty the bowl, firstly stop the pump and open the drain valve at the
bottom of the bowl. When empty Ensure that the drain valve is fully
closed prior to re-energising the pump.
2.1.3 The Particulate Filter is fitted with a micro-fibre filter element, which
cannot be cleaned and therefore must be replaced when discoloured or is
suspected of reducing air flow. This unit is also fitted with a poly-
carbonate bowl to allow visual inspection of the filter element. Spare filter
elements can be supplied, refer to Section 7 for Part numbers.
2.1.4 The Pump is an Industrial Double Ended type with the two pumps
connected in series to ensure adequate flow rates for the larger
installations. As an example on transport tube dimensions of 4.0mm I/D,
flow rates in excess of 4 litres/min. are achievable for sample line lengths
up to 300 metres. Based on these figures, sample times for a 300 metre
sample line will be in the order of 1 minute, providing sharp bends and
fittings are kept to a minimum. A Pump Service Kit can be supplied, refer
to Section 7 for Part numbers.
2.1.5 The Coalescing Filter is of nylon construction and, as with the Particulate
filter, incorporates a clear bowl for visual inspection of the filter and
moisture level. Here again the element must be replaced when
discoloured. The drain outlet is fitted with a needle valve, which is opened
sufficiently to allow a small airflow through the Coalescing Filter all the
time the pump is running. This should drain any moisture that has
collected in the Filter bowl. Spare filter elements can be supplied, refer to
Section 7 for Part numbers.
2.1.6 The Flow Meter is fitted in the sample flow line to indicate airflow to the
sensors and works in conjunction with the Sample by-pass needle valve.
The steel float, sensing ring and control relay, are all part of the flow fail
device. If the float passes down through the sensor a Low Flow signal is
sent to its’ control relay. When flow returns the float will raise back
through the sensor and the signal to its’ control relay will revert to normal.
If the gas concentration within the enclosure exceeds 30% LEL the Power
Supply Change-over Unit will disconnect the supply to the TQ4400
Analysing Unit. The power supply cannot be re-connected until the gas
concentration has fallen below the alarm level and a manual reset at the
Power Supply Change-over Unit has been carried out.
2.1.9 Sample Line Equipment is available in several forms to suit the sample
location.
The In-Line Filter is a stainless steel unit that is suitable for attaching to a
stop-valve when fitted in a stop valve box. It is advisable to remove the In-
Line Filter complete for cleaning, as splitting the filter in situ may damage
the threads. Refer to the Installation section 4.5 for Filter Drawings.
Page 9 of 43
PNEUMATIC/INSTRUMENT
SCHEMATIC DIAGRAM
AIR IN
(Min 6 Bar Max 10 Bar) Flame Arrestor Mounted
(See Note 2) On Outside Of Cabinet
17 Gas Gas
Detector Detector Hydrocarbon Monitor
Vent
11A 11B
2A
12 Link To
3,1 Display
Unit
Stream 1
17 C NC BTC
1,1 2,1 NO BOARD
Pump Pump 15
13 8A
5A 5B 6
9
4 Flow Fail
Signal
7
TQ Environmental Plc
NC
10
C NO C
NO
3,n
17 14 16
Stream n NC
Drain
1A
Page 10 of 43
TQ Environmental Plc
STOP VALVE
FLAME TRAP
NC PURGE SOLENOID
PARTICULATE FILTER
BTC BOARD
BTC
15 USED TO DRIVE SOLENOIDS; ACCEPTS GAS SENSOR
BOARD AND FLOW FAIL SENSOR INPUTS; COMMUNICATES
SYSTEM STATUS TO DISPLAY UNIT
COALESING FILTER
DRAIN VALVE
3-WAY VALVE
NO C THE VALVE IS NORMALLY SET SO SAMPLE GAS
10 FLOWS THROUGH PORTS NO & C. HOWEVER TO GAS
TEST THE SYSTEM THE POSITION OF THE VALVE
NC IS MANUALLY CHANGED SO THAT TEST GAS FLOWS
THROUGH PORTS NC & C.
GAS SENSORS
12 AIR REGULATOR
CATCH POT
ALLOWS FREE PASSAGE OF AIR UNDER NORMAL
16 RUNNING CONDITIONS BUT THE OUTLET IS BLOCKED
SHOULD WATER BE DRAWN INTO THE SYSTEM.
2.2 Sensors
There are two type of sensors, the infrared type, for flammable gases, or the
electro-chemical type for Toxic and Oxygen gases. When a system comprises of
more than one sensor, they are connected in series in the sample line which then
is vented out from the enclosure through a flame arrestor.
The operation of the infrared sensor within the TQ4400 Tankscan system
has been developed from the infrared heat source detector utilised in the
thermal imaging cameras measuring infrared radiation. These detectors
have now developed into non-dispersive infrared analysers.
These sensors typically monitor for Oxygen and Toxic Gases and because
of their properties have a life span of approximately 2 years.
The BTC board accepts hard wired inputs from the gas detectors, flow fail relay
and communicates the system status to the Display Unit via a RS 485 serial link.
System status consists of gas concentrations, system fault and alarm status, and
current sample locations.
The Display Unit analyses the information and transmits back to the controller
BTC board any system operations required, to operate gas concentration alarm
relays, sample-line or reverse purge solenoid valves.
RS485 Display
RS485 Watchdog
Rela
Boar
Both the Control PCB and the Display PCB are constantly monitored by
an individual watchdog unit. This alarms if the any or both of the
processors on the relevant Board fail.
During normal operation the Display Unit will show the current sample
location, gas type, gas concentration and fault alarm status, and generate
alarm outputs by communicating with the BTC board. Refer to section 3.3
for display operation.
This Display Unit can be installed in either the front door of the TQ4400
Analysing Unit, or, remotely as a wall mounted or console mounted unit.
The unit is supplied with plug and socket connections for ease of
installation and maintenance.
TQ ENVIRONMENTAL PLC
TQ4400 GAS DETECTION SYSTEM
218
ALARM ALARM SYSTEM WATCHDOG
1 2 HEALTHY
189
MAIN SUPPLY
STANDBY SUPPLY
GAS ALARM
322 380
RESET
580
TQ ENVIRONMENTAL PLC
Flanshaw Way, Wakefield, W Yorks
England, WF2 9LP
Tel: + 44 1924 380700
Fax: + 44 1924 361700
Email: sales@tqplc.com
website :http:// www.tqplc.com
Page 16 of 43
TQ Environmental Plc
The unit will accept 110 - 240V a.c, 50-60 Hz inputs, and will automatically
change back to ‘Main’ when the main supply is restored.
• Mains Supply On
• Emergency Supply On
• Internal Gas Alarm
•
2.5 Watchdog
This unit is mounted on the rear of the enclosure front door to monitor the main
processors in the control board and the display board.
In the event of either of these processors failing the LED and an audible buzzer
will activate.
WATCHDOG ALARM
UNIT
ALARM
MUTE
The audible buzzer can be extinguished using the mute button on the unit, but to
reset the fault the system has to be restarted by powering down from either the
fused isolator in the bottom right hand side of the cabinet or from the power
supply changeover unit.
2.6 Outputs.
• Two sets of Volt Free relay change-over contacts one for High and
one for Low Alarms for each sensor
• One set of Volt Free Change-over relay contacts for System Fault
Alarm.
• One set of Volt Free Change-over relay contacts for Mains Supply
Fail
• One set of Volt Free Change-over relay contacts for Common
Concentration Alarm
The Common Alarm relays can be configured to provide a 24V dc output for
each alarm level to drive audible/visual warning devices or remote indicators.
Relays can also be configured to provide outputs for individual location gas
alarms. These additional relay outputs must be specified prior to order
placement.
3.0 OPERATION
This section explains in detail the TQ4400 system operation and typical alarm
conditions. Four front panel push buttons are used for operator interface namely:
SKIP, HOLD, ACK, and RESET.
When power is applied to the system, the display will indicate System Set-up
mode, as below
SYSTEM SETUP
PLEASE WAIT
The system will stay in this mode for approximately 150 seconds.
After the ‘start-up’ delay the system will enter the normal operating mode.
CHAN 1
METHANE 00015%LEL
The top line of the display shows the channel location and the bottom line of the
display will show the gas sensor name, concentration of the gas, and the units of
the gas being analysed. The system will sequentially sample all of the channel
locations, displaying the appropriate data on the LCD.
At any time during the normal operating mode, the user has the option to
GOTO, Hold or Skip a channel. These functions are invoked by pressing down
the relevant push button, and are discussed further below:
The user may press down and hold the RESET and HOLD button until the
display reads GOTO, the user must then release the RESET and HOLD
button. You can then select which sample location to ‘GOTO’ by using
ACK to go up and RESET to go down through the sample locations.
Pressing Hold selects the desired channel.
Once the unit is sampling from the desired location you can then either
HOLD, SKIP or Reverse Purge the location.
The user may press down and hold the HOLD button until the display
reads HOLD CHANNEL, the user must then release the HOLD button.
CHAN 1
HOLD CHANNEL
This will invoke the Hold Channel function. The current Channel location
will be continuously sampled for a maximum period of 20 minutes after
which time the system will revert to sequential sampling. At any time the
user may release the channel and enable the system to revert back to
sequential sampling.
This is achieved by pressing down and holding the HOLD button until the
display reads RELEASE CHANNEL, the user must then release the HOLD
button.
CHAN 1
RELEASE CHANNEL
The user may press down and hold the SKIP button until the display reads
SKIP MODE, the user must then release the SKIP button.
CHAN 1
SKIP MODE
This will invoke the Skip Channel function. The current channel location
will be skipped when the system is sequentially sampling the channel
locations. When the system returns to the skipped channel, the LCD will
display SKIP MODE for 5 seconds and then proceed to the next sequential
channel. When the LCD displays SKIP MODE the user may revoke the
skip command by pressing down and holding the SKIP button until the
display reads NORMAL MODE, the user must then release the SKIP
button.
CHAN 1
NORMAL MODE
The user may press down and hold the ACK and RESET buttons until the
display reads GLOBAL REVERSE PURGE followed by REVERSE
PURGE. This initiates a global reverse purge where air is blown down
every sample line for a set period of time. The purge duration is factory set
and a ‘Button box’ is required to be interfaced to the controller BTC board
to change the value.
After the system has finished purging it will revert back to sampling.
This is a reverse purge, for all sample points, which automatically initiates
after a set number of complete cycles of sample points. We recommend
this function to be enabled for an analyser unit which draws samples from
points where water can be found, such as ballast tanks. The purge
frequency is factory set and can only be altered using a ‘button box’ being
interfaced with the controller BTC board. The box can be obtained by
contacting TQ.
There are three possible fault conditions: Sensor Fault, Flow Fail and
Comms Failure. The sensor will be in fault if the output of the sensor falls
below a set value. When this occurs the LCD will display SENSOR
FAULT, the System Healthy LED will extinguish and the Fault relay will
be activated.
SENSOR FAULT
The Flow Fail will occur if the pressure through the system drops to a set
value. When this occurs the LCD will display FLOW FAIL, the System
Healthy led will extinguish and the Fault relay will be activated.
FLOW FAIL
To clear the Fault condition press and hold the RESET button until the
display reads RESET ALARM. At the same time, the System Healthy led
will illuminate and the Fault relay will be de-activated.
RESET ALARMS
COMMS FAILURE
This cannot be reset by the RESET button; the panel has to be opened and
powered down and back up again. However it is preferred to do this from
the power supply changeover unit.
There are two alarms on the system, a low level alarm, ALARM 1, and a
high level alarm, ALARM 2. When the gas concentration exceeds the set
levels, the appropriate alarms will be activated, and operate the appropriate
LED’s and alarm relays. The LCD will display the first channel to be in
alarm, together with the sensor gas type and relevant alarm condition. The
system will continue to sample the channels sequentially.
CHAN 1
CHAN 1 SYSTEM
HEALTHY
METHANE HI ALARM
The user may reset the alarmed channel by pressing the RESET button. At
which point the alarms for that channel will be cleared. If there are any
pending alarms then the LCD will display the next alarmed channel
information. The user must again press the RESET button to clear that
particular alarm. When no more alarms are present, the system will display
the concentration as normal.
The user may press the Ack button to clear the audible buzzer. This will
acknowledge the alarmed channel and display ALARM
ACKNOWLEDGED on the LCD.
CHAN 1
ACKNOWLEDGED ALARM
If there is a pending alarm the LCD will display the pending alarm information.
When all alarmed channels have been acknowledged, the system will display the
gas concentration sequentially, but will also display ALARM
ACKNOWLEDGED on the LCD for 5 seconds. To de-activate the alarm relays
the user must use the RESET function as described above.
RESET ALARMS
Each alarm is then reset on a channel per channel basis, i.e. if a particular
channel is in alarm then another channel comes into alarm, then the first channel
requires one reset and a second reset clears the next set of alarms in the second
channel.
4.0 INSTALLATION
The display unit can be supplied as a wall / console mounted or already installed
within the analysing unit, refer to Fig. 7, page 15.
As with the TQ4400 Analysing Unit this unit contains sensitive electronics it is
recommended that the unit be installed in a relatively stable environment, where
vibration is at a minimum and away from high voltage equipment.
It is recommended that this unit be mounted adjacent to the Analysing Unit for
ease of connection and to keep cable runs to a minimum. Again the unit is
designed to be fixed to a rigid bulkhead via 4 x 8mm mounting brackets on the
rear of the enclosure, refer to Fig 8, page 16.
The Shut Off Valves must be installed in each of the sample lines in order to
comply with classification society regulations.
ACCOMMODATION
BULKHEAD
Weld Tube
50
ACCOMMODATION
BULKHEAD Manual Shut
Off Valve
Refer to Fig 9a for the minimum required valve spacing when using the
valve/weld tube arrangement. It is recommended that after installation the shut
off valves be labelled with the details of the corresponding sample line location
in order to ease identification.
8 7 6 5 4 3 2 1
100
9 10 11 12 13 14 15 16
Snorkel Valves must be attached to the ends of any sample lines that are
periodically submerged in water, e.g. ballast tanks, in order to prevent the
sampling of water when the sample location is flooded.
Snorkel valves must be mounted in the vertical position to operate
correctly. If they are mounted at any other angle there is a risk that the ball
inside the valve will not seal correctly and allow water to enter the system.
The snorkel valve must also be rigidly secured via straps or “U” bolts
around the body of the valve to prevent movement due to surging ballast.
103 mm
55 mm
Weld
Bracket
BULKHEAD
105
55
120
Mounting Plate
When sample lines are installed in void spaces it is recommended that end of
line particulate filters are fitted to prevent dust particles/debris from being
sucked into the system.
Please note end of line filters are only suitable for use in dry areas and must be
installed in an accessible position for ease of service.
P Clip
40mm Filter
30mm
Element
15mm
When sample lines are installed in void spaces and the end of the sample
line is not readily accessible it is recommended that an in-line filter be
used.
This has the same function as the end of line filter i.e. to remove
dust/debris. However, this filter is installed directly in the sample line by
means of two compression fittings, which match the size of the sample
lines used, refer to fig 12.
Again as with end of line filters in-line filters are only suitable for use in
dry areas and must be installed in accessible position for ease of service.
Filter
Element
100 mm
20 mm
Sample lines from point of connection at the analysing unit to point of sample
should be as straight as possible and U-bends should be kept to a minimum.
However due to the heavy duty vacuum pump and the ‘Reverse Purge’ facility,
which removes moisture/debris from the lines some U-bends can be
accommodated.
The sample lines between the bulkhead shut off valves and the analysing unit
should be free of detachable connections except for the connection points for the
shut off valves at the bulkhead and the analysing unit and should be routed the
shortest way possible. If sample lines between the shut of valve and the
analysing unit have to be joined welded connections should be used.
Sample lines should not be run through gas safe spaces except for the section
from where they penetrate the accommodation bulkhead to the point where they
attach to the analysing unit.
Vent and drain exhaust lines are to be vented to atmosphere in a safe area away
from ignition sources and the area within 3m of the outlets is to be considered as
a hazardous location.
After all sample, vent and drain lines are installed it is vitally important to test
for leaks and blockages. Applying compressed air at the start of the line and
ensuring that airflow’s from the end of the line identify blockages. Leaks are
identified by blocking one end of the line and applying compressed air with a
pressure of 5-6 bar, hold the pressure in the line and monitor for pressure drops,
there should be no drop over one minute.
Ensure that all Sample Lines are connected to the Analysing Unit on the correct
ports, in order to eliminate the possibility of ‘crossed lines’.
Keep all sensor and communication cables separated from voltage distribution /
switching cables.
NOTES
Gas Sampling/Control Unit
1. Sample lines should have continous
fall if possible, From point of entry, to sampling
cabinet, to point of sample. 'U' Bends in pipework
to be kept to a minimum.
SAMPLING AREA
Mounting Plate
Page 33 of 43
TQ Environmental Plc
5.0 COMMISSIONING
As the system is a very important safety feature that contributes to the safe
running of hazardous cargo carrying vessel, TQ Environmental urge that the
above comments are understood.
This section repeatedly references the ‘system drawings’; these drawings are
project specific and no two sets are the same. Please ensure that the correct
drawings are available.
5.1 Installation.
5.1.1 Ensure that all points detailed in section 4 are completed, pay
particular attention to the points dedicated to sample lines.
Only when section 5.1 has been completed can the commissioning
proceed.
5.2.2 Check that the voltage to the system corresponds to the voltage stated
in the system drawings.
Only when the two above points have been completed, can the
system be ‘Powered up’ for testing.
5.2.3 Check with the ships staff that the ballast tanks are not in ballast. If
some are, take a record of these tanks. This is extremely important, as
the tanks need to be inhibited from the sampling sequence.
5.2.4 Apply power to the system via the power supply change over unit.
Fault alarms may occur after system boot up, this is due to the time
taken by some sensors to ‘warm up’.
5.2.5 After power up, enable ‘skip’ on tanks which are ballast. This is
explained in section 3.3.3.
5.3.2 Hold on the sample location, which is the furthest away, (usually the
fore peak), refer to section 3.3.2.
5.3.3 Adjust the sample by pass so that the sample flow reads
approximately 3 litres/minute.
5.3.4 Remove the ‘hold’ function on the location selected, refer to section
3.3.2.
5.3.5 As the system changes sample locations, the flow rate will change.
This is normal as the sample line lengths vary.
This section gives details on how to set the individual sample locations
‘dwell time’, this is the time taken to transport a sample gas from a sample
location and analyse it accurately.
Whilst this test is carried out, it is possible to test the sample lines for
blockages or leaks. Appendix A can be used to record the test results.
5.4.4 Apply gas to the sample line and record how long it takes for the
system to display a gas concentration on the LCD. Log this time in the
Dwell Time column.
5.4.5 Block the sample line off, as the flow decreases a flow fail alarm will
activated, if this is not the case a leak in the line may be apparent -
amend and repeat the test. Log the result in the table, column ‘Flow
Fail’.
5.4.6 Enter the Dwell Time for each location into the system, in order to
achieve this you require a ‘button box’ to interface with the controller
Filename: Eng:H/Drg’s & Docs /4826/4826T3 Page 35 of 43
TQ Environmental Plc
BTC board. This can be obtained by contacting TQ, where a box and
instructions can be despatched.
Frequency: 6 Months
Ensure that the concentration of gas used is greater than that of the highest
alarm set point.
Description:
When sample locations are grouped into zones, and different zones activate
different alarms, ensure that all ‘zone alarm configurations’ are known so
that alarms can be checked.
Activate a flow fail alarm, this can be achieved by blocking the current
sample line through the ball stop valve. Once the alarm is activated,
acknowledge the alarm, refer to section 3.4.
Connect the test gas to the calibration point within the analysing unit but do
not turn the gas on. Ensure that the 3-Way valve is set on the ‘calibration’
position and turn the gas on at a rate of 1 litre / minute.
The system will now generate a gas alarm on the current sample location.
Ensure all relevant alarms are activated, for example any external beacons
and alarms on the Vessels alarm management system.
Ensure also that the display reads the same concentration as that of the
calibration gas used, i.e. 50% LEL if 50% LEL calibration gas is used.
It must be noted however that all calibration gases have a tolerance that
must be taken in to account.
Description: Remove the sensors weather cap and clean the mirror /
lens with the lint free cloth. This may activate a system
fault alarm if the sensors optical path is blocked, to clear
this alarm refer to section 3.4.
6.4 System Calibration (All Sensors)
Frequency: 12 months
Description: Refer to section 6.1 for applying test gas. Repeat for all
Sensors.
Note, if the calibration for any of the sensors requires
altering, a ‘button box’ and instructions is required from
TQ.
6.5 Pump Service
Frequency: 24 months
Description:
a) Power down the TQ4400 gas detection equipment. Visually inspect end
of line snorkel valves for dirt and silt build up. Hose down and clean the
valve as necessary.
Frequency: 12 months
Equipment Needed: Zero and Span Calibration Gas suitable for the
sensor used.
Span: 50% LEL or similar
Zero: Synthetic Air 0% LEL
Description:
Please refer to section 2.1.3 for an introduction to the TQ126F, and the
drawing showing the TQ 126F PCB Layout, Fig 14.
Ensure the correct voltage is across the gas sensor by measuring the voltage
across terminals 1 and 3 of the ‘PEL’ terminal connector, next to VR2,
within the sensor’s junction box. Adjust VR1 so the voltage is 2.00V d.c,
+/- 0.1v.
Apply Zero gas to the sensor using a suitable gassing cap at a rate of 1
litre/minute, adjust VR2 so that the TQ126F display reads 0.00 %.
Apply Span gas to the sensor using the suitable gassing cap at a rate of 1
litre/minute; adjust VRoVM so that the TQ 126F display reads the same
value as the span gas, i.e. 50.00 %.
While applying gas to the sensor and ensure that the power to the Analysing
Unit is cut at 30 % LEL.
VR 2 VR 1
VRDVM
RL 1
VR 3
VR20MA S/W 1
VR4MA
Appendix A
TQ 4400 SERIES
GAS
DETECTION SYSTEM
SET UP MANUAL
This manual must not be copied or reproduced in part without the express written
permission of TQ Environmental PLC. All information contained herein is subject to
modification.
Filename: 4826CR1
First Issue: 6th November 2001
Author: W.Cawood/G. Thompson
Page 1 of 17
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
Contents
Page 2 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
When any parameters require changing within the TQ4400, a Set-Up box must be
connected to the unit to access the main control parameters.
The connection is detailed on the figure on the next page and described below.
1.2. Connection
Refer to figure 1; page 4 of this manual.
On the Set-up box there are two flying cables. The first cable is a 16 way
ribbon cable and is connected as per figure 1 overleaf. Please take note on
connection of where pin 1 is on the Circuit board and where the Pin 1
connection on the ribbon cable is located i.e. indicated by a red or blue
strip.
The second cable is a five core spiro bound multi-core cable connected to
an 8 way 45o connector. This 8 way connector is connected into a 9 way
connector (CONN 2) located on the top side of the PCB with the blue wire
being Pin 1 & Pin 8 being the grey wire which must terminate in terminal 8
of CONN 2
Page 3 of 16
16 WAY RIBBON
Figure 1
RED OR BLUE STRIPE
INDICATES PIN 1
TQ 4400 Set Up Manual
PIN 1
TQ ENVIRONMENTAL PLC
BACK OF PANEL
CARD GUIDE
Page 4 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
2.1. Power Up
When the system is first powered up the title screen will be displayed
showing the software name and version number.
TQ ENVIRONMENTAL
DOWNLOADING DATA
....
3. Menu Access
After the title screen is displayed, data is transferred from the NVRAM to
system memory. To access the menu, the MENU button must be pressed and
held down until the LCD displays SYSTEM TRANSFERRED.
Page 5 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
SYSTEM TRANSFERRED
The menu may be navigated by pressing the UP and DOWN buttons, which
will enable the user to scroll through the menu items. The menu items will
wrap around from the last menu item to the first menu item and vice-versa.
MENU
PARAMETERS
For example, if the UP button is pressed when the last menu item, EXIT
MENU, is displayed, the first menu item, PARAMETERS, will be displayed.
MENU
TECHNICIAN MODE
Conversely, if the DOWN button is pressed when the first menu item,
PARAMETERS, is displayed, the last menu item, EXIT MENU, will be
displayed.
MENU
EXIT MENU
To select the desired menu item, the user must press the SELECT button.
Page 6 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
4. Parameters
System parameters may be set and edited by entering the PARAMETERS
menu option.
Once entered, the display will prompt the user to select a desired channel
location for editing. The user must press the UP and DOWN buttons to
display the required channel location and then press the SELECT button to
accept that channel location.
PARAMETERS MENU
CHANNEL 1
When a channel location has been selected, the user may cycle through the
Parameters Sub Menu using the UP and DOWN buttons and select the
required Parameters Sub Menu Item using the SELECT button.
PARAMETERS MENU
SET LOCATION
SET LOCATION
CH_
The user must use the UP and DOWN buttons to cycle through the
alphanumeric characters, pressing the SELECT button when the display
shows the required character. To leave spaces, select the <SPACE>
Page 7 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
character and press the SELECT button. When the SELECT button has
been pressed the next digit on the right will be displayed. To accept the
channel location description the user must press the MENU button.
PARAMETERS MENU
METH_
The user must use the UP and DOWN buttons to cycle through the
alphanumeric characters, pressing the SELECT button when the display
shows the required character. To leave spaces, select the <SPACE>
character and press the SELECT button. When the SELECT button has
been pressed the next digit on the right will be displayed. To accept the
channel location description the user must press the MENU button.
Page 8 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
PARAMETERS MENU
To change the dwell time for that particular channel the user must press the
UP and DOWN buttons and the SELECT button when the desired dwell
time is displayed.
00040
This option will allow the user to set sensor parameters for a specified
sensor on a specified channel. To select a particular sensor the user must
press the UP and DOWN buttons to cycle through the available sensors and
SELECT button when the desired sensor is displayed.
PARAMETERS MENU
PARAMETERS MENU
Page 9 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
This option will allow the user to set sensor parameters for a specified
sensor on all channels. The sensor parameters are the same as the Select
Local Sensor parameters and are described as follows:
SENSOR MENU
SET ALARMS
When selected, this option displays a Set Alarms sub menu which
allows the user to Select High Alarm, Select Low Alarm, or Exit Sub
Menu. The following describes the typical for a high alarm but the
Select Low alarm option works in exactly the same way
SET ALARMS
This option will allow the user to change the alarm point level.
The alarm point level will increase or decrease in steps of 1 if
Page 10 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
00040
When the desired alarm point level is displayed, the user must
press the SELECT button to accept the displayed value.
+_
This option is the same as the Set High Alarm above, but
refers to the low alarm point.
SET ALARMS
Page 11 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
This option will allow the user to select the appropriate units
corresponding to the gas type. The available units are as follows:
PPM, %LEL, %VOL, and MGM.
SET UNITS
%LEL
This option allows the user to set the desired gas sensor range.
SENSOR MENU
SET RANGE
SET RANGE
50000
Page 12 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
TECHNICIAN MENU
12
This option allows the user to select the desired number of sensors.
TECHNICIAN MENU
01
This option allows the user to skip a channel. When the SELECT
button is pressed, the display will show SKIP MODE or NORMAL
MODE to indicate to the user the channel status.
Page 13 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
TECHNICIAN MENU
SKIP CHANNEL
TECHNICIAN MENU
NORMAL MODE
This option allows the user to set a time period for the purge of each
sensor.
TECHNICIAN MENU
00060
Page 14 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
This option operates in conjunction with the Set Purge Time option.
Set Purge Cycle is the number of complete cycles before a purge is
processed. Purge may be turned off by setting Purge Cycle to 0.
00
This option will allow the user to calibrate a particular sensor. When
the sensor to be calibrated is selected the user is prompted to set the
value of concentration the sensor should be reading. This is achieved
using the UP and DOWN buttons and pressing the SELECT button to
accept the value. These values will then be scaled and stored in the
NVRAM for future reference.
TECHNICIAN MENU
CALIBRATE SENSOR
CALIBRATE SENSOR
00050
Page 15 of 16
TQ ENVIRONMENTAL PLC
TQ 4400 Set Up Manual
This option allows the user to clear all calibration data from the
NVRAM and in doing so sets all sensors to default calibration.
TECHNICIAN MENU
CLEAR CALIBRATION
6. Disconnection
When all changes have been made, it is necessary to exit all menus. When this
is done the system will start sampling.
Power Down
Remove both of the connections from the Set-up Box and re-apply power.
The system will now start running within the users defined set up.
Page 16 of 16
TQ Environmental Plc
GD129NI INFRARED
COMBUSTIBLE GAS SENSOR
(NON-INDICATING)
OPERATING MANUAL
CONTENTS:
page no:
Proprietary 3
Warning, Cautions and Notes 3
Safety Warnings 4
Section 1 Description
1.1 General description 5
1.2 Method of detection 5
1.3 Sensor unit 5
1.4 Gases monitored 7
1.5 Performance specifications 8
Section 2 Installation
2.1 Mechanical installation 9
2.2 Electrical installation 10
Section 4 Maintenance
4.1 Routine maintenance 14
4.2 Warranty 14
Section 5 Spares 15
Section 6 Certification 16
PROPRIETARY
While great efforts have been made to assure the accuracy and clarity of this
document, TQ Environmental PLC assumes no liability resulting from any omissions
in this document, or from misuse of the information obtained herein. The
information in this document has been carefully checked and is believed to be entirely
reliable with all of the necessary information included. TQ Environmental PLC
reserves the right to make changes to any products described herein to improve
reliability, function, or design, and reserves the right to revise this document and
make changes from time to time in content hereof with no obligation to notify any
persons of revisions or changes. TQ Environmental PLC does not assume any
liability arising out of the application or any use of any product or circuit described
herein; neither does it convey license under its patent rights or the rights of others.
SAFETY WARNINGS
SECTION 1 - DESCRIPTION
The GD129NI Sensor is used for diffusion sensing applications. These are
applications in which the sensor continuously monitors that part of the environment
with which it is in contact and the gas diffuses through the sensor’s optical path. This
technical manual covers the use of the GD129NI Sensor as a diffusion type sensor.
The fully assembled GD129NI Sensor unit has the approximate dimensions of 242mm
(Height) X 106mm (Width) X 92mm (Depth). The main components of the GD129NI
Sensor unit are:
Figure 1 - Configuration
The amplifier printed circuit board (PCB) installed inside the J-Box, contains an
amplifier circuit for converting the IR detector’s absorption signals into a 4-20mA
output signal.
Sensor Assembly.
The sensor assembly consists of a Flame Arrestor surrounding an Optical Bench
Assembly. The entire Sensor Assembly is surrounded by a protective stainless steel
Guard. Refer to Figure 2.
Flame Arrestor.
The Flame Arrestor is made of 316 Sintered Stainless Steel. The stainless steel
ensures high corrosion-resistance. The arrestor has a sheet of filter material fixed
around the outside to stop the entrance of dust, dirt and moisture.
Guard.
The stainless steel or resin moulded guard provides physical protection for the Flame
Arrestor and the Optical Bench Assembly. In sensor calibration operations, a
calibration cup can be installed over the Guard to provide for adequate flow of
calibration gas to the sensor.
Methane
Propane
Butane
Hexane
Filename: 2089MAB2 Page 7 of 18
TQ Environmental Plc
Acetone
Pentane
Ethane
Toluene
The GD129NI Sensor does not detect certain other combustible gases, such as
Hydrogen and Hydrogen Sulphide.
FACTOR SPECIFICATION
Detection Method: IR Absorption
Sampling Method: Continuous Diffusion
Measuring Range: 0 - 100% Lower Explosive Limit (LEL)
Accuracy: + 2% Full Scale (FS) Linearised
Repeatability: + 1% FS
Response Time: 1. Raw: <3 seconds to 90% of FS
2. Normal: <20 seconds to 90% of final reading (As
installed using 50% LEL CH4 test gas)
3. High Gas Levels: <5 seconds to FS Value
Temperature Range: -30°C to +60°C (The range can be extended if a
sunshield is fitted around the sensor)
Humidity Range: 0 - 99% Relative Humidity (Non-condensing)
Mean Time Between Failures: Electronics: 10 Years, IR Source: 7 Years
Warranty: 3 Years
Operating Voltage: 11 - 28Vdc
Operating Current: 135mA at 12 Vdc/75mA at 24 Vdc
Connections: 3 Wire, 4-20mA (Source)
Construction Materials: Flame Arrestor: 316 Sintered Stainless Steel
Guard: 316 Stainless Steel or Resin Moulded
Weight: 1.05 kg (including junction box)
Electrical Hazardous Area E Exd llC T6
Certifications: Within an ambient temperature (Ta) -20C to +55C
SECTION 2 - INSTALLATION
Filename: 2089MAB2 Page 8 of 18
TQ Environmental Plc
• For the monitoring of heavier-than-air gases, mount the sensor unit as close as
practical to the floor or ground. For monitoring of lighter than air gases, install
the sensor unit as high as practical.
• The sensor unit should be installed in a location where it is easily accessible for
repairs.
• Mount the sensor unit in a position that minimises the risk of mechanical damage.
• Prevent water and dust accumulation from affecting operation by mounting the
sensor unit with the guard pointing downward, as shown in Figure 3.
• It is important to ensure the conduit-entry point at the top of the J-Box is
watertight. Use an approved EExd watertight packing gland. Apply commercial-
Filename: 2089MAB2 Page 9 of 18
TQ Environmental Plc
grade pipe thread sealant, such as Liquid Teflon, to the gland threads and install
the appropriate sealing washers.
• When the GD129NI is used in conjunction with a calibration cup for checking
operation the junction box must be mounted at least 10mm away from a vertical
surface.
• The fixing holes on the junction box accept 5mm diameter bolts.
4-20mA AMPLIFIER
OUTPUT Rload
FB
COMMON 0v
- 0V DC
24V DC
24 V DC
+ 24V DC POWER SUPPLY
It is important that for installation in hazardous areas, approved and certified screened
cable and cable glands are used with the instrument, and that termination is carried
out in the approved manner.
The cable screen must NOT be connected at the detector end, as it is to be connected
to ground at the control panel.
After wiring the lid of the junction box shall be screwed back onto the base.
3.1 COMMISSIONING.
Prior to connecting power to the GD129NI Sensor, the following preliminary checks
should be made.
a. Ensure the Sensor Assembly is screwed tightly into its junction box/enclosure.
b. Check that the Sensor Assembly is correctly wired to its PCB.
CAUTION
TO AVOID DAMAGE TO THE EQUIPMENT, ENSURE THE VOLTAGE
APPLIED TO THE PCB DOES NOT EXCEED 30 VOLTS.
3.2 CALIBRATION.
It is likely that the GD129NI Sensor will remain stable at its initial calibration
settings for long periods (2 - 3 years) and on-site calibration is NOT required.
EXAMPLE 1. Assuming the calibration gas is Methane, and the unit is linearised for
Methane and the gas concentration is 50% LEL; draw a vertical line from the 50%
LEL mark on the X-axis to the point where it intersects the METHANE curve. Read
across to the Y-axis; the amplifier output current should be 12.00mA.
EXAMPLE 2. Assuming the calibration gas is Hexane and the gas concentration is
10% LEL; draw a vertical line from the 10% LEL point on the X-axis to the point
where it intersects the HEXANE curve. Read across to the Y-axis; the amplifier
output current is between 8.00mA and 9.00mA. Interpolate between the two values;
the output current should be approximately 8.80mA.
For Methane (standard) or a gas for which the sensor is calibrated and linearised, use
the following formula to calculate the output current from the sensor in mA when the
accuracy of the applied test gas is known.
The GD129NI provides differing current output levels between 0mA and 4mA to
indicate various sensor fault conditions.
NOTE:
In the event of more than one fault occurring, the output currents for the
respective faults will be added together.
SECTION 4 - MAINTENANCE
The sensor unit may require corrective maintenance if any of the following occur:
CAUTION
THE OPTICAL BENCH AND THE SENSOR AMPLIFIER CIRCUITS ARE
MATCHED TO EACH OTHER AT THE FACTORY AND EITHER ONE
SHOULD NOT BE REPLACED AS A SINGLE UNIT. FOR THIS REASON
REPLACEMENT OF THE OPTICAL BENCH OR MAIN BOARD SHOULD
NOT BE ATTEMPTED IN THE FIELD. REFER THE UNIT TO TQ
ENVIRONMENTAL PLC FOR SERVICE.
If the unit ever becomes defective such that it is necessary to refer the unit to a service
facility, an exchange unit can be provided while the defective unit is being serviced at
the facility. Contact the local TQ representative or contact TQ directly. See the front
cover of this manual for details on how to contact TQ.
4.2 WARRANTY
SECTION 5 - SPARES
SECTION 6 –CERTIFICATION
SIRA 01ATEX1111:
The GD 129NI may be used with flammable gases and vapours with apparatus groups
IIA, IIB, IIC and temperature classes T1, T2, T3, T4, T5 & T6.
The equipment fitted is only certified for use in ambient temperatures in the range –20
degrees Celsius to +55 degrees Celsius and should not be used outside this range.
In addition, the GD129NI must be used with either the stainless steel flame arrester
guard (TQ Part No 317-012 ) or with the alternative stainless steel Flow Through
Tube (TQ Part No. 340-039 ) in place. In case of a fault, power to the instrument must
be provided from a source which limits the power to a maximum of 2.14watt
(178mA@ 12v to 71mA @ 30v).
Installations through bulkheads are also covered by the certificate provided that an
approved Adapter Tube (TQ Part No. 340-038 ) is used in conjunction with a
suitable Flange Interface Plate. The Interface Plate and Adapter Tube must be factory
fitted to the GD129NI.
Installation shall be carried out by suitably trained personnel in accordance with the
applicable code of practice e.g. EN 60079-14:1997, and using approved cable glands.
Inspection and maintenance of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice e.g. EN 60079-17.
The entry into service, use, assembling, and adjustment of the equipment shall be in
accordance with this Operating Manual.
The certification of this equipment relies upon the following materials used in its
construction:
If the equipment is likely to come into contact with aggressive substances, then it is
the responsibility of the user to take suitable precautions that prevent it from being
adversely affected, thus ensuring that the type of protection provided by the
equipment is not compromised.
Aggressive substances, e.g. acidic liquids or gases that may attack metals, or
solvents that may attack polymeric materials.
Filename: 2089MAB2 Page 16 of 18
TQ Environmental Plc
Certification Details:-
0518
Surveillance Authority Marking
TQ’s Manufacturing Mark GD129NI
ATEX Group & Category
ll 2G
CENELEC Marking E Exd llC T6
Ambient Temperature -20C to +55C
Apparatus Certificate No SIRA 01 ATEX llll
Certificate Holder Austech Instruments (Europe) Ltd
This declaration confirms that the GD129NI Infra Red Gas Sensor has been designed
and constructed in accordance with good engineering practice and is suitable for use
in foreseeable indoor and outdoor industrial environments. Austech Instruments
(Europe) Ltd attests to the following:
The equipment has been designed such as to avoid the possibility of physical
injury or other harm that may be caused by direct or indirect contact – ESHR 1.2.7
The equipment does not emit, nor is susceptible to, electrostatic discharges,
extraneous voltages or environmental effects when used within the stated
operating conditions – ESHRs 1.3.2 & 1.4.1
3.0 DRAWINGS
5798AH 2 Console Mount Mimic Panel Front Plate &Cut Out Details
40 x 8mm 316L St/St Compression 2) All Sample Line connections are Via left
Fittings For Connection to 8mm Gas Detection/Control Unit hand side of cabinet see drg.5798E1.
OD Sample Lines
3) Test point & drain exit through bottom of
cabinet see drg.5798C1.
Class Approved
Penetration of M.C.T Sample Lines Connect Directly on to Flame 4) See Drg.5798D1 For Shut off Valve Detail.
Type (Yard to Supply) Arrestors Via 20 x 8mm 316L St/St Compression Fittings TQ4400 Ballast Tank Void Space
Gas Sampling System
5) Drain Line to be led to atmosphere with the
outlet arranged in a safe location away from
ignition sources.
Detector
(See Note 1)
TQ ENVIRONMENTAL PLC
Flanshaw Way, Wakefield, W Yorks
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
SAS 427/28/34/45 SHINA
PRODUCTION 12-02-03 TQ ENVIRONMENTAL 1. Penetration Type Changed Date. 12-02-03 Sampling System
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 13-02-03 CONTROL UNIT Dwg No.
WF2 9LP SAMPLE TUBE
380
10 210
MAIN SUPPLY
STANDBY SUPPLY
RESET
570 580
TQ ENVIRONMENTAL PLC
Flanshaw Way, Wakefield, W Yorks
England, WF2 9LP
Tel: + 44 1924 380700
Fax: + 44 1924 361700
Email: sales@tqplc.com
website :http:// www.tqplc.com
'A' 'A'
65
NOTES:
25
1) Glands:
80 To Suit Cable ( L - TPYC - 2.5 ) ( 13.5mmOD )
135
190
2) Only required if using cabinet gas remote
monitoring facility.
245
300
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
TQ ENVIRONMENTAL Date. Sampling System SHINA
PRODUCTION * 28-01-03 1. Cable Spec Changed 28-01-03 SAS 427/28/34/45
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 POWER SUPPLY Dwg No.
WF2 9LP CHANGE-OVER CONTROL
Red Black
Rubber
Sleeve
130mm
Rubber Sleeve
(Screen Cut Back
To Outer Sheath)
Red 30
2
RL1/1
3
4
Mains Fail Red 157 TBF - 02
150
1
7 151
2 Mains Fail Volt Free Contacts
RL1/2
6 3
5 152
TBF - 01
R153 To Mimic Panel Terminal 3 (System Running)
1
2
2 To Mimic Panel Terminal 4 (0V)
RL3/1
3
Red
158 TBF - 03
System Fail
154
1
7 155
2 System Fault Volt Free Contacts
RL3/2
6 3
5 156
2
RL4/1
3 White
4
Control Unit
Watchdog
7 Watchdog Alarm Output To
TBF-01 of Watchdog unit
RL4/2
6 Red Terminal 1 See Drg 5798AN
5 159
2 30
RL5/1
3
4 R153
Display Unit
Watchdog
7
RL5/2 162
6
5
NOTES:
1) Connect ribbon
cable red wire to
pin 1.
4 x Insulated Bushes ( Part No. 803 - 002) DISPLAY (Part No. 814 - 010 )
1
RED WIRE
TO BOTTOM
300mm
CONNECT TO CONN5
OF PCB 3185K2
Rear
Of
Display
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. Project Title Changed Date. 28-01-03 SAS 427/28/34/45 Sampling System
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 TQ4400 Dwg No.
WF2 9LP FRONT PANEL
DISPLAY
See Drg 5798W
Blue Red
CONN 1 1 2 3 4 5 6 7 8 9 CONN 15
1 2 3 4 5 6 7 8 9
CONN 5
2 Core Twisted
Pair with Overall Aluminium
Buzzer Screen
-
CONN 6 CONN 8 +
1 2 3 1 2 3
0v 5v 24v
BTC Board Red Blue
63
F16
67 F42 See Drg 5798R
TB-02
NOTES
1) See Drg 5798G For button wiring detail.
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Client.
Ballast Tank
TQ ENVIRONMENTAL Date. Sampling System SHINA
PRODUCTION * 28-01-03 1. Cable No.63 Added 28-01-03 SAS 427/28/34/45
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 TQ4400 CONTROL Dwg No.
WF2 9LP UNIT/WBT SYSTEM
App. N.D.A
CLIENT * 28-01-03 SCALE N/A
Web: http//www.tqplc.com
Email: sales@tqplc.com Date. 11-02-03
INTERCONNECTION
DETAILS 5798V2
TB-01
(220V)
F3
BROWN
BLUE
6 5
4 5
RL2 -
(Pump On/Off) Arc Suppressor
+
Brown
3 6
Blue
Red
33
F10
7 8
PUMP
NOTES:
1) All Wiring to be 7/30
C.S.A. TR-64 U.O.S
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
Sampling System SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. Cable Labels Added Date. 28-01-03 SAS 427/28/34/45
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 Dwg No.
WF2 9LP SAMPLE PUMP
Black 21
Clear 51
Red 31
Screen
Red Blue
+24V
0V
0V
5V
0V
Blue A B
1 Red
2
8 Red
2
Blue 9
1
Blue Red
1 2
7 Red
2 1
Blue 10
Blue Red
1 2
6 Red
2
Blue 11
1
Blue
1 Red
2
5 Red
2 1
Blue 12
Blue
1 Red
2
4 Red
2 1
Blue 13
Blue Red
1 2
3 Red
2 1
Blue 14
Blue Red
1 2
2 Red
2 1
Blue 15
Blue Red
1 2
1 Red Blue 16
+24V
2 1
0V
0V
5V
0V
B A
Screen
Clear 51
Black 21
Red 31
Blue Red
Cable 80
2 Core Twisted
Pair with Overall
Screen
3 Core 0.82mmsq
Screened Cable
Red Blue
+24V
0V
0V
5V
0V
Blue A B
1 2
Red
2 1
Blue
1 2
Red
2 1
NOT USED
Blue
1 2
Red
2 1
Blue
1 2
Red
2 1
Blue
1 2
20 Red
2 1
Blue
1 2
19 Red
2 1
Blue
1 2
18 Red
2 1
Blue
1 2
17 Red
+24V
2 1
0V
0V
5V
0V
B A
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL Date. 28-01-03 SAS 427/28/34/45 Sampling System
*
PLC Drawing Title.
DEVELOPMENT Flanshaw Way
Chkd. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire
Date. SOLENOID & RELAY Dwg No.
WF2 9LP
Blue
Blue
Pair With Overall Screen
Red
Red
2 Core Twisted Pair With 2 Core Twisted Pair With
Overall Screen Overall Screen
(Plug 2) (Socket 2) (Socket 4) (Plug 4)
GND 24v
NOTES:
B21
TB-02
1) ALL WIRING TO BE 7/30 R34
F15
CSA TR-64 U.O.S
2) CABLE SCREEN CONNECTED ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Client.
IN SOLENOID PLUG. Ballast Tank SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL Date. 28-01-03 SAS 427/28/34/45 Sampling Unit
*
PLC Drawing Title.
3) SOCKETS MOUNTED ON SIDE DEVELOPMENT Flanshaw Way
Chkd. Proj No. 5798/99/800/6094
OF ENCLOSURE. SERVICE Wakefield
Date. Dwg No.
West Yorkshire
WF2 9LP SENSOR, FLOW FAIL &
App. ALARM OUTPUT
CLIENT * 28-01-03 SCALE N/A
Web: http//www.tqplc.com
Email: sales@tqplc.com Date. CIRCUIT DIAGRAM 5800S1
Brown 1.0mm sq Brown 1.0mm sq Red 1.0mmsq
F40 (1A)QBG
NOTES: 50 BTC Board
Multicore 64
(1A)QBG See Dwg 5798T
F41
51
1) All Wiring to be Tri - Rated U.O.S. Relay/Solenoid Boards
Multicore 70
(3A)QBG
2) All 220v AC Wiring is to be TQ Standard F42 52
Spec Minimum tobe 1mm2 Tri - Rate Coloured: Display Controller
Multicore 67
Fuse - Brown
Neutral - Blue F43
Earth - Yellow/Green Spare
Violet 1.0mmsq
3) FUSES:
C = Ceramic
QBG = Quick Blow Glass
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
Sampling System SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL Date. 28-01-03 SAS 427/28/34/45
*
PLC Drawing Title.
DEVELOPMENT Flanshaw Way
Chkd. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire
Date. Dwg No.
WF2 9LP
POWER DISTRIBUTION
NOTES
1) Parts List Refers to coponents required for each sample point.
Solenoid Bank
1 2
2
3
Solenoid
Driver
55 Board
85
SIDE OF CONTROL PANEL
Solenoid Bank
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. Item No.1 Ammended Date. 28-01-03 SAS 427/28/34/45 Sampling System
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 Dwg No.
WF2 9LP FLAME ARRESTOR
COALESING FILTER
DRAIN VALVE
9
DRAINS MOISTURE COLLECTED IN THE
COALESCING FILTER
3-WAY VALVE
NO C
THE VALVE IS NORMALLY SET SO SAMPLE GAS
10 FLOWS THROUGH PORTS NO & C. HOWEVER TO
TEST THE SYSTEM THE POSITION OF THE VALVE
NC IS MANUALLY CHANGED SO THAT TEST GAS FLOWS
THROUGH PORTS NC & C.
12 AIR REGULATOR
CATCH POT
ALLOWS FREE PASSAGE OF AIR UNDER NORMAL
16 RUNNING CONDITIONS BUT THE OUTLET IS BLOCKED
SHOULD WATER BE DRAWN INTO THE SYSTEM.
STOP VALVE
FLAME TRAP
2,1 TO
SHOULD GAS IGNITE IN THE CABINET, THE FLAME TRAP
2,20
PREVENTS THE FLAME FROM PROPAGATING DOWN
2A AND
THE SAMPLE LINE.
2B
NC PURGE SOLENOID
PARTICULATE FILTER
AIR IN
Hydrocarbon
(Min 6 Bar Max 10 Bar)
Flame Arrestor Mounted Monitor
(See Note 4)
On Outside Of Cabinet
17 See Drg.5798A GD129
H2S 4-20mA
Sensor Gas Signal to
Vent Detector Computer
11A
Shut Off Valve See Drg.5798D 2A 11
12
3,1
Stream 1 TQ4400 CONTROL UNIT
C NC
ALARM ALARM SYSTEM
1 2 HEALTHY
17 1,1 2,1
UP DOWN SELECT MENU
NO 15
Pump Pump
13 8a
6 CPU &
5A 5B 9 8b
Display
4
2B
NC
10
NO C
C NO
17 3,20
14 16
Stream 20 NC
NOTES
1) All process connections 8mm OD 3) Pump is a single double ended pump
connected in series,See drawing 4) Air supply to be from dry
Shaft Horse Power = 1/20 HP filtered instrument air supply.
2) All numbers refer to parts list, Drg.5798N
See also drawings. 5798L & 5798M. Output = 0.1Kw
Efficiency = 65%
All system components are
Power Factor = 0.9
housed in a single enclosure,
See drawing 5798H
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
Sampling System SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. Drg No's Ammended Date. 28-01-03 SAS 427/28/34/45
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 PNEUMATIC/ Dwg No.
WF2 9LP INSTRUMENT
Drawing No:
Client: 5798J2
No: Revision: Sign: Date: Check: Date: SHINA Title:
Gas Detection/Control
SAS 427/28/34/45 Unit parts list.
1 Parts 8 + 21 Changed N.A 11-02-03 I.R 29-01-03
LEFT HAND SIDE PANEL BACK PANEL RIGHT HAND SIDE PANEL
26
23 23
19 1 2 3 1 2 3 1 2 3 1 2 3 4 5 6 7 8 9
2 1 3
9 1
8 2
7 3
6 4
R12
LED2 FS1
8 2
7 3
6 4
SOL 10 SOL 7
+
5 5
4
C6 6
CONN15 C9 CONN12 3 7
+ +
C10 2 8
1 9
R14
R15
9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1
IC5 IC4
SOL 11 SOL 6
3
CONN16
SW1
+ C8
CONN11
3
+
C2
SOL 12 SOL 5
CONN17
IC3
CONN10
31 30 31
R3
R4
R2
R6
+ +
27 28
MH5 C5 C4 MH2
LK3 TR1
SOL 13 SOL 4
R1
R5
LED1
CONN18 CONN9
+
IC1
C11
+ LK2
R10
R16
XL1 C3 R9
LK1 LK5
SOL 14 SOL 3
R11
TR2
LK4
CONN19 R7 CONN8
R8
+
C1
IC2
SOL 15 SOL 2
CONN20 CONN7
C7
+
24
R13
LED3 FS2
SOL 16 SOL 1
CONN4 CONN2
CONN21 CONN6
PSU 1
PSU 2
TQ ENVIRONMENTAL PLC 4264C0
11
25
11A
CONN3 CONN1 CONN5
LK6
MH4 MH1
0V +5V 0VS +24V 0V +24V
CONN14 CONN13
SOL 9 SOL 8
R12
LED2 FS1
3 SOL 10 SOL 7
+
RL2
TB-04 F1-F3 TB-01
C6
CONN15 C9 CONN12
+ +
C10
27 28
R14
R15
IC5 IC4
SOL 11 SOL 6
CONN16 CONN11
+ C8
SW1
6
SOL 12
CONN17
C2
IC3
+
SOL 5
CONN10
32 31 30
R3
R4
R2
8
R6
+ +
MH5 C5 C4 MH2
LK3 TR1
SOL 13 SOL 4
7
R1
R5
LED1
CONN18 CONN9
+
IC1
C11
+ LK2
R10
R16
XL1 C3 R9
LK1 LK5
SOL 14 SOL 3
R11
TR2
LK4
CONN19 R7 CONN8
R8
+
C1
SOL 15
IC2
SOL 2
27 28
CONN20 CONN7
19
RL1-RL4
C7
+
LED3 FS2
SOL 16 SOL 1
CONN4 CONN2
CONN21 CONN6
20
+24V0VS +5V 0V 0V
MH6 MH3
E
TQ ENVIRONMENTAL PLC 4264C0
5
29
31
12 14
13
9
18
16 10
18 21
NOTES
1) No's 1-17 refer to Pneumatic/Instrument parts list Drg.5798N1
2) No's 18-32 refer to Gas Detection/Control Unit parts list Drg.5798J1
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
Sampling System SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. Project Title Changed Date. 28-01-03 SAS 427/28/34/45
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title.
Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-02-03 Dwg No.
WF2 9LP GAS DETECTION/CONTROL
55
NOTES
2) QTY: 13
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
Sampling System SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. Material 316 to 316L Date. 28-01-03 SAS 427/28/34/45
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-02-03 Dwg No.
WF2 9LP SNORKEL VALVE
NOTES
1. Sample lines should have continous
fall ( or at least be Installed horizontally)
From point of entry, to sampling cabinet,
to point of sample. 'U' Bends in pipework
Gas Sampling/Control Unit to be kept to a minimum.
BULKHEAD
BULKHEAD
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
Date. Sampling System SHINA
PRODUCTION * 28-01-03 TQ ENVIRONMENTAL 1. Changed Material 316 to 316L 28-01-03 SAS 427/28/34/45
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 SNORKEL VALVE Dwg No.
WF2 9LP
MOUNTING DETAILS
CLIENT * 28-01-03 SCALE N/A
Web: http//www.tqplc.com
Email: sales@tqplc.com
App. N.D.A
Date. 11-02-03
(For Sample Points)
(Located in Ballast Tanks)
5798F2
GAS DETECTION/CONTROL PANEL
(LEFT HAND SIDE)
9 8
20 x Flame
Arrestors
20
19
18
16 1 17
70
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title.
Ballast Tank Client.
TQ ENVIRONMENTAL Date. 27-01-03 Sampling System
SAS 427/98/34/45 SHINA
PRODUCTION * 27-01-03 1. Note 2 Removed
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 13-02-03 GAS DETECTION/ Dwg No.
WF2 9LP CONTROL UNIT
105
Name Tag
50
No. W.B.T ( )
3 2 2 3
120app
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
TQ ENVIRONMENTAL Date. SAS 427/28/34/45 Sampling System SHINA
PRODUCTION * 27-01-03 1. Name Tag added 27-01-03
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 13-02-03 WELD TUBE/SHUT OFF Dwg No.
WF2 9LP
'A'
TQ4400 Ballast Tank Void Space
Gas Sampling System
'W'
1000 90 1000
942 990
160
TQ ENVIRONMENTAL PLC
Flanshaw Way, Wakefield, W Yorks
England, WF2 9LP
Tel: + 44 1924 380700
Fax: + 44 1924 361700
Email: sales@tqplc.com
website :http:// www.tqplc.com
'B' 'B'
'A'
Vent Line Exit Point Drain Mimic Panel
FIXING DETAIL
360
REAR VIEW OF
FIXING BRACKET 275
15 20
20
29
300
10
NOTES:
54
463
1) Glands: 'W' - (TPYCS - 2.5) (14.2mm OD)
526 'X' - ( MPYC - 4) ( 11.2mm OD )
589
'Y' - ( TPYC - 2.5 ) (13.5mm OD )
'Z' - ( MPYCS - 4 ) ( 11.9mm OD )
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
TQ ENVIRONMENTAL Date. 27-01-03 SAS 427/28/34/45 Sampling System SHINA
PRODUCTION * 27-01-03 1. Mounting Details Added
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 GAS DETECTION/CONTROL Dwg No.
WF2 9LP UNIT ENCLOSURE
'A'
'X'
BALLAST TANK AND VOID SPACE
'A'
5) TPYC - 2.5 = O.D 13.5mm
GAS DETECTION STATUS
'A' 'A'
ALARM
1
ALARM
2
SYSTEM
HEALTHY
WATCHDOG
'B'
H2S ALARM
'B'
'C'
'A' 'A'
TQ ENVIRONMENTAL PLC
Flanshaw Way, Wakefield, W Yorks
England, WF2 9LP
Tel: + 44 1924 380700
Fax: + 44 1924 361700
Email: sales@tqplc.com
website :http:// www.tqplc.com
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
TQ ENVIRONMENTAL Date. 27-01-03 SAS 427/28/34/45 Sampling System SHINA
PRODUCTION * 27-01-03 1. Cable Spec Changed
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 13-02-03 GAS DETECTION Dwg No.
WF2 9LP SYSTEM ELECTRICAL
1) F.P.TK (C)
2) No.1 W.B.TK (S)
3) No.1 W.B.TK (P) Brass Chain
4) No.2 W.B.TK (S) Appox. 120mm
5) No.2 W.B.TK (P)
6) No.3 W.B.TK (S)
7) No.3 W.B.TK (P)
8) No.4 W.B.TK (S)
9) No.4 W.B.TK (P)
10) No.5 W.B.TK (S)
11) No.5 W.B.TK (P)
12) No.6 W.B.TK (S)
13) No.6 W.B.TK (P)
14) No.1 UPPER STOOL SPACE
15) No.2 UPPER STOOL SPACE
16) No.3 UPPER STOOL SPACE
17) No.4 UPPER STOOL SPACE No.1 UPPER
Example Text
18) No.5 UPPER STOOL SPACE STOOL SPACE
19) No.6 UPPER STOOL SPACE
20) No.7 UPPER STOOL SPACE
Notes
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
TQ ENVIRONMENTAL Date. Sampling System SHINA
PRODUCTION * 15-08-03 15-08-03 SAS 427/28/34
PLC
DEVELOPMENT Flanshaw Way Chkd. Drawing Title. Proj No. 5798/99/800
Wakefield
SERVICE West Yorkshire Date. Shut Off Valve Dwg No.
WF2 9LP
& Tag Detail
CLIENT * 15-08-03 SCALE N/A
Web: http//www.tqplc.com
Email: sales@tqplc.com
App.
Date.
5798AU1
40
70 5
Ø9 mm
50
70
CL
NOTES:
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
TQ ENVIRONMENTAL Date. Sampling System SHINA
PRODUCTION * 28-01-03 1. Project Title Changed 28-01-03 SAS 427/28/34/45
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 28-01-03 SNORKEL VALVE Dwg No.
WF2 9LP MOUNTING
Welding
70
Pipe Clip
Ø9 mm
70
BULKHEAD
20
105
Stainless
Steel
Fixing
Srew
55
NOTES:
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
TQ ENVIRONMENTAL Date. Sampling System SHINA
PRODUCTION * 28-01-03 1. Project Title Changed 28-01-03 SAS 427/28/34/45
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 28-01-03 SNORKEL VALVE Dwg No.
WF2 9LP MOUNTING
6 145.5
6 x Ø3.5mm
No.3 UPPER STOOL SPACE
40
20
23 35 35
35 35
35 35 35 35 35 23
NOTES:
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client. HYUNDAI MIPO
TQ ENVIRONMENTAL Date. 28-01-03 SAS 427/28/34/45 Sampling System DOCKYARD CO.LTD
PRODUCTION * 28-01-03 1. Text Changed
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 Sample Line Dwg No.
WF2 9LP
Identification Label
CLIENT * 28-01-03 SCALE 1:1.2
Web: http//www.tqplc.com
Email: sales@tqplc.com
App. N.D.A
Date. 11-02-03
(Lines 17-20) 5798AR2
291
6 145.5
6 x Ø3.5mm
No.3 UPPER STOOL SPACE
20
23 35 35 35 35 35 35 35 23
NOTES:
6 145.5
6 x Ø3.5mm
40
20
23 35 35 35 35 35 35 35 23
NOTES:
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
Sampling System SHINA
PRODUCTION TQ ENVIRONMENTAL 1. Text Changed Date. 28-01-03 SAS 427/28/34/45
* 28-01-03 PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 Sample Line Dwg No.
WF2 9LP Identification Label
CLIENT
Web: http//www.tqplc.com
App. N.D.A (Lines 1-8) 5798AP2
* 28-01-03 SCALE 1:1.2 Email: sales@tqplc.com Date. 11-02-03
TBF01
LED Mounted on box lid
From RL4/2 Pin 7 W/D Output 1 Red
See Drg 5798X1 1
0V 4
TB-02 2
3
To Door 0V
Mounted LED
24V
4
5 White
3 8
RL1 RL1
2 4 1
6
Red
NOTES:-
BUZZER
1) ALL WIRING TO BE C.S.A 7/30 6
U.O.S RL1
2)PUSH BUTTON CABLE 4 TO BE
Black
CONNECTED DIRECT 7 5
TO TERMINAL 2 & 3
PUSH BUTTON
(Mounted on box lid)
Black
4
ABS Enclosure
Housing Field Terminals 160
Relay/Buzzer etc.
NOTES
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
TQ ENVIRONMENTAL Date. 28-01-03 SAS 427/28/34/45 Sampling System SHINA
PRODUCTION * 28-01-03 1. Project Title Changed
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 Dwg No.
WF2 9LP MIMIC PANEL
App. N.D.A MOUNTING ARRANGEMENT
CLIENT * 28-01-03 SCALE N/A
Web: http//www.tqplc.com
Email: sales@tqplc.com Date. 11-02-03 5798AM2
F17
24V
Red 42
CONTROL BOARD
+
RL4
-
2
Plug 7
1
Grey 170
Red 41
DISPLAY BOARD
+
RL5
-
Red 41
Conn 12 3
Conn 11 3
Grey 101
NOTES:-
1) ALL WIRING TO BE C.S.A 7/30
U.O.S
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
SHINA
PRODUCTION * 28-01-03 TQ ENVIRONMENTAL 1. F11 to F17 Date. 28-01-03 SAS 427/28/34/45 Sampling System
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 Dwg No.
WF2 9LP WATCH DOG
Red
FLAMMABLE 1
1
ALARM
R
H2S 2 Red
ALARM 2
R
SYSTEM 3 Green
HEALTHY 3
G
0V 4 Black
4
1 2
5 White
3 8
RL1 RL1
2 4 1
6
Red
BUZZER
6
RL1
NOTES:-
Black
7 5
1) ALL WIRING TO BE C.S.A 7/30
U.O.S
PUSH BUTTON
2)PUSH BUTTON CABLE 4 TO BE
CONNECTED DIRECT
TO TERMINAL 4 Black
4
FLAMMABLE ALARM
H2S ALARM
SYSTEM RUNNING
MUTE
Relay Driver Board
1 2 3 4 5 6
TBF-01 IF GREEN LIGHT DOES NOT ILLUMINATE
INVESTIGATE IMMEDIATELY
1 2
TQ ENVIRONMENTAL PLC (+44) 01924 380700
10 9 8 7 6 5 4 3 2 1
H2S Flammable
0V
4 Core 1.5mmsq Black 24V
Armoured Cable to BS6683
MS4 ( L - MPYCS - 4 )
A4804
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL Date. 28-01-03 SAS 427/28/34/45 Sampling System
*
PLC Drawing Title.
DEVELOPMENT Flanshaw Way
Chkd. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire
Date. Dwg No.
WF2 9LP
GAS DETECTION/CONTROL
130
'A' 'A'
20
'B'
FLAMMABLE ALARM
40
'B'
H2S ALARM
170
40
'B'
'C'
SYSTEM RUNNING
10
20 MUTE
10
'A' 'A'
7.5 7.5
35 35
55
NOTES
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. SAS 427/28/34/45 Client.
SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. Project Title Changed Date. 28-01-03 Ballast Tank Sampling System
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No.5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 CONSOLE MOUNTING Dwg No.
WF2 9LP MIMIC PANEL FRONT
PCB 3185K.2
TQ 4400 FRONT PANEL
IC14 CONN 1
60 Blue RESET
1
2
3 61 Violet HOLD
4
5
62 Brown SKIP
6
21
7
63 White ACK
8
N.C 9
1 0V ALARM 1 (RED)
CONN 14 64 Black
CONN 15
1 ALARM 2 (RED)
65 Yellow
2
3 SYSTEM
4 HEALTHY
66 Green (GREEN)
5
TBF-01
6 - 69 Red Watchdog
Buzzer
7 + Alarm Box
8 4
+24V 9 3
68 Red Black 21
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
TQ ENVIRONMENTAL Date. Sampling System SHINA
PRODUCTION * 28-01-03 1. Watchdog LED Added 28-01-03 SAS 427/28/34/45
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 Dwg No.
WF2 9LP FUNCTION BUTTONS
1 2 3 TBF-02
E
N L
3 Core 1.5mmsq
Screened Black
Armoured Cable
to BS6883 3 Core 1.5mmsq Screened
TI ( L - TPYC - 1.5 ) Black Armoured Cable to BS6883
TPYCS - 2.5 A4801
N L E
220V ac 60Hz
10A Main
supply
TPYC - 2.5
A0901
N L E
3 Core 1.5mmsq Screened
220V ac 60Hz Black Armoured Cable to BS6883
10A Standby TPYC - 2.5 A4802
supply
TPYC - 2.5
A1008
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
TQ ENVIRONMENTAL Date. 28-01-03 Sampling System SHINA
PRODUCTION * 28-01-03 1. Cable Spec. Changed SAS 427/28/34/45
PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
Date. 29-01-03 POWER SUPPLY/ Dwg No.
SERVICE West Yorkshire
WF2 9LP GAS DETECTION/CONTROL
See Drg.4907X
See Drg.5798T
TBF - 01 TBF - 02 TBF - 03
50 12 11 10 9 8 7 6 5 4 3 2 1 1 2 1 2 3 1 2 3 1 2 3
Common Concentration
Alarm Output For
Connection to Bridge
Alarm System
See Drg.5798T
NOTES:
1) FOR USE IF REQUIRED
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. Project Title Changed Date. 28-01-03 SAS 427/28/34/45 Sampling System
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 GAS DETECTION/CONTROL Dwg No.
WF2 9LP PANEL INPUT /OUTPUT
Drawing No:
Client: 5798AD2
No: Revision: Sign: Date: Check: Date: SHINA Title:
Power Supply Change -
SAS 427/28/34/45 Over Unit parts list.
1 Ferrite Beads Added N.A 11-02-03 I.R 29-01-03
Brown 1mmsq T/R
EMC
Input 6 Amp Suppressor ISOLATOR 'C'
Blue 1mmsq T/R
Terminals Fused Isolator A 6A
K2
Ships 44 K1 43
13 14 15
5
Main L
1
L Input to
Supply 14 13
6 33 34 16 Gas Detection
2
220V/ N N Control
60Hz 9 43 44 Unit
10A E 12
E
F1
(100mA) 36 White A2
Input 6 Amp A1 Reset 35 White
Terminals Fused Isolator B F2 (3A)
Ships
Standby 32 31 7 Note 1
3
Supply L
220V/ 4 22 21 8 14 13 36 White Red 7/30
N PSU1 Red 7/30 K1 Main
60Hz 21
21
Red 0.5mmsq 23
Red 23
Green
100uF 2
White 7/30 Part No.
901-101-035
3
Red
1
1 NC 2
2 NO 3
3 White 27
C
Tankscan
Unit
TQ120 Flammable
Sensor
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
Sampling System SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. Ferrite Beads Added Date. 28-01-03 SAS 427/28/34/45
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 POWER SUPPLY Dwg No.
WF2 9LP
CHANGE-OVER
CLIENT * 28-01-03 SCALE N/A
Web: http//www.tqplc.com
Email: sales@tqplc.com
App. N.D.A
Date. 11-02-03
UNIT CCT DIAGRAM 5798AC2
7b MAIN SUPPLY
7c STANDBY SUPPLY
7a GAS ALARM
15
RESET
14
10 3 10 11 RL1
2
4
TB-01 (See Note 2)
6
PSU1 F1 F2 K1 K2 F3 F4
5
1
11
ISOLATOR 'A' ISOLATOR 'B' ISOLATOR 'C'
TBF-01 TBF-02
E E
13
NOTES:
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
Sampling System SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. Project Title Changed Date. 28-01-03 SAS 427/28/34/45
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 POWER SUPPLY Dwg No.
WF2 9LP CHANGE-OVER UNIT
App.
CLIENT * 28-01-03 SCALE N/A
Web: http//www.tqplc.com
Email: sales@tqplc.com
N.D.A
Date. 11-02-03
INTERNAL LAYOUT
5798AB2
1 2
(1)
(60)
GD129 IR SENSOR GD129
Black 11 To Socket 3
3 4
(2)
White 3
White 2
White 4
(63) Comms
RS485 Comms To
To CPU CPU
CONN15
CONN4
5
5
3
3
1
2
6
7
8
9
1
2
6
7
8
9
MH3
3 4
2 1
2 1
9 To
CONN7
(6) Socket 2
8
3
3
To Conn 9
(65)
CONN8
Red Blk
H2S Sensor H2S
6
1
2 1
Blk Vlt To
CONN6
5
2
Socket 1
Red
4
3
3
3
CONN14
2
1
1
2
3 4 CONN1
White 5
3
CONN12
9
(3)
1
8
2
7
3
To Conn 4
3 4
2
1
(4) CONN2
Comms Red
RS485 COMMS
To Conn 7
(62) To 1
9
TO RELAY/SOLENOID Sol
2
8
BOARDS Red
To Socket 6
Board Blk
3
7
Blk
4
6
1 2
5
5
6
4
(5)
3
8
2
(64)
9
1
POWER
Power
CONN9
CONN3
MH1
MH4
CONN10
CONN13
9
8
7
6
2
1
9
8
7
6
2
1
5
3
RL
Plug/Socket 7
8 5 6
9
NOTES
1. See Drg. 5798S for wiring details
ISSUE CONTROL DATE PROJECTION C Copyright of No. Revisions. Date. Sig. Drn. P.M Project Title. Ballast Tank Client.
SHINA
PRODUCTION 28-01-03 TQ ENVIRONMENTAL 1. RL + Plug 7 Added Date. 28-01-03 SAS 427/28/34/45 Sampling System
* PLC
DEVELOPMENT Flanshaw Way Chkd. I.R Drawing Title. Proj No. 5798/99/800/6094
Wakefield
SERVICE West Yorkshire Date. 29-01-03 BTC CONTROL UNIT Dwg No.
WF2 9LP