You are on page 1of 16

This document is the property of L&T Construction and must not be passed on to any third person or firm not

authorised by us, nor be copied/made use of in full or part by such person or firm without our prior

29.06.2018 C Received As per comments GCWMP/ADB/PS/01/ICB/Works/03/2013/993 MP RSN RVS

29.11.2017 B Received As per comments GCWMP/ADB/PS/01/ICB/Works/03/2013/802 MP RSN/GPR RVS


24.08.2017 A For Approval MP ABS RVS
Design Team
DATE REV. NO. DESCRIPTION Prepared Checked
Lead

REVISIONS

L&T Construction
Water & Renewable Energy

CLIENT :

COLOMBO MUNICIPAL COUNCIL

PROJECT :
GREATER COLOMBO WASTE WATER MANAGEMENT PROJECT -Designing, Construction, Installation, and Rehabilitation of Wastewater
Pumping Stations of Colombo Municipal Council
ICB Contract No.: GCWMP/ADB/PS/01/ICB/Works/03/2013
permission writing

SUPPLIER / CONTRACTOR: L&T Construction


Water & Effluent Treatment SBG
Job No LE150572

TITLE :
NAME SIGN DATE
PRED MP MP 24.08.2017
CHKD ABS ABS 24.08.2017 CENTRAL CONTROL STATION AT MALIGAKANDA DESIGN REPORT
Design
RVS RVS 24.08.2017
Team Lead

RELEASED FOR PRELIMINARY ENQUIRY INFORMATION  APPROVAL CONSTRUCTION

#  Sensitivity: Unclassified
INSTRUMENTATION DESIGN OF PUMPING STATIONS
LTCD/GCRW-
GCWMP/ADB/PS/01/ICB/Works/03/2013/802 L&T Letter L&T Letter Reference Dated: 28.11.2017 &
Reference WET/WW/MSD/CMS/1262 dated Revision: B
dated 19th September 2017 Reference 15.03.2017
25th August 2017
Page/
Comment
Client / Consultant Comment drawing Contractor Answer Client / Consultant Comment Contractor Answer
no
no.
We accept the use of GSM network for dat transfer Based on the demonstration on 12th February
1 between pump stations and central control at Pg. 6 of 14 Noted. 2018, we accept the proposed system. Noted & Point Closed.
Maligakanda.
Please provide the past experiemce regarding the Based on the demonstration on 12th February
ELPRO-615-M1 modem/router operation for data 2018, we accept the proposed system.
Noted. End user name & contact
transfer in Srilanka with customer details. If not used in
details are given;
srilanka please arrange data transfer delay.
2 Pg. 6 of 14 Mr. Mahesh Aberathna - Electrical Noted & Point Closed.
Engineer - Eastern Project
(NWS&DB) Mobile No: 0718162527.

Indicate the expected data transfer delay. M/s ELPRO confirmed that, there will Is not the delay due to equipment
Noted. Transfer delay is
not any delay due to equipment performances we wanted to clarify. It is the
3 Pg. 6 of 14 depends on signal health of
performance. time taken to transfer data from one station to
service provider.
another.
Please provide the indicative cost for data transfer and
M/s ELPRO checked the same with
all associated services for the first three years of
DIALOG and the approximate
4 operation. (for 14 pumping stations and one central Pg. 6 of 14 Noted Point Closed.
monthly charges may come around
control) - indicating the cost including the cost CMC
1500lkr/pumping station.
will have to bear after taking over.
Indicate if the data transfer if through a dedicated web
server or direct from point to point. If a dedicated
Yes. Data transfer shall be direct
5 server is required indicate the proposed arrangement Pg. 6 of 14 Noted Point Closed.
from point to point.
and cost including any cost associated with domain
and hosting.
Software - The list of software is not complete. There We can not accept the software list. It is As per discussion on 14.0518,
are other software applicable for the equipment such necessary to provide all necessary software Provided all the required
as VFD diagnosis. All the software required for system
applicable for the central control room and softwares to operate the
6 Pg. 7 of 14 performance are considered
pump stations. With the little information system and to set the
including VFD diagnosis.
supplied up to now we cannot conclude the parameter for SCADA
total requirement. monitoring.
What is meant by the quantity against software? If it is
Same is applicable for the quantity of software.
the number of stations, the quantity need to be Noted. We are providing
Please note that both servers shall have
changed. separate softwares for both
Softwares quantity shall be provided identical software and hardware configuration
7 Pg. 7 of 14 servers with password
for Central control room. with pass word controlled login. So as a
protection. Minimum software
minimum software shall run simultaneously in
will work simultaneosuly.
both servers.

 Sensitivity: LNT Construction Internal Use
#
General Comments
Proposed loyout with space
requirement is attached here with.
Indicate the space requirement for the central SCADA We will check the space availability and inform
8 Please check and confirm the Noted.
room with proposed layout. you soon.
location and arrangments to
proceed.
All SCADA screens should be submitted for As per discussion on 14.05.18,
approval before configuration. The P&ID is the wannathamulla &
Noted.CCR SCADA screen and basis for the SCADA screens. P&ID’s are not bampalapitiya P&ID got
Please submit SCADA screen design for the central
Wanathamulla pumping station HMI yet finalized for the pump stations as some of approved. Inline with that we
control room and one pump station indicating
9 screen shot is enclosed. Any the information are not available for the have developed SCADA
navigation and options for parameter adjustment. (use
changes required shall be done packaged type equipment. Therefore please screen for all pumping station
wanathamulla pump station as sample)
before commisiong of the same. submit finalized P&ID with correct tag numbers for your review & Approval.
for the items in packages.
Polwatta Pumping Station
Please add Polwatta Pump Station to the
SCADA screen design is
10 Central monitoring sation scope( Page 6,10 of
included in Central Monitoring
21)
Station.
We cannot accept SCADA screen for the
SCADA screen for the central
central control station. Each pump station
control station Pumping station
should appear on a diagram representing the
11 wise prepared and submitted.
sewage collection network. Current key data on
The Plant key parameters
each pump station should be displayed on the
shown in home page.
home page.( Page 20 of 21)
We cannot accept SCADA screen for As per discussion on 14.05.18,
Wanathamulla Pump Station. The screen wannathamulla &
should be based on approved P&ID. However bampalapitiya P&ID got
12 components such as pressure gauges need not approved. Inline with that we
appear. All information on each equipment have developed SCADA
should appear. Direct indication / navigation screen for all pumping station
should be provided.( Page 21 of 21) for your review & Approval.

 Sensitivity: LNT Construction Internal Use
#
  L & T Construction 
Water & Effluent Treatment IC
 
DOCUMENT NO. &
REVISION DATE:
GREATER COLOMBO WASTE WATER LE150572-I-WW-SW-CR- 29.06.2018
PROJECT:
MANAGEMENT PROJECT MAD-5001 & R - C
DSIGN TEAM
CENTRAL SCADA STATION AT PREPARED CHECKED
TITLE: LEAD
MALIGAKANDA DESIGN REPORT
MP RSN RVS

CENTRAL SCADA STATION AT


MALIGAKANDA DESIGN REPORT

Sensitivity: LNT Construction Internal Use 
  L & T Construction 
Water & Effluent Treatment IC
 
DOCUMENT NO. &
REVISION DATE:
GREATER COLOMBO WASTE WATER LE150572-I-WW-SW-CR- 29.06.2018
PROJECT:
MANAGEMENT PROJECT MAD-5001 & R - C
DSIGN TEAM
CENTRAL SCADA STATION AT PREPARED CHECKED
TITLE: LEAD
MALIGAKANDA DESIGN REPORT
MP RSN RVS

INDEX

SI. NO. TITLE SHEET NO.

1 Index Sheet 02

2 Central Control SCADA Station 03

3 ICA Panel 05

4 GSM Modem 05

5 Software’s 05

6 System Configuration drawing 06

7 GSM Modem Catalogs 07

8 Proposed Control room Layout 14

Sensitivity: LNT Construction Internal Use 
  L & T Construction 
Water & Effluent Treatment IC
 
DOCUMENT NO. &
REVISION DATE:
GREATER COLOMBO WASTE WATER LE150572-I-WW-SW-CR- 29.06.2018
PROJECT:
MANAGEMENT PROJECT MAD-5001 & R - C
DSIGN TEAM
CENTRAL SCADA STATION AT PREPARED CHECKED
TITLE: LEAD
MALIGAKANDA DESIGN REPORT
MP RSN RVS

1. SCADA CENTRAL STATION:

a. Introduction

SCADA is ‘Supervisory Control and Data Acquisition’. The major function of


SCADA is for acquiring data from remote devices such as valves, pumps,
transmitters etc. and providing overall control remotely from a SCADA software
platform.

This provides process control locally so that these devices turn on and off at
the right time, supporting your control strategy and a remote method of
capturing data and events (alarms) for monitoring these processes. SCADA
platforms also provide functions for graphical displays, alarming, trending and
historical storage of data.

Instrumentation, ICA PLC control works at the following pumping stations and
central SCADA station at Maligakanda office, CMC Central Control room
purpose is to Monitor the pumping stations are located in different below
mentioned locations,

1. Wanathamulla PS

2. Vystwyke PS

3. Bampalapitiya PS

4. Thimbirigasyaya PS

5. Maligawatta PS

6. St. John´s Market (CS3) PS

7. Slave Island

8. Borella PS

Sensitivity: LNT Construction Internal Use 
  L & T Construction 
Water & Effluent Treatment IC
 
DOCUMENT NO. &
REVISION DATE:
GREATER COLOMBO WASTE WATER LE150572-I-WW-SW-CR- 29.06.2018
PROJECT:
MANAGEMENT PROJECT MAD-5001 & R - C
DSIGN TEAM
CENTRAL SCADA STATION AT PREPARED CHECKED
TITLE: LEAD
MALIGAKANDA DESIGN REPORT
MP RSN RVS

9. Harbor PS

10. Fort PS
There are three additional pump stations which will be operating along with the
above mentioned pumping stations. They are included under the scope of this
Kirlupone Project. They are as follows:
11. Kalinga Mawatha Pump Station

12. Thalakotuwa Pump Station

13. S-8 Pump station

Refer to system configuration drawing No LE150572-I-WW-SW-CR-MAD-5002, R - B

Following equipment’s are considered in the Centre control room at


Maligakanda for monitoring the individual Pumping station operations,

i) Instruments are provided at each pumping station as indicated in the


P&ID
ii) ICA (Instrumentation, Control and Automation) panel with control PLC
and HMI (Touch Panel) at each pumping station
iii) GSM modems (ELPRO) at each pump station and at central control
room for two way data communication between all stations with suitable
accessories.
iv) Central control room equipment including,
a) Two work stations facilitating operator log-in and Engineer log-in
with user pass word control.
b) Laptop computer configured as Portable Engineering Station with
suitable SCADA software / PLC Programming software and HMI
Configuration software.
c) Asset management computer with access to the printers.
d) UPS with 20 Min. backup.

Sensitivity: LNT Construction Internal Use 
  L & T Construction 
Water & Effluent Treatment IC
 
DOCUMENT NO. &
REVISION DATE:
GREATER COLOMBO WASTE WATER LE150572-I-WW-SW-CR- 29.06.2018
PROJECT:
MANAGEMENT PROJECT MAD-5001 & R - C
DSIGN TEAM
CENTRAL SCADA STATION AT PREPARED CHECKED
TITLE: LEAD
MALIGAKANDA DESIGN REPORT
MP RSN RVS

e) One 52 inch wall mounted LED screen for demonstrations.


f) Three printer, one dot matrix type, one color (A3) one laser jet.

2. ICA PLC PANEL (ICA)

ICA PLC is the main component in HMI system that has a direct connection with
Transmitters, valves and motors associated with a control device.

These ICA’s are nothing but real-time programmable logic controllers


(PLCs) which are responsible for properly converting remote station information
to digital form for GSM modem to transmit the data and also converts the
received signals from master unit in order to control the process equipment.

3. GSM MODEM

GSM (Global System for Mobile Communication) router is considered at each


pumping station and at central control room for two way data communication
between all stations with suitable accessories.

4. SOFTWARES FOR CCR

1. Vijeo Citect SCADA Software – 1No


2. Unity Pro – 1No
3. Viejo Designer – 1No
4. MS Windows – 3No’s
5. Asset Management Software – 1No
6. CAT Electronic Technician 2017C V1.0

Sensitivity: LNT Construction Internal Use 
  L & T Construction 
Water & Effluent Treatment IC
 
DOCUMENT NO. &
REVISION DATE:
GREATER COLOMBO WASTE WATER LE150572-I-WW-SW-CR- 29.06.2018
PROJECT:
MANAGEMENT PROJECT MAD-5001 & R - C
DSIGN TEAM
CENTRAL SCADA STATION AT PREPARED CHECKED
TITLE: LEAD
MALIGAKANDA DESIGN REPORT
MP RSN RVS

CENTRAL CONTROL STATION SYSTEM


ARCHITECTURE AT MALIGAKANDA

Sensitivity: LNT Construction Internal Use 
615M-1 Multi-Service Provider Cellular Modem and Router
Wide Area Ethernet/Serial Connectivity Solution

Applications
• Networking Wind Turbines and • Tank Farm Monitoring
Solar Collectors • Water Distribution Network
• Electricity Network Control • Environmental Monitoring

Specifications
Transmitter/Receiver
Frequency Quad-band 850/900/1900/2100MHz/AWS(1,2)
Quad-band 850/900/1800/1900MHz(3,4)
Description 800MHz Cellular/1900MHz PCS/2100MHz(5)
800MHz Cellular/1900MHz PCS/2100MHz(6)
The ELPRO 615M-1 is a powerful Multi-Service Provider Cellular Broadband 800MHz Cellular/1900MHz PCS(7)
Router that delivers wireless data connectivity for up to two LAN connections and
Transmit Power (Max) 250mW(1,2); 2W(3,4); 250mW(5,6,7)
one serial port through public cellular networks at 3G network speeds. UMTS
technology leverages high-speed HSPA to provide data access at speeds up Transmission UMTS, HSPA, EDGE, GPRS, EVDO Rev A (IS-856-A), 1xEVDO
to 14.4Mbps with backward compatibility to GSM’s EDGE and GPRS. CDMA Rev 0 (IS-856), 1xRTT (IS-2000)
technology leverages high-speed EV-DO Rev A to provide data access at speeds Modulation UMTS, HSPA, EDGE, GPRS, EVDO Rev A (IS-856-A), 1xEVDO
up to 3.1Mbps with backward compatibility to EV-DO Rev 0 and CDMA 1 x RTT. Rev 0 (IS-856), 1xRTT (IS-2000)
Receive Sensitivity -109dBm(1); -109dBm(2); -105dBm(3,4); -107dBm(5,6,7)
It provides real-time redundancy between Carriers in case of a network failure, Channel Spacing 5MHz(1,2); 10MHz(2); 1.25MHz(5,6,7)
reliable connectivity for Programmable Logic Controllers (PLC’s), Remote Terminal
Data Rate Downlink up to 384kbps; Uplink up to 384kbps(1)
Units (RTUs), Ethernet web cameras or any other Ethernet connectivity device.
Downlink up to 14.4Mbps ; Uplink up to 5.76Mbps(2)
The ELPRO 615M-1 features an integrated DHCP server, port forwarding and Downlink up to 236kbps; Uplink up to 236kbps(3)
port mapping capabilities. Downlink up to 115kbps; Uplink up to 115kbps(4)
Downlink up to 3.1Mbps; Uplink up to 1.8Mbps(5)
Downlink up to 2.4Mbps; Uplink up to 153.6kbps(6)
Product Features Downlink up to 153.6kbps; Uplink up to 153.6kbps(7)
• Multicarrier Protocols: GPRS/EDGE, UMTS/HSPA; EVDO Rev0/A, 1xRTT Range (LoS) Cellular depends on service provider
• Receive Antenna Diversity Antenna Connector 2 x Female SMA Standard Polarity(1,2,3,4,5,6,7)
• Client and Router Configuration Input/Output
• TCP/IP Packet Assembler/Dis-assembler for Serial Devices Discrete Input ON 2.3Vdc, OFF 0.7Vdc, 5.5Vdc max
• Internal PPTP VPN Server and Client Discrete Output NPN Transistor close to Digital Ground, Pull down 100ohm
• IPsec, GRE Tunneling, PPTP, VPN, RADIUS/802.1x Relay Outputs Max voltage 30Vdc, Max current 1A
• Built-in DHCP Server and Port Forwarding Analog Inputs Voltage input range 0 – 30Vdc, Accuracy +/-0.2Vdc
• MAC and IP Address Filtering Ethernet Port
• ARP/GARP Filtering – Whitelist/Blacklist Ethernet Port 10/100baseT; RJ45 Connector – 2 x IEEE 802.3 (auto MDIX)
• Dual 10/100baseT IEEE 802.3 Ethernet Link Activity Activity LED
• RS-232 Serial Port Note: Specifications subject to change.
1) UMTS
• Analog I/O and Digital I/O 2) HSPA
• Over-The-Air Network Diagnostics and Configuration 3) EDGE
4) GPRS
• Auto-Redial for Always-On Connection 5) EVDO Rev A (IS-856-A)
• USB Configuration and Firmware Programming 6) 1xEVDO Rev 0 (IS-856)
7) 1xRTT (IS-2000)
Continued on back.

©2012 Cooper Bussmann


www.cooperbussmann.com/wireless

0712 BU-SB11857 Page 1 of 2 Data Sheet # 7925


615M-1 Multi-Service Provider Cellular Modem and Router
Wide Area Ethernet/Serial Connectivity Solution

Specifications Ordering
Serial Port To order, select product code from the table and specify country of application.
RS232 DB9 Female DCE
Product Code Description Frequency RF Power
Data Rate (Bps) 1200, 2400, 4800, 9600, 14400, 19200, 38400, 57600,
615M-1 Cellular Modem and Router Quad-band Up to 2W
76800, 115200bps
Supplied with BR-615-DINCLIP
Serial Settings 8 Data Bits; No Stop/1 Start/Parity (Configurable)
Note: Available RF power and frequency may vary depending on country of application.
Protocols and Configuration
Protocols Supported TCP/IP, UDP, ARP, ICMP, FTP, TFTP, TELNET, PING, GPS-
NMEA (optional), DHCP; MAC Filtering (Whitelist),
Accessories
IP Filtering (Blacklist), DMZ, Dynamic DNS, Port Forwarding;
SNMP, HTTP embedded web server; IPsec, GRE Tunneling, The following accessories can assist with compatibility when commissioning.
PPTP, VPN, RADIUS/802.1x
Product Code Description Data
User Configuration Configuration and Firmware upgrades via HTTP/OTA (Over-the-Air)
Sheet #
Configurable Client/Router, Serial Client Server
Antennas - Cellular
Parameters Simultaneous RS232/485 connection
Security VPN, SIM Card PIN, RADIUS, IPsec WHGSM-3 Cellular Antenna - 130mm (5”), SMA Male, Magnetic 7941
Base Mount, 2dBi gain
Bandwidth Protection MAC Address – Whitelist/Blacklist, IP Filtering – Whitelist/Blacklist
Cables
Network Management SNMP V2c, V3
CC3/10-SMA Coaxial Cable Kit - 3m (9.8’)/10m (32’), N-type to SMA 7932
LED Indication/Diagnostics 7947
LED Indication RSSI; SVC; NET; GPS; AUX CCTAIL-SMA-F/M Coaxial Cable Tail - 600mm (24”), SMA to N-type 7951
Please refer to product manual for further information Female or Male
Reported Diagnostics Diagnostics available through web pages SER-RJ45 Configuration Cable - RS232 Serial, DB9 Female to RJ45 7956
Compliance ETH-C5X Ethernet Cable - 1.8m (6’), Crossover, RJ45 to RJ45 7952
EMC FCC Part 15; Industry Canada; CE; A-Tick ETH-C5A Ethernet Cable - 1.8m (6’), Direct, RJ45 to RJ45 7953
RF (Radio) EN 300 328; FCC Part 15 Surge Diverters
Hazardous Area Class I, Division 2 CSD-SMA-2500 SMA Surge Diverter for use with CC10, CC20 - SMA 7959
Safety IEC 60950-1 CSD-N-6000 Coaxial Surge Diverter, Bulkhead N Female to N Female 7960
UL UL Listed IOP32D Signal Surge Diverter - 2 wire/4 wire 7961
Environmental MIL-STD-810F Power Supplies
Approvals PTCRB, Carrier Specific Approvals PS-WW-XP 100Vac Input Power Supply 7934
General PS-DINAC-12DC-OK DIN Rail Power Supply, 100 - 250Vac, 12Vdc/2.5A 7935
Size 109 x 153 x 45mm (4.3” x 6” x 1.8”) PS-DINAC-24DC-OK DIN Rail Power Supply, 100 - 250Vac, 24Vdc/2A 7958
Housing Powder-coded Aluminum Mounting Brackets
Mounting DIN Rail, Panel Mount (optional) BR-615-DINCLIP DIN Rail Mount Kit for 615M-xx Series 7986
Terminal Blocks I/O: Removable terminal block, Screwless-Push in wire, 18 - 28AWG BR-615-PLATE Panel Mounting Plate Kit: for 615M-xx Series 7987
Temperature Rating -30 to +70°C; -22 to +158°F
Humidity Rating 5 – 95% RH Non-condensing
Weight 1.13kg (2.5lb)
Power Supply
Nominal Supply 9 to 28Vdc; Under/Over Voltage Protection and Reverse Polarity
Molex 43025-0400 4-pin locking connector
Average Current Draw 130mA @ 13.8Vdc (Idle)
Transmit Current Draw 350mA @ 13.8Vdc
Note: Specifications subject to change.

The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehen-
sive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of
any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.

©2012 Cooper Bussmann


www.cooperbussmann.com/wireless

0712 BU-SB11857 Page 2 of 2 Data Sheet # 7925


CC3-N/SMA Coaxial Cable
Pre-terminated Cable for Easy Commissioning

Specifications
Termination
Antenna N-type Male
Module N-type Male(1), SMA Male(2)
Loss
150MHz 0.6dB
220MHz 0.8dB
450MHz 1.0dB
900MHz 1.0dB
2.4GHz 2.0dB
5GHz 4.0dB
General
Length 3m (9.8ft)
Description
Note: Specifications subject to change.
The CC3 is a pre-terminated 3m (9.8’) length of RG58 cellfoil coaxial cable 1) CC3-N
which delivers easy integration with ELPRO products and/or other accessories 2) CC3-SMA
such as bulk head or in-line surge arrestors.

ELPRO also offers longer length cables. Installations requiring longer lengths Ordering
than the CC20 can offer and at higher frequencies are best suited to low-loss
To order, select product code from the table and specify country of application.
RG213, LDF4 and LMR400 cables. Use a CCTail to connect large diameter
cables to the module to avoid damage to the connector. Product Code Description
CC3-N Coaxial Cable Kit - 3m (9.8’) N-type to N-type
CC3-SMA Coaxial Cable Kit - 3m (9.8’) N-type to SMA

Product Compatibility
Please refer to product datasheets for compatibility details to suit your application.

The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product
data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper
Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.

©2013 Cooper Bussmann


www.cooperbussmann.com/wireless

0313 BU-SB13091 Page 1 of 1 Datasheet: 7932


CSD-SMA-2500 Surge Diverter
SMA Coaxial Cable Power Surge Protection

Specifications
Parameters
Frequency < 2.5GHz
Insertion Loss <0.2dB
Max RF Power 37W
VSWR 1.20:1
Impedance 50Ohms
Max Discharge Current 40kA (8/20us)
Connectors SMA Male - SMA Female
General
Size 41mm x 22mm (1.6” x 0.9”)
Description Housing Plated Brass

The CSD-SMA-2500 Surge Diverter is a low insertion loss for applications Mounting In-line between ELPRO product and coaxial cable
up to 2.5GHz. This in-line surge arrestor has SMA male and SMA female Weight 100g (3.5oz)
connectors and fitted 6mm2 earth cable, that protects the module from the Note: Specifications subject to change.
impact of lightning/transients via the antenna port.

The CSD-SMA-2500 is designed to be connected directly to the antenna port Ordering


allowing simple installation or retrofit. To order, select product code from the table and specify country of application.
Used with the CC3, CC10, CC20 SMA male to N-type male coaxial cable kits, Product Code Description
allows connection to ELPRO products with SMA female/male antenna connector. CSD-SMA-2500 SMA Surge Diverter for use with CC3, CC10, CC20-SMA

Note: Transient devices rely on good earthing practices to be effective. This


product assumes both a metallic enclosure and good earth connection to Product Compatibility
the enclosure. If in doubt, apply another earth under the locknut to create a The following products are compatible with this accessory. Please refer to
sufficient Earth. product datasheets for compatibility details to suit your application.

Also note: In applications of high vibration, it is recommended to use Product Code Description Data Sheet #
CSD-N-6000 Surge Diverter.
CC3-SMA Coaxial Cable Kit - 3m (9.8’)/10m 7932
CC10-SMA (32’)/20m (65’), N-type to SMA 7947
Warning: Do not stand near or touch operating equipment during an electrical CC20-SMA 7948
storm as the CSD-SMA-2500 will not protect personnel.
CCTAIL-SMA-F Coaxial Cable Tail - 600mm (24”), 7951
N-type Female to BNC/SMA Male

The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product
data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper
Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.

©2013 Cooper Bussmann


www.cooperbussmann.com/wireless

0413 BU-SB13108 Page 1 of 1 Datasheet: 7959


PS-DINAC-12DC-OK Power supply
Universal power supplies for ELPRO products

The PS-DINAC-12DC-OK Power Supply is a DIN rail mounted power Compatible with:
supply, able to be used worldwide with universal 85 to 264VAC input. This
product has UL/ CUL/ TUV/ CB and CE approvals and is NEC Class 2
compliant.

ELPRO TECHNOLOGIES
Industrial Wireless Technology
Technical Specifications
Title: Details:
Ordering Information
Please specify the below details when ordering:
Input: 85 - 264VAC, 50-60Hz
PS-DINAC-12DC-OK 12VDC version
Output: 12VDC, 5A
DC OK Relay Contact

© ELPRO Technologies Elp_acc_PS-DIN-12DC_V2.0


Mounting: T-section DIN rail (35/7.5 or 15mm)
Product Compatibility
Weight: 330g
The PS-DINAC-12DC-OK Power Supply product can be
Dimensions: 40mm x 90mm x 100mm used with the following ELPRO products:

Please note: This product can be used on 5W licensed units • All ELPRO Products
without a battery.
(Cannot be used with ELPRO 505U, 505U-K, 905U-K and
915U-K products).

Note: ELPRO Technologies supplies accessories as needed. Every attempt is made to ensure accuracy of third party technical specifications and this
brochure is correct at time of publishing. ELPRO does not accept liability for changes to technical specifications outside of its control.

Technologies

THINK WIRELESS... THINK ELPRO

Contact ELPRO Technical Support: Regional Offices:


Web site www.elprotech.com USA/Canada +1 866 713 4409 Americas + 1 619 741 3574 Europe + 49 15222 722 642
E-mail ELPRO-sales@cooperindustries.com Other countries +61 7 3352 8624 Australasia + 61 7 3352 8600 China + 86-21 2899 4109
Technical Data TD032068EN Effective January 2014

SGNEXTG-GSM-6 Antenna
Antenna for use with ELPRO cellular products

Description
The SGNEXTG-GSM-6 Antenna is a ground-independent multiband
cellular antenna suitable for wireless cellular applications where
signal strength is poor and additional antenna gain is required.
Vertically polarized with an omnidirectional radiation pattern, the
antenna is equipped with a fiberglass/aluminum radome and a
stainless steel mounting point.

Securely mount the antenna with the provided ferrule and locknut, or
with the provided pole mounting kit.

Specifications
SPECIFICATION DESCRIPTION
Parameters
Frequency 825–960 MHz, 1710–2190 MHz
Gain 6.2 dBi (825–960 MHz)
3 dBi (1710–2190 MHz)
Bandwidth 135 MHz at center frequency (825–960 MHz)
480 MHz at center frequency (1710–2190 MHz)
VSWR <1.6:1 across each band
Polarization Vertical
H-plane Omnidirectional
E-plane 32°
Termination
Termination N-Type female on 7.9" (200 mm) RG-58 coaxial cable
General
Size 31.4" (800 mm)
Housing Fiberglass/aluminum
Mounting Aluminum ferrule, secured to bracket with 0.5" (12.7 mm) hole
and supplied locknut
Weight 1.5 lbs (700g)
Wind loading 10.1 lbs (4.6 kg) at 99 mph (160 km/h)

NNote: Specifications are subject to change.

Ordering
PRODUCT CODE DESCRIPTION FREQUENCY
SGNEXTG-GSM-6 Cellular antenna, N-type female
6.2 dBi gain 825–960 MHz
3 dBi gain 1710–2190 MHz

Product Compatibility
PRODUCT CODE DESCRIPTION DATA SHEET
CC3-N/SMA Coaxial cable kit, 9.8' (3m), N-type SMA TD032019EN
CC10-BNC/N/SMA Coaxial cable kit, 32.8' (10m), N-type SMA TD032020EN