1. GENERAL
------------------------------------------------------------------------------------------------- 1
1.1 Scope ------------------------------------------------------------------------------------------- 1
1. GENERAL
1.1 Scope
This specification shall apply to the design requirements and material of steel structures
except handrails, platforms, ladders, stairs, etc. which are furnished as accessories of the
process equipment such as towers, tanks, etc.
2.1 Code
Unless otherwise specified, metric Celsius and kilogram units shall be applied as the
measurement system for drawings and documents to be submitted.
2.4 Units
Unless otherwise specified, metric Celsius and kN units shall be applied as the
measurements system for drawings and documents to be submitted.
ENGINEERING SPECIFICATIONS
SSD0003EJE
STEEL STRUCTURE DESIGN
ISSUED:2013.07.31 PAGE 3 OF 7
3. Design Loads
The design loads shall be basically applied as described in the GENERAL DESIGN CRITERIA FOR
CIVL & STRUCTURAL WORK specification (SSD0010EAN).
Load
Term of combination
Loading condition Combination Remark
loading
factor
(See note 1)
Long-term Normal operation D + L + Eqo + Po + Cr + V + T 1.0
Erection D + Eqe + Pe + W 0.75 Not
applicable for
Short-term Hydraulic test D + L + Eqt + Pt + 0.25W 0.75 normal type's
piperack
Wind D + L + Eqo + Po + V + T + W 0.75
Load
Term of combination
Loading condition Combination Remark
loading
factor
(See note 1)
Long-term Normal operation 1.2(D + Eqo + Po + T) + 1.6(Cr + L + V) N/A
0.9(D + Eqe + Pe) + 1.3(0.5W)
Erection N/A Not
0.9(D + Eqe + Pe) + 1.0E applicable for
1.2(D + Eqt + Pt) + 1.3(0.5W) + L normal type's
Short-term Hydraulic test N/A piperack
1.2(D + Eqt + Pt) + 1.0E + L
1.2(D + Eqo + Po + T) + 1.3W + L + V
Wind N/A
1.2(D + Eqo + Po + T) + 1.0E + L + V
W ; Wind force
Eqo ; Operating equipment load
Eqe ; Erection load of equipment
Eqt ; Test load of equipment
Po ; Operating pipe load
Pe ; Erection load of pipe
Pt ; Test load of pipe
Cr ; Handling device load (Equipment load and lifting load)
V ; Vibration load
T ; Loads, forces and effects due to contraction or expansion
resulting from temperature changes, shrinkage, moisture
change creep in component materials, movement due to
differential settlement or combination thereof.
(Note 1)
The total of combined load effects may be multiplied by load combination factors.
An increase in the allowable stresses will not be allowed in conjunction with a decrease
due to the above load combinations.
(Note 2)
For equipment test load shall be considered as dead load.
For equipment operating load shall be considered as dead load.
4. Design Requirements
4.1 Deflection
4.1.1 Unless otherwise specified, the following criteria for the deflection shall be adhered to
for the normal operation and test load combination.
(1) Wall stanchions less than 1/300 of the height and 2.5cm
(2) Purlins and girths less than 1/150 of the span
(3) Beams and girders supporting floors less than 1/300 of the span and 2.5cm
(4) Cantilevered girders less than 1/250 of the span and 2.5cm
(5) Grating and floor plate less than 6mm
ENGINEERING SPECIFICATIONS
SSD0003EJE
STEEL STRUCTURE DESIGN
ISSUED:2013.07.31 PAGE 5 OF 7
4.1.2 The deflection of girders for travelling cranes, depending on types, shall be as follows
for the span of the girders.
(1) Hand-operated crane less than 1/500 of the span
(2) Light electric crane of 60 m/min less than 1/800 of the span
and below in travelling speed:
(3) Normal electric crane of 90 m/min less than 1/1000 of the span
and below in travelling speed:
(4) Normal electric crane of above less than 1/1200 of the span
90 m/min in travelling speed,
crane for steel manufacturer, etc.:
4.2.1 The lateral displacements due to the load combinations including wind or seismic
loads shall not exceed the bellows ;
(1) Piperacks less than h/180
(2) Equipment Structures less than h/180
(3) Occupied Buildings less than h/200
4.3.3 Neither the floor plate nor grating flooring shall be considered as offering lateral restraint to
beams
5. DESIGN DETAILS
5.1 Flooring
5.1.1 Galvanized grating flooring shall be used for floors including stairs, walkways and
platforms on pipe rack and other parts.
ENGINEERING SPECIFICATIONS
SSD0003EJE
STEEL STRUCTURE DESIGN
ISSUED:2013.07.31 PAGE 6 OF 7
5.1.2 The other material for flooring, such as checkered plate, expanded metal, etc,. shall be
used for floors, if specified in the detail drawings.
5.2.3 Opening in grating for pipes shall be large enough to accommodate pipe flange.
5.2.4 Platforms, except tower wing platforms, shall be framed with straight structural
members and shall be designed for the loads specified.
5.3 Stairways
5.3.1 Stairs shall be 750mm(sub stair) and 900mm (main stair) wide and shall be
constructed of standard channel stringers.
5.3.2 Stair treads shall have a theoretical width and rise as follows.
(1) width ; no less than 225 mm
(2) rise ; not more than200 mm
5.3.3 Minimum vertical headroom clearance shall be 2300mm and minimum perpendicular
clearance shall be 1800mm.
5.3.4 The maximum vertical run for a single flight of stairs shall be 4500mm.
5.3.5 Stair landings shall preferably be minimum 900mm wide but not less than the width
of the respective stairs.
5.3.6 Where doors open into a platform, provide a 750mm minimum width clear of door
swing on landing in front of doors.
4.3.7 Stair treads shall be galvanized steel grating with visible edge safety nosing.
5.4 Ladders
5.4.1 Ladders shall be 450mm wide and shall be constructed of minimum 19mm in diameter
steel bars welded at every 300mm space to flat bar or angle side rails.
5.4.2 Ladders exceeding 9m of straight run shall be provided with intermediate landings
ENGINEERING SPECIFICATIONS
SSD0003EJE
STEEL STRUCTURE DESIGN
ISSUED:2013.07.31 PAGE 7 OF 7
5.4.3 Ladders higher than 4.5m above grade and in an exposed position shall be
provided with a 750mm diameter safety cage.
5.4.4 Ladder access openings shall be provided with a safety chain or bar.
5.4.5 Headroom clearance under cages shall be minimum 2.1m and maximum 2.4m from grade
or platform level.
5.5 Handrails
5.5.1 Stairways, platforms and walkways shall be provided with handrails consisting of
toe plates (except the part of the stair stringers).
5.5.2 Toe plates shall likewise be provided on the edge of platforms at access openings
and equipment opening where no handrail is provided.
5.5.3 Handrails shall be designed for a minimum concentrated load of 50kg applied at any point in
any direction on the top rail.