Professional Documents
Culture Documents
performance
Technical
Building acoustics
C02
Building acoustics is the science of controlling noise in
buildings, including the minimisation of noise transmission The Building Regulation requirements regarding the
from one space to another, and the control of noise levels sound insulation of walls and partitions only relate to the
and characteristics within a space. transmission of airborne sounds. These include speech,
musical instruments, loudspeakers and other sounds that
Noise can be defined as sound that is undesirable, but it can originate in the air. In most cases, floors must also resist the
be subjective and depends on the reactions of the individual. transmission of impact sounds, such as heavy footsteps and
When a noise is troublesome, it can reduce comfort and the movement of furniture.
efficiency. If a person is subjected to noise for long periods, it
can result in physical discomfort or mental distress. Within Indirect paths (flanking transmission)
homes, a noisy neighbour can be one of the main problems Flanking sound is defined as sound from a source room that
experienced in attached housing. It’s estimated that up to is not transmitted via the separating building element. It is
300,000 people in Ireland have had their lives disturbed by transmitted indirectly via paths such as windows, external
noisy neighbours. walls and internal corridors. Refer to figure 1.
The best defence against noise is to ensure that proper It is imperative that flanking transmission is considered at
precautions are taken at the design stage and during the design stage and construction detailing is specified so as
construction of the building. The correct acoustic climate to eliminate or at least to minimise any downgrading of the
must be provided in each space, and noise transmission acoustic performance. The sound insulation values quoted
levels should be compatible with the building’s usage. in system performance tables are laboratory values and
Retrofitted remedial measures taken after occupation can be the practicalities of construction will mean that acoustic
expensive and inconvenient. performances measured in the laboratory will be difficult to
achieve on site.
The term ‘building acoustics’ covers both sound insulation
and sound absorption. One of the main reasons for this difference is the loss of
acoustic performance via flanking transmission paths. Good
Sound insulation detailing at the design stage will minimise this effect and
optimise the overall levels of acoustic privacy achieved.
Sound insulation is the term describing the reduction of
sound that passes between two spaces separated by a If designing for residential units, design advice on flanking
dividing element. details must be followed to maximise the possibility
of achieving the specified acoustic performance. It is
In transmitting between two spaces, the sound energy may imperative that the design advice is followed, otherwise
pass through the dividing element (direct transmission) site sound insulation values may not meet the minimum
and through the surrounding structure (indirect or standards required by Building Regulations and expensive
flanking transmission). When designing for optimum remedial treatment will be required.
sound insulation, it’s important to consider both methods
of transmission. The walls or floors, which flank the Small openings such as gaps, cracks or holes will conduct
dividing element, constitute the main paths for flanking airborne sounds and can significantly reduce the sound
transmission, but this can also occur at windows, doorways, insulation of a construction. For optimum sound insulation a
heating or ventilation ducts, for example. construction must be airtight. Within masonry construction,
most gaps can be sealed at the finishing stage using Gyproc
The acoustic environment of the room and/or the building, Airtite Quiet, Gyproc plaster or Gyproc jointing compounds.
and the ability to reduce or eliminate air paths in the vicinity At the base of the partition, gaps will occur, particularly
of the sound reducing element, these include doorsets, when boards are lifted tight to the ceiling. Small gaps or air
glazing, suspended ceiling cavities, ductwork, etc. will have a paths can be sealed with Gyproc Sealant.
significant effect on its performance. For these reasons it is
unlikely that figures quoted from laboratory test conditions
will be achieved in practice. When the background noise
is low, consideration may have to be given to a superior
standard of sound insulation performance in conjunction
with the adjoining flanking conditions.
ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C02. S01. P21
Technical performance and principles of system design
Technical
performance
1
C02
External noise
Internal noise
External noise
Mechanical
services noise
2 3
1
1
3
2 2
Deflection head A (subject to fire performance) Deflection head B (subject to fire performance)
1 Gyproc Sealant for optimum sound insulation 3 Gypframe GA4 Steel Angle to minimise loss of sound insulation
performance due to air leakage
2 50mm timber head plate equivalent to channel width forming
fire-stop
performance
Technical
Building acoustics (continued)
C02
by sound insulating walls abutting structural steelwork,
Deflection heads, by definition, must be able to move and, consideration should be given to the potential loss of sound
therefore, achieving an airtight seal is very difficult without insulation performance through the steelwork.
incorporating sophisticated components and techniques.
Air leakage at the partition heads will have a detrimental Figures 4 to 7 are example details relating to a typical
effect on acoustic performance of any partition. scenario where a partition is specified against a requirement
of Rw 50dB. Although these details refer to structural steel
The approach shown in figure 2 could, for example, result in column abutments, similar principles apply when abutting
a loss of around 4dB to 5dB due to air leakage, in addition to structural steel beams. We recommend that these details
any performance lost due to flanking transmission. are checked by an Acoustic Consultant, in particular the
performance via the flanking structure.
Where acoustic performance is a key consideration, steps
can be taken to minimise this loss of performance. Sound by-passing a partition via the void above a
Figure 3 shows the generally accepted method of achieving suspended ceiling
this and, provided that care is taken to ensure a tight fit This is a common source of sound transmission, particularly
between the cloaking angle and lining board surface, the where the ceiling is absorbent to sound. Sound can easily
loss in performance can be reduced. travel through a perforated tile, or lightweight suspended
ceiling, and over the top of a partition where it abuts the
Other factors, such as flanking transmission through the underside of the suspended ceiling. Where sound insulation
structural soffit, can significantly affect the overall level of is important, partitions should, wherever possible, continue
sound insulation. Therefore, other measures may need to through the ceiling to the structural soffit, and be sealed
be taken. at the perimeter junctions. Gyproc plasterboard suspended
ceilings offer better insulation where partitions must stop
– A suspended ceiling installed on both sides of the at ceiling level to provide a continuous plenum. In this
partition may provide a similar cloaking effect to that of instance, a cavity barrier can be incorporated above the
steel angles ceiling line.
– CasoLine mf incorporating imperforate plasterboard can
deliver a similar reduction in air leakage at the partition Figures 8 to 11 show the stages of sound insulation
head. A tight fit between the ceiling perimeter and improvement for typical ceiling/high performance partition
the surface of the partition lining board is important, junctions. The best result is achieved by running the
although mechanically fixed perimeters are not essential partition through to the structural soffit.
ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C02. S01. P23
Technical performance and principles of system design
Technical
performance
4
C02
3
7
Rw 50dB Typically
Rw 25dB
5
6
4
1
3
7
Rw 50dB Estimated
Potential Rw 50dB
flanking
sound
transmission
performance
Technical
Building acoustics (continued)
C02
5
4
6
Rw 50dB 6
Estimated
Reduced risk Rw 50dB 1
of flanking
sound
transmission
7
5
6
4
Rw 50dB
Estimated 1
≥Rw 50dB
subject to width
of encasement
Encased steel column with additional framing, insulation and plasterboard lining
ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C02. S01. P25
Technical performance and principles of system design
Technical
performance
8 9
C02
Concealed grid – lined with a single layer of plasterboard and Concealed grid – lined with a double layer of plasterboard and
overlaid with insulation = 48dB overlaid with insulation = 49dB
10 11
Concealed grid lined with a double layer of plasterboard within Partition lining continued to the soffit enabling the full
each room and overlaid with insulation = 56dB potential of the partition to be achieved = 58dB
performance
Technical
Building acoustics (continued)
Composite construction Table 2 – Guide to sound insulation levels for speech privacy
A common mistake made when designing a building is to Sound insulation Speech privacy
C02
specify a high performance element and then incorporate between rooms Rw 1
a lower performing element within it; for example, a door 25dB Normal speech can be overheard
within a partition. 30dB Loud speech can be heard clearly
35dB Loud speech can be distinguished under normal
Where the difference between insulation is relatively small conditions
(7dB or less), there needs to be a comparatively large area 40dB Loud speech can be heard but not distinguished
of the lower insulation element before the overall sound 45dB Loud speech can be heard faintly but not
insulation is significantly affected. However, where there is a distinguished
greater difference in sound insulation performance between > 50dB Loud speech can only be heard with great difficulty
the two elements, this would normally result in a greater
reduction of overall sound insulation performance. 1 Refer to page 29 for explanations of Rw.
Table 1 shows the acoustic effect various door types For healthcare and educational environments, acoustic
have within a partition system. For example; if a poor privacy issues are covered in more detail within Health
performance door is included within a partition, it does not Technical Memorandum (HTM) 05 series and TGD 021-5
matter if the wall achieves 35dB or 50dB sound insulation, from the Department of Education
as the net performance will never be greater than 27dB. The
lowest performing element will always dominate the When designing for residential buildings, the standards
overall performance. of sound insulation given in table 2 are not adequate.
Reference should be made to the requirements of Technical
Table 1 – The effect various door types have within a partition Guidance Document E (RoI) or Technical Booklet G (NI).
system
Door construction Mean sound insulation of partition Ambient noise levels
alone (dB)
Along with acoustic privacy, the acceptable level of sound
25 30 35 40 45 50 within a room should be assessed. Factors that affect the
Mean sound insulation of partition with ambient noise level of a space are:
doorways accounting for 7% of area (dB)
Poor performance door with 23 25 27 27 27 27 – The level of external noise
large gaps around the edge
– The level of sound insulation designed into the
Light door with edge sealing 24 28 30 32 32 32
surrounding structure
Heavy door with edge sealing 25 29 33 35 37 37
– The amount and type of sound absorbing surfaces within
Double doors with a sound lock 25 30 35 40 44 49
the room
Acoustic privacy – The noise generated by building services
Two main factors affect the level of acoustic privacy achieved Where control of ambient noise is critical, advice should be
when designing a building: sought from an Acoustic Consultant.
– The sound insulation performance of the structure For each room there might be a range of levels that are
separating the two spaces considered acceptable. The designer should select a level
– The ambient background noise present within the appropriate for the particular circumstances.
receiving room
For this purpose there are a number of methods, including
The ambient background noise level can be a useful tool the Noise Rating (NR) system.
when designing buildings, as it is possible to mask speech
from an adjacent space and hence provide enhanced speech The NR system quantifies the level of noise present within
confidentiality, for example a Doctor’s consultancy room a space, taking into account break-in of noise from the
next to a waiting room. There are a number of commercially adjacent areas, and also the background noise present
available systems to achieve this. It is, however, more within the space from ventilation or other building services.
common to treat the problem by specifying appropriate Table 3 gives the recommended maximum noise within
levels of sound insulation. A guide to sound insulation levels different activity spaces, using the NR system criteria.
is given in table 2.
ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C02. S01. P27
Technical performance and principles of system design
Technical
performance
Table 3 – Recommended maximum noise rating for various types By converting some of the sound energy into heat, sound
of room function absorbing materials will also help sound insulation because
C02
performance
Technical
Building acoustics (continued)
12
C02
Sound transmission in a typical classroom
Rating methods this book present relevant sound insulation values both
in Rw terms but also in the Ctr adapted form. This rating is
Sound insulation rating methods expressed as Rw + Ctr and allows the Acoustic Consultant to
critically compare performances. The rating method mainly
The sound insulation rating methods that follow are defined
considers low frequency performance, and has not been
in: BS EN ISO 717: Part 1: 2013 (airborne) and
universally welcomed due to the difficulties in measuring
BS EN ISO 717: Part 2: 2013 (impact).
low frequency performance.
Rw
Consequently, within separating constructions,
This single figure rating method is used for laboratory
Gyproc can offer enhanced specifications that meet the low
airborne sound insulation tests. The figure indicates the
frequency performance of the Ctr rating whilst also offering
amount of sound energy being stopped by a separating
good mid and high frequency sound insulation.
building element when tested in isolation in the absence of
any flanking paths.
Ln,w
This single figure rating method is used for laboratory
DnT,w
impact sound insulation tests on separating floors.
This single figure rating method gives the airborne sound
The figure indicates the amount of sound energy being
insulation performance between two adjacent rooms
transmitted through the floor tested in isolation, in
within a building as measured on site. The result achieved is
the absence of any flanking paths. With impact sound
affected not only by the separating element, but also by the
insulation, the lower the figure the better the performance.
surrounding structure and junction details.
L’nT,w
Ctr
This single figure rating method gives the impact sound
The Ctr adaptation term is a correction that can be added to
insulation performance for floors. The figure indicates the
either the Rw (laboratory) or DnT,w (site) airborne rating.
sound insulation performance between two adjacent rooms
within a building as measured on site. The result achieved
The term has been adopted within Building Regulations
is affected not only by the separating floor but also by the
Technical Booklet G (NI). The Ctr term is used because
surrounding structure, e.g. flanking walls and associated
it targets the low frequency performance of a building
junction details.
element and in particular the performance achieved in the
100 – 315 Hz frequency range. This term was originally
developed to describe how a building element would
perform if subject to excessive low frequency sound sources,
such as traffic and railway noise. Performance tables in
ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C02. S01. P29
Technical performance and principles of system design
Technical
performance
evaluating the airborne sound insulation performance Typically the average sound insulation of a material forming
of suspended ceilings. Laboratory tests simulate the a solid partition is governed by its mass; the heavier the
room-to-room performance of the suspended ceiling when material, the greater its resistance to sound transmission.
a partition is built up to the underside of the ceiling with To increase the sound insulation of a solid partition by
sound transmitted via the plenum. approximately 4dB, the mass must be doubled. This is
known as the empirical mass law.
Sound absorption rating methods
The following ratings are calculated in accordance with For example; a 100mm solid block wall of average mass
BS EN ISO 11654: 1997. 100kg/m² will have an approximate Rw value of 40dB,
whereas a 200mm solid wall of the same material would
Sound absorption coefficient, αs have an Rw value of 44dB.
Individual sound absorption figures quoted in
one-third octave frequency bands are used within advanced Increasing mass is a very inefficient way of achieving
modelling techniques to accurately predict the acoustic sound insulation and one of the advantages of using
characteristics of a space. The coefficient ranges from 0 lightweight cavity partitions and walls is that better than
(total reflection) through to 1 (total absorption). predicted sound reduction values can be achieved. This
is why this construction is commonly used in auditoria,
Practical sound absorption coefficient, αP e.g. GypWall audio. Lightweight systems versus the mass
A convenient octave-based expression of the sound law shows how lightweight systems consistently exceed
absorption coefficient; commonly used by Acoustic mass law predictions. This demonstrates that adding mass
Consultants when performing calculations of reverberation is not always the best method to satisfy acoustic design
times within a building space. requirements and that, lightweight systems, if correctly
designed, can provide very effective acoustic solutions.
Sound absorption rating, αw Refer to figure 13.
A single figure rating used to describe the performance of a
material. The single figure rating can have a modifier added 13
to indicate if the spectral shape is dominated by a particular 70 l 300mm GypWall audio
frequency range
l 148mm GypWall quiet sf
– L – absorption is predominantly in the low frequency 60
l 200mm GypWall
region
l 100mm GypWall
50
– M – absorption is predominantly in the mid frequency
region
Sound reduction index
40
75mm GypWall l
– H – absorption is predominantly in the high frequency
region
30
accurately reflect the product performance. An NRC value Lightweight systems versus the mass law
is the arithmetic mean of the absorption coefficients across
a limited frequency range; this means that it will hide
extremes in performance. For instance, a ceiling tile may be Acoustic performance is commonly expressed as a decibel
a very efficient absorber at high frequencies but very poor (dB) value. The logarithmic scale of decibels provides a
at low frequencies, and the NRC value will not reflect this. simple way to cover a large range of values and show them
To optimise the room acoustics the more accurate sound as a convenient number. Unfortunately the decibel scale can
absorption rating, αw, should be used. create confusion especially when comparing
alternative systems as the difference in acoustic
performance can appear to be quite small. In reality an
increase of 6dB is equivalent to a doubling of the acoustic
performance of the system.
performance
Technical
Building acoustics (continued)
A simple stud partition, for example, can have an Rw rating sides. This will increase the sound insulation performance by
of 6dB better than predicted by the mass law. In this case, approximately 6dB or 10dB respectively.
C02
the maximum sound insulation obtainable will be governed
by the transmission of energy through the stud frame. The Acoustic benefits of applying Gyproc Finish Plasters to
use of other frame types, or configurations, can result in certain GypWall partition systems
even better insulation. If Gyproc plasterboard or Gyproc
specialist boards are fixed to a timber stud frame using a Applying 2mm Gyproc Finish Plasters to both sides of
flexible mounting system, such as Gypframe RB1 Resilient certain GypWall partitions has a positive effect on the
Bar, or a more flexible frame is used, for example, Gypframe sound insulation performance. This is effective on partitions
studs and channels, sound transmission through the that are limited by their high frequency performance
framing is minimised and performance significantly better (coincidence region).
than the mass law prediction can be achieved.
The application of Gyproc Finish Plasters also adds mass
The use of two completely separate stud frames can produce to the partition which has a positive effect on the mid-
even better results. In this case, the maximum energy frequency of the spectrum.
transmission is through the cavity between the plasterboard
linings. The air in the cavity can be considered as a spring Figure 14 shows an example of a partition that will be
connecting the linings, which allows the passage of energy. positively affected by skim finish using Gyproc Finish
The spring will have some inherent damping, which can be Plasters.
significantly increased by the introduction of
a sound absorbing material, such as mineral wool,
14
positioned in the cavity. The increased damping of the
65
air-spring results in a reduced coupling between the
plasterboard linings and a consequent decrease in sound 50
60
4040
Two important effects; resonance and coincidence, occur 35
frequencies. 15
10
Unskimmed partition
more board layers. A simple way of increasing the sound
insulation performance of a single layer metal stud partition Acoustic benefits of applying Gyproc Finish Plasters to certain
is to add an additional layer of plasterboard to one, or both, GypWall partitions
Table 6 – TGD E: Sound Insulation Requirements (RoI) Table 6a – TB G: Sound Insulation Requirements (NI)
Separating Airborne sound Impact sound Separating Airborne sound Impact sound
construction insulation DnT,wdB insulation L’nT,wdB construction insulation insulation L’nT,wdB
Walls 53 (min) - DnT,w+CwdB
ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C02. S01. P31
Technical performance and principles of system design
Technical
performance
Plasters are shown. Systems with additional performance cover reverberation noise in the common internal parts of
will show two acoustic figures in the tables – Sound buildings containing flats or rooms for residential purposes.
insulation performance for partitions finished using jointing The regulations state that “the common internal parts
or plaster skim and sound insulation performance for of buildings which contain flats or rooms for residential
partitions with a 2mm skim finish of Gyproc Finish Plasters. purposes shall be designed and constructed in such a way
as to prevent more reverberation around the common parts
Legislation and guidance than is reasonable”.
Building Regulations – Residential Buildings The regulations give two methods of calculating the amount
Building Regulations Technical Guidance Document E (RoI) of absorption required in any communal areas. The two
or Technical Booklet G (NI) gives guidance on how to provide methods are referred to as ‘Method A’ and ‘Method B’.
reasonable standards of sound insulation in dwellings
and other residential buildings. They cover both new-build AD E specifies sound absorption in terms of a class of
and refurbishment or conversion, and include minimum absorber. There are five classes (A through to E) with
standards of performance. Class A signifying the products with the highest level of
sound absorption. However, to comply with method A, only
Complying with the regulations class C or D is required. The values ascribed to the different
classes are given in table 7.
In Ireland, housebuilders and residential developers can
demonstrate compliance of separating walls and floors for
Table 7 – Absorption class
new-build houses and apartments using manufacturers’
Sound absorption class αw
proprietary systems or Building Regulations Example /
Guidance and verifying by Pre-Completion Testing A 0.90, 0.95, 1.00
B 0.80, 0.85
a series of Robust Details. These forms of construction Unclassified 0.00, 0.05, 0.10
If you are following the Robust Detail route, you must Example constructions
register each plot, with the details you intend to use, and These are constructions developed to repeatedly achieve
pay a fee. You will then be given a registration certificate to required design performance levels, if built correctly
hand to your building control authority before work starts. with correctly designed flanking details. Use of these
Robust Details Ltd administers the scheme. constructions does not guarantee regulatory performance
levels will be achieved, and the onus is therefore on
If you are building to the Irish Green Building Council’s the housebuilder to demonstrate compliance by Post-
Home Quality Rating Tool, Robust Details may entitle you to Completion Testing on site.
additional credits under the Health and Wellbeing category
– check the Robust Details Handbook for the most up-to- Other constructions
date details.
These include manufacturers’ proprietary solutions and new,
or innovative, constructions not considered to be ‘Example
Constructions’. Again, the onus is on the housebuilder to
demonstrate compliance by Post-Completion Testing.
Post-Completion Testing
Post-Completion Testing is carried out when the building is
complete, with doors, access hatches and windows fitted.
performance
Technical
Building acoustics (continued)
rooms may be affected. This will result in additional testing BS 8233 – Sound insulation and noise
requirements. It may be prudent to seek specialist advice to
reduction for buildings
C02
identify and remedy any problems.
BS 8233 provides guidance on acoustic ratings appropriate
Acoustic design of schools to a variety of different building types. It is applicable
to the design of new buildings, or refurbished buildings
Each room or other space in a school building shall be undergoing a change of use. It deals with control of noise
designed and constructed in such a way that it has the from outside the building, noise from plant and services
acoustic conditions and the insulation against disturbance within it, and room acoustics for non-critical situations.
by noise appropriate to its intended use.
A full revision of the standard, launched in 2014, includes
To satisfy this requirement, it is recommended that changes which reflect:
buildings comply with the guidance TGD 021-5 Acoustic
– Legislative framework revision since publication of the
Performance of Schools from the Department of Education
1999 edition
in RoI and Building Bulletin 93 (BB93) Acoustic design of
schools, a design guide for Northern Ireland. – Revisions to Building Regulations
– The publication of specialist documents for specific
BB93 was written by the Department for Children, Schools sectors, such as healthcare and education
and Families (DCSF), formerly the Department for Education
and Skills (DfES), and provides a regulatory framework for – A reappraisal of the tabular content with respect to
the acoustic design of schools; including sound insulation setting targets for various classes of living space in the
between spaces, ambient noise levels and optimum light of research findings
reverberation times for various spaces within educational – The need to transfer some of the more detailed
buildings. information from the main text to annexes
– Requirements for offices
For more information refer to our Education Sector Guide,
available from the Gyproc Technical Department.
Designing for on-site performance in
Northern Ireland
Health and Technical Memorandum
Achieving a DnT,w + Ctr performance on site
HTM 08-01 Acoustics – Healthcare Buildings
The Ctr rating method puts increased emphasis on the
Good acoustic design is fundamental to the quality of low frequency region of the spectrum. For lightweight
healthcare buildings. The control of unwanted noise construction this means a significant change in some of
improves patient privacy, dignity and sleep patterns; all key the design principles. For partitions, the cavity should be as
conditions for healing. Good acoustic design also increases large as possible and double layers of plasterboard should
the morale and comfort of healthcare professionals. be used.
HTM 08-01 covers the acoustic design criteria that are For masonry walls lined with lightweight panels, cavities
important for healthcare premises and contains a method of with a depth of less than 60mm should be avoided. Two
determining the level of sound insulation required between linings, with small, identical sized cavities either side of a
adjacent spaces in a healthcare environment. The document solid masonry wall, should not be specified. These cavities
also gives recommended reverberation times for various can interact and cause a significant downgrade in the
types of space. critical low frequency zone. If a small cavity is required, one
side only should be lined with a double layer of plasterboard.
Optimum performance is achieved by lining one side only
Hotels and Hospitality: Acoustic Standards
and having a cavity depth of at least 85mm.
The Fáilte Ireland Guest House Classification Scheme Refer to C02. S01. P41 for more information on service voids.
requires that bedrooms, the toilets and bathrooms serving
them, and the corridors off which they shall open shall be
separated from each other by walls or partitions, floors and
ceilings and having an acoustic attenuation of 50 dB.
ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C02. S01. P33
Technical performance and principles of system design
Technical
performance
A method of determining the achievable site DnT,w + Ctr – Inappropriate detailing of flanking conditions can greatly
performance is to refer to a laboratory Rw + Ctr rating. reduce the level of performance of the system from that
Depending on the wall specification, a minimum drop achieved in the laboratory. Refer to figures 4-7 for more
of 4dB is typical when comparing Rw + Ctr and DnT,w + Ctr. information
However, we recommend that a safety margin of + 9dB
– For separating wall and floor constructions to be fully
should be used to reduce the risk of failure to comply with
effective, care must be taken to correctly detail the
Building Regulations. This assumes all flanking paths are
junctions between the separating wall or floor and
appropriately detailed, ideal site lay-out exists and a high
associated elements such as external walls, other
quality of workmanship is applied.
separating elements and penetrations or door openings,
For purpose-built dwelling houses and flats requiring
etc.
DnT,w + Ctr 45dB for separating walls, separating floors and
stairs, we recommend specifications capable of achieving – If junctions are incorrectly detailed then the acoustic
Rw + Ctr 54dB. performance will be limited and Building Regulations
requirements will not be achieved in practice
For purpose-built rooms for residential purposes requiring – Pre-Completion Testing exposes poor flanking details
DnT,w + Ctr 43dB for separating walls, and DnT,w + Ctr 45dB for and inadequate separating wall and floor specifications.
separating floors and stairs, we recommend specifications Good flanking detailing and specifications that provide
capable of achieving Rw + Ctr 52dB for separating walls, and a reasonable margin of safety on site are therefore
Rw + Ctr 54dB for separating floors and stairs. essential.
performance
Technical
Building acoustics (continued)
C02
Gypframe AcouStuds component used predominantly with lightweight separating
floors to de-couple the ceiling from the floor structure and
Gypframe AcouStuds are metal stud sections optimised to
thereby improve the airborne sound insulation performance
give enhanced sound insulation performance. These unique
of the separating floor.
shaped studs are used for increased acoustic performance.
Gypframe AcouStuds can be used to upgrade the acoustic
The value of this component is recognised in Robust Details,
performance of 70mm, 92mm and 146mm wall systems.
where all lightweight floor solutions feature resilient bars to
partially de-couple the ceiling from the floor structure.
Figure 16 shows the performance improvement possible
using acoustic stud technology compared with a standard ‘C’
Figure 20 shows the substantial performance improvements
stud of the same cavity dimension.
achievable for airborne sound insulation when Gypframe
RB1 Resilient Bar is utilised instead of a directly fixed ceiling.
GypWall staggered
GypWall staggered features staggered studs that are located Floating floor treatment
within a head and base channel by means of retaining
Floating floor treatments are used with both lightweight
clips. This arrangement means there is limited connection
and concrete separating floors to de-couple the walking
through the framework to the plasterboard face on the
surface from the floor structure and thereby improve both
opposite side of the partition. The system design enables a
the airborne and impact sound insulation performance of a
higher level of sound insulation to be achieved with modest
separating floor.
cavity sizes.
ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C02. S01. P35
Technical performance and principles of system design
Technical
performance
16 17 75
70
C02
70
65
65
60
60
55
55
50
50
45
45
40
40
35
35
30
30
25
25
20
100 3150
100 3150 Frequency, Hz
Frequency, Hz
GypWall GypWall staggered
Gypframe ‘C’ Stud Gypframe AcouStud
18 19 85
75
80
70
75
65
70
Sound reduction index
60
Sound reduction index
65
55
60
50
55
45
50
40 45
35 40
30 35
100 3150 100 3150
Frequency, Hz
Frequency, Hz
Gypframe ‘C’ Studs, no bar Gypframe RB1 Resilient Bar both sides 211mm GypWall 300mm GypWall audio
Acoustic benefits of resilient bars (partition) Acoustic benefits of twin stud framework
20
65
60
55
50
Sound reduction index
45
40
35
30
25
20
15
100 3150
Frequency, Hz