Mechanical Punch Points

Inspection Location : Fire Water Hydrant Lines at GCS


Date of Inspection : 29.01.2021
EPC : M/s. Tata Projects Ltd.
NOA : DLH/OES/MM/CBM-BOKARO/X11RC16002/2016

Sr. TPI Observations Remediation to be done Remarks/Rectification TPI / ONGC


No. Status Accepted
1. Supports structure base plates are Fixed & anchored all balance
not fixed and anchored near GC pipe supports base plates.
exhauset chimeney
2. Fire water line boundary wall Provide regid & permanent
supports are failured and anchored supports as required
are failure due to lines are sagging
3. Rapping coating had done is Rectify all the rapping coating
completely failure almost all the and maintain the above
places and also not maintain level i.s. ground level as per drg.
200 mm above the ground level
4. Found temporary supports Provide permanent supports
5. Found gap between pipes & footing Provide proper packing plates
there for pipes are not in rest
6. Flanges studs are missing & some Place studs where required
flanges studs are shorter in length and replace all shorter studs
with proper size studs
7. Some places painting balance and Complete balance painting
found scratches on the painted pipe and touch up all scratches
surface location.
Note : Offer for witness
painting DFT after
painting/rectification done
8. Water pipe line ground clearance Maintain minimum ground
not maintained. clearance as per drg.
9. Found obstacles near water pipe Remove all obstacles
lines
10. Stencils balance Do as per standard

TPL TPL/ONGC
QC

Page 1 of 7
Note :

1. Referance photographs attached below


2. Attched photos are not consider quantity, these photos are only for understanding & examples for punch points
3. Your rectification team must be instructed to look inch by inch and attened all such examples highlited points

Supports structure base plates are not fixed and anchored near GC exhauset chimeney

Fire water line boundary wall supports are failured and anchored are failure due to lines are sagging.

Page 2 of 7
Fire water line boundary wall supports are failured and anchored are failure due to lines are sagging.

Page 3 of 7
Rapping coating had done is completely failure almost all the places and also not maintain level i.s. 200 mm
above the ground level

Found temporary supports

Found gap between pipes & footing there for pipes are not in rest

Page 4 of 7
Flanges studs are missing & some flanges studs are shorter in length and also found loose bolts

Page 5 of 7
Water pipe line ground clearance not maintained.

Some places painting balance and found scratches on the painted pipe surface

Page 6 of 7
Found obstacles near water pipe lines

Stencils balance

Tauseef Azhar
Mechanical Surveyor
ICS

Page 7 of 7