Professional Documents
Culture Documents
Experiment Name:
Load (external) characteristics of D.C separately excited Generator.
Objective:
To connect the separately excited generator to an external load ,to run
it at normal speed and to obtain its external characteristics.
Experiment Tools :
Generator
Motor
Taco_Generator
Digital_Taco_generator
Two Voltmeter
Three Ammeter
Control unit
Two DC power supply
Wires connection.
Two variable resistance
Connection Diagram:
1
Load (external) characteristics D.C separately excited Generator
Experiment Procedures:
1-The motor-generator set is arranged and connected to the D.C supplies as
shown in the figure.
2-The generator is run up to its normal speed by means of the shunt motor .
3-the speed is kept constant during the experiment by means of the motor field
regulating resistance R1.
4-With the generator at no – load ,its terminal voltage is adjusted to the rated
value by adjusting Ifg which will kept constant after that.
5-To obtain the external characteristic a load resistance RL is connected and a
series of readings between zero load current and 25% over load is taken.
6-plot the relation between VL and IL .
7-plot the variation of power input ,power output, and efficiency with the load
current .
2
Load (external) characteristics D.C separately excited Generator
Calculated values:
Pin1=Iin1*Vin1=0.18*195=35.1W
Pin2=Iin2*Vin2=0.29*210=60.9 W
Pin3=Iin3*Vin3= 0.4*220=88 W
Pin4=Iin4*Vin4=0.53*230=121.9W
Pin5=Iin5*Vin5=0.73*230=167.9W
Pin6=Iin6*Vin6= 1 * 230 =230 W
Pout1=Iout1*Vout1= 0*195 = 0 W
Pout2=Iout2*Vout2=0.1*190 = 19 W
Pout3=Iout3*Vout3=0.2*182 = 36.4 W
Pout4=Iout4*Vout4=0.3*172 = 51.6 W
Pout5=Iout5*Vout5=0.42*160 = 67.2 W
Pout6=Iout6*Vout6= 0.52*152 =79.04 W
3
Load (external) characteristics D.C separately excited Generator
51.6
= ∗100 %=44.254 %
116.6
67.2
= ∗100 %=41.84 %
160.6
79.04
= ∗100 %=34.365 %
230
Curves:
Conclusion:
1-when we starting the experiment at constant speed and constant field
current at no-load the value of VL is maximum because armature
circuit is open and Ia =0 so Eg=VL – Ia*Ra ,and Eg = køn , k is
constant for any machine because we can’t making control on “k”
pz
because k = 60 a this by the designer and “ø” is constant because If is
constant so Eg constant and VL will be constant and Eg = VL at no load.
4
Load (external) characteristics D.C separately excited Generator
and making many columns from above that crossing the curve of
external C.C and line of Ra and measuring the vertical distances that
are under the line of Ra and moving them to upper the curve of
external characteristic and matching between this point from value of
Eg voltage at no-load (Eg no-load) so this curve will be internal C.C, so
the distance between dashed line (Eg no-load ) and internal C.C will
be drop voltage due to armature reaction and the distance between
internal C.C and external C.C will be drop voltage due to armature
resitance Ra.
11- The benefit from this curve of external C.C if we has device we
want to know the values of current that passing through it and the
voltage across it using machine that we found the curve of it and we
knowing the value of resistance of new load RLso the experiment are
by ploting the line of RL by chosing one value of Ia let it be Ia2 and
finding V2=Ia2*RL2 and plotting the line from orgin to (Ia2 , V2) it will
be linear as we explain that above this line of RL will cross the curve
of external C.C for this machine at one point let this point be (IL2 , VL2
) so VL2 will be the voltage across new load and IL2 current that pass
through this load.
Discussion :
1-Comment on the shape of the curves you have obtained and state
why a d.c separately excited generator is called “a constant voltage
generator” .
Comment:
The relation between Ra and ILis linear
The relation between Eg and IL is reverse proportional
The relation between termial voltage and IL is reverse proportional
7
Load (external) characteristics D.C separately excited Generator
The voltage drop due to armature resistance is larger than the voltage
drop due to armature reaction
The input power is larger than output power as shown so the losses in
machine is very high.
The relation between IL and power is directly proportional.
The relation between IL and efficiency at first time will increase
faster ,after that the increasing in efficiency will be shorter and finally
at the end efficiency will decrease when IL is increase as shown in
figure.
D.C separately excited generator is called “a constant voltage
generator” because the value of Eg in real generator doesn’t change
because the voltage drop is very small , in real generator the voltage
drop due to Ra is small because Ra is nearly 0.002ῼ and there is no
voltage drop due to armature reaction because there are some
methods to remove armature reaction so Eg will be constant so flux
in machine doesn’t change even if load increase and speed is
constant .
Methods used to remove armature reaction :
Putting the brushes on (MNA) don’t in (GNA) and nearly at
80% from the load because real machine can’t reach to rated.
Commutating poles or Interpoles : are a small poles placed
midway between the main poles , and the effects of the interpoles
do not extended the main pole faces , the armature reaction under
them is unaffected ,that mains the flux weakening in the machine
is unaffected, the interpoles must be of the same polarity as the
next upcoming main pole in generator.
Compensating Windings : to completely cancel armature reaction
and eliminate both neutral plane shift and flux
weakening ,placing compensating windings in slots curved in the
facs of the poles parallel to the rotor conductors ,the windings are
connected in series with the rotor windings.
8
Load (external) characteristics D.C separately excited Generator
3-Why does the terminal voltage (load voltage) decrease with increase of
of the load current ?
When we adding load as variable resistance and we starting by small
load means maximum value of variable resistance means minimum
value of current and increasing load step by step the value of terminal
voltage will be decrease because from the law:
VL = Eg – Ia *Ra , and by increasing load so Ia will increasing so the
value of VL will decrease because two reason :
When Ia increase the voltage drop in armature resistance “Ia*Ra”
will increase so the value of terminal voltage will decrease.
Armature reaction will changing the value of Eg and will
making two problem:
Flux Weakening (Demagnetising Effect):when we
connecting load current will start flow in armature circuit
and this current will produce flux and this flux inverse the
main flux so the net flux in machine won’t be constant it
9
Load (external) characteristics D.C separately excited Generator
4-Knowing the value of the load resistance RL , show how can you
locate the operating point on the external characteristic ?
The benefit from the curve of external C.C if we has device we want to
know the values of current that passing through it and the voltage across
it using machine that we found the curve of it and we knowing the value
of resistance of new load RLso the experiment are by ploting the line of
RL by chosing one value of Ia let it be Ia2 and finding V2=Ia2*RL2 and
plotting the line from orgin to (Ia2 , V2) it will be linear as we explain that
above this line of RL will cross the curve of external C.C for this machine
at one point let this point be (IL2 , VL2 ) this will be the operating point
so VL2 will be the voltage across new load and IL2 current that pass
through this load.
10
Load (external) characteristics D.C separately excited Generator
195−152
VR= ∗100 %=28.29 %
152
11