THE GOVERNMENT OF THE REPUBLIC OF IRAQ

MINISTRY OF ELECTRICITY

Intermediate Station (GIS)


Switchgear 33 KV

Section 2
Technical Data

D-01d Sept. 2020


Table of Contents
a) 33kV Metal Enclosed GIS Switchgear…………………………………………..…3
b) 33/0.416kVAuxiliaryTransformer………………………………………………12
c) 48VDC Battery and Battery Charger…………………………………………….14
d) Remote Terminal Unit ………………………………………………….……..20
e) Communication equipment……………………………………………………25
f) GPS Receiver and Antenna. ……………………………………………………….29
g) Coaxial cable ……………………………………………………………………..31
h) Optical cable between Equipment………………………………………………...32
i) Metering Devices of Multifunction………………………………………………34
j) Smart Meter ……………………………………………………………………....35
k) Transducers …………………………………………………………...…………..37
l) LV AC Distribution Pan..........................................................................................39
m) Over current / Earth Fault protection…………..…………………..41
n) Trip Circuit Supervision………………………………………………………..43
o) Multi Contact Tripping Relay…………………………………………………44
p) 33 kV Load Shedding Frequency Relay………………………………………45
q) Voltage Earth fault Relay………………………………………………………….46
r) Under Voltage Protection……………………………………………………….47
s) Over Voltage Protection……………………………………………………………48
t) Unbalance Protection Relay…………………………………………………....49
u) 33 kV XLPE insulated three cores Power Cables to Aux.TR……………….…51
v) LV PVC insulated Single core Power Cables (Unarmored)……………………51
w) LV PVC insulated Multi corePowerCables.....................................................52
x) LV control & Signal Cable……………………………………………………….53
y) Grounding System…………………………………………………………….….54
z) Ampere Meters…………………………………………………………………...55

2
A) 33kV Metal CladSwitchgear

Technical Particulars and Guarantees of 33 kV Metal Enclosed GIS Switchgear

Specification
No. Description Unit
Required Proposed

A 33kV METAL ENCLOSED GIS SWITCHGEAR


1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
GIS insulated
1.3 Type
Metal Enclosed
type
1.4 Model To be filled in
IEC 62271-1,
1.5 Applicable Standards
IEC 62271-200
1.6 Type Test
• Certificate Provided Yes
1.7 Location of service Indoor
Minimum period in continuous
1.8 Years 3
operation without failure.
2 ELECTRICAL DATA
2.1 Rated voltage kV 36
2.2 Rated insulation level
• Impulse withstand voltage
kV peak 170
(1.2/50µs)
• One minute50Hz
kV rms 70
withstand voltage
2.3 Rated frequency Hz 50
2.4 Rated normal current A (for incomer)1250
(for feeders) 630
2.5 Rated short-time withstand current kA rms 25
2.6
Rated peak withstand current kA peak ≥ 60
2.7 Rated duration of short circuit sec ≥3
Technical Particulars and Guarantees of 33kv Metal Enclosed GIS Switchgear

Specification
No. Description Unit
Required Proposed
Rated supply voltage of closing and
2.8
opening devices, auxiliary
and control circuits
• Closing and Tripping V DC 48
• Indication V DC 48
• Control V DC 48
3 DESIGN DETAIL
3.1 Busbars
• Type Single
• Rated normal current A 1250
• Temperature rise on
°C To be filled in
continuous operation.
• Cross section area mm2 To be filled in
According
• Insulation of busbar
to clause 3.1.5
• Maximum working temperature of
°C To be filled in
busbar insulation
• Minimum clearance
mm To be filled in
between phases
• Minimum clearance between
mm To be filled in
phases and earth
3.2 Material
• Cover Metallic
• Partitions Metallic
• HV conductor copper
Silver-plated
• Contacts
copper
Minimum thickness of sheet
3.3 mm To be filled in
metal used.
3.4 Color and type of painting for panel. Light gray finish
3.5 Degree of protection
• SF6gas Enclosed IP66
Compartment

4
• Cable IP41
• Instruments IP50
• Bus-bar To be filled in
Busbar/Circuit
3.6 Minimum compartments of Breaker/Cable/
cubicles at switchgear board LV-voltage
compartment
3.7 Pressure relief device Yes
4 DIMENSION AND WEIGHT
4.1 Dimensions (L x W x H)
• Incoming Cubicle m To be filled in
• Transformer Cubicle m To be filled in
4.2 Weight
• Incoming Cubicle kg To be filled in
• Transformer Cubicle kg To be filled in
B CIRCUIT BREAKER
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Interrupter Distinguishing Medium Vacuum, triple
and type of C.B pole operation,
1.4 Model To be filled in
1.5 Applicable Standards IEC62271-100
1.6 Number of poles 3
Inside metal
1.7 Location of service
Enclosed GIS
Switchgear
Motor charged
1.8 Type of operating mechanism
Spring
Type Tests included extended endurance
1.9
test (10000 operation for incomer) (30000
operation for feeders)

• Certificate Provided Yes


2 ELECTRICAL DATA
2.1 Rated voltage kV 36
2.2 Rated insulation level
• Impulse withstand voltage
kV peak 170
(1.2/50µs)
• One minute 50 Hz
kV rms 70
withstand voltage
2.3 Rated frequency Hz 50
2.4 Rated normal current A (for incomer)1250
(for feeders) 630
2.5 Rated Short- time withstand kA rms 25
2.6 Rated peak withstand current kA peak ≥ 60
2.7 Rated duration of short circuit sec 3
Rated supply voltage of closing
2.8 and opening devices, and auxiliary
control circuits
• Closing andTripping V DC 48
• Motor V DC 48
• Indication V DC 48
• Control V DC 48
2.9 Rated Short time breaking current
2.10 Rated Short time Breaking current kA 25
Rated operating sequence for double O-0.3 sec-CO-
2.11
reclosing 15 sec-CO
3 DESIGN DETAILS
3.1 First pole-to-clear factor 1.5
3.2 Rated transient recovery voltage kV/µs To be filled in
3.3 Total interrupting time Sec. Max 0.1
• Closingtime Sec. To be filled in
• Openingtime Sec. To be filled in
Not more than 3
• OperationTime (Make/Break)
cycle
Motor charged
3.4 Operating mechanism spring stored
energy

Spring charging timeout


3.5 Sec. To be filled in
Rated operation voltage
Temperature rise of main contacts
3.6 °C To be filled in
continuous operation at rated
C.B is trip-free with lock-out
3.7 To be filled in
preventing closing by ( anti pumping
device in C.B or Protection Relay )
3.8 Power consumption
• Closing and operating coil VA To be filled in
6
• Motor VA To be filled in
Number and type of spare auxiliary
3.9 Switches 8NO+8NC
3.10 Auxiliary switch
• Continuous current
A To be filled in
carrying capacity
• Breaking capacity at 48 VDC A To be filled in
Guaranteed number of SC
3.11 breakings without necessary to 20
inspect the circuit breaker poles
Guaranteed number of operations 10,000(for
3.12 with no load without necessary to incomers)
inspect the circuit breaker poles 20000(for
&operating feeders)
Type of corrosion protection of
3.13 To be filled in
steel parts
4 DIMENSION AND WEIGHT
Dimensions (L x W x H) of Circuit
4.1 M To be filled in
Breaker
4.2 Weight of Circuit Breaker kg To be filled in
C DISCONNECTOR & EARTHING SWITCH
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type
Load break GIS -
• Disconnector insulated
Fault making GIS
• Earthing switch - insulated
1.4 Model To be filled in
1.5 Applicable Standards IEC 62271-102
1.6 Number of poles 3
Inside Enclosed GIS
1.7 Location of service
Switchgear
2 ELECTRICAL DATA
2.1 Rated voltage kV 36

Technical Particulars and Guarantees of 33 kV Metal Enclosed GIS Switchgear


Specification
No. Description Unit
Required Proposed

2.2 Rated insulation level


• Impulse withstand voltage
kV peak 170
(1.2/50µs)
• One minute 50 Hz
kV rms 70
withstandvoltage
Rated normal current for (for incomer)1250
2.3 A
disconnector
(for feeders) 630
Rated short-time current at
2.4 time duration of 3 sec. for disconnector kA 25
and earthing
2.5 Making capacity for earthing switch kA To be filled in
3 DESIGN DETAIL
3.1 Minimum Clearance in air
• Between phases mm To be filled in
• Toearth mm To be filled in
3.2 Type of operating mechanism
Type of interlocking
3.3
mechanism interlocked
Number and type of spare auxiliary
3.4 Switches for Disconnector and Earthswitch 5NO+5NC

3.5 Auxiliary switch


• Continuous current
A To be filled
carryingcapacity
• Breaking capacity at 48 vDC A To be filled
D CURRENT TRANSFORMERS
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
Molded type
1.3 Type
Indoor

8
Technical Particulars and Guarantees of 33 kV Metal Enclosed GIS Switchgear

Specification
No. Description Unit
Required Proposed

1.4 Model To be filled in


1.5 Applicable Standards IEC60044-1
2 ELECTRICAL DATA
2.1 Ratedvoltage kV 36
2.2 Rated primary current A 600 (for incomer)
300 (for feeders)
2.3 Rated secondary current
• Measuring A 5
• Protection(O/C, E/F) A 5
Rated short time thermal current
2.4 kA 25
( 3 sec)
2.5 Rated dynamic current kA peak ≥ 60
2.6 Rated insulation level
• Impulse withstand
kV peak 170
voltage (1.2/50µs)
• One minute 50
kV rms 70
Hz
withstandvoltage
3 DESIGN DETAIL
3.1 Characteristics of Current Transformer
1) For Measuring
• Accuracyclass 0.2
Min. 30
• Ratedburden VA

2) For Protection
• Accuracy class 5P10
• Rated burden VA Min 15
Technical Particulars and Guarantees of 33 kV Metal Enclosed GIS Switchgear

Specification
No. Description Unit
Required Proposed

E VOLTAGE TRANSFORMERS
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
Molded type
1.3 Type
Indoor
1.4 Model To be filled in
1.5 Applicable Standards IEC60044-2
1.6 Number of phases Single phase x 3

2 ELECTRICAL DATA
2.1 Rated primary voltage kV 33 /√3

2.2 Rated secondary voltage V 110/√3 , 110/3

2.3 Rated voltage factor


• For continuous 1.2
• For 8 Hrs 1.9
2.4 Rated insulation level
• Impulse withstand
kV peak 170
voltage (1.2/50µs)
• One minute 50
kV rms 70
Hz
withstandvoltage
2.5 Fuse protection
• Ratedprimary A To be filled in
• Ratedsecondary A To be filled in
3 DESIGN DETAIL
3.1 Accuracy class 1.0/3P

10
Technical Particulars and Guarantees of 33 kV Metal Enclosed GIS Switchgear

Specification
No. Description Unit
Required Proposed

3.2 Ratio error % To be filled in


3.3 Rated burden VA Min 50
3.4 Phasedisplacement minutes To be filled in

B) 33/0.416kV AuxiliaryTransformer

Technical Particulars and Guarantees of 100kVA, 33/0.416kV Auxiliary Transformer


Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
Oil immersed
1.3 Type cable box for
both H.V & L.V
1.4 Model To be filled in
1.5 Applicable Standards IEC60076
1.6 Location of service Outdoor
1.7 Short circuit Test Report
Date of carried out To be filled in
Testing laboratory name and country To be filled in
Certificate Provided Yes
2 RATINGS
2.1 Rated power KVA 100
2.2 Rated voltage ratio
33(+2 x 2.5%/-2
• Primary kV
x
2.5%)
• Secondary kV 0.416Y/0.24
2.3 Number of phase 3
2.4 Frequency Hz 50
2.5 Vector group symbol Dyn11
2.6 Cooling method ONAN
Maximum temperature rise at
2.7
rated power
• Top oil bythermometer K 45
• Winding byresistance K 50
Technical Particulars and Guarantees of 100 kVA, 33/0.416kV Auxiliary Transformer
Specification
No. Description Unit
Required Proposed

• Hot spot ofwinding K To be filled in


Impedance voltage at continuous
2.8 % ≥4
rated power
2.9 Winding connection:
• Primary Delta
Star (Neutral
• Secondary
brought out)
3 Rated insulation level for Primary
• Impulse withstand
kV peak 170
voltage (1.2/50µs)
• One minute 50Hzwithstand kV rms 70
4 DESIGN DETAILS
4.1 Off-load tap changer
• Tappingrange +5%/-5%
• Tappingstep 2.5%
4.2 No load current at rated voltage A To be filled in
4.3 Type of oil (As per IEC requirement ) Yes
4.4 Standards IEC 60296

4.5 Type of corrosion protection

• Insidetank To be filled in
• Outsidetank To be filled in
glove or valve
4.6 Type of valves
gates
5 DIMENSION AND WEIGHT
Dimension of Transformer
5.1 mm To be filled in
(L x W x H)

12
5.2 Total oil required
• Volume Liter To be filled in
• Weight Ton To be filled in
5.3 Net weight of copper winding and kg To be filled in
Total weight of complete
5.4 kg To be filled in
transformer including fitting and

C) 48VDC Battery and Battery Charger

Technical Particulars and Guarantees of DC48V Battery and Battery Charger


Specification
No. Description Unit
Required Proposed

A BATTERIES
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
Pocket-plate
1.3 Type Hi- discharge
type Nickel-
Cadmium
1.4 Model To be filled in
IEEE 1115 for
Applicable Standards calculation,
1.5
IEC60623
equipment
2 DESIGN DETAIL
Rated capacity for 10 hours rate
2.1 AH
(To be confirmed calculation Report)
2.2 Rated voltage of battery V 48
2.3 Nominal charging rate current A To be filled in
2.4 Nominal voltage of battery cell V/cel 1.2
l
2.5 Number of cells 40
2.6 Final discharge-end voltage V/cel To be filled in
l
Potassium
2.7 Type of electrolyte
hydroxide
2.8 Specific gravity of electrolyte at 20°C To be filled in
Nickel-
2.9 Type of positive plate
hydroxide
and graphite
Electrolytic
2.10 Type of negative plate
cadmium
2.11 Type of separators To be filled in
Technical Particulars and Guarantees of DC48V Battery and Battery Charger
Specification
No. Description Unit
Required Proposed
Steel painted
2.12 Type of mounting rack trays with anti-
acid coating
Anticipated life of electrolyte
2.13 Years To be filled in
under actual operation condition
3 DIMENSION AND WEIGHT
Over all dimension of batteries on
3.1 m To be filled in
rack
3.2 Weight of cell withelectrolyte Kg/cell To be filled in
3.3 Volume of electrolyte Liter/cell To be filled in
B BATTERY CHARGERS
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
Full automatic
1.3 Type of battery charger constant
voltage DC
power
source
Single
1.4 Type of rectifier phase
Thyristor
full wave
bridge
1.5 Type of cooling for rectifier Self air-cooled
1.6 Model To be filled in
1.7 Applicable Standards IEC62040-1, -2, -
3
1.8 Degree of protection IP 41
2 or Dual type
1.9 Number of chargers

2 ELECTRICAL DATA
14
2.1 Rated input AC voltage V 230 ±10%
2.2 Number of phase of AC input 1
2.3 Rated Frequency Hz 50
2.4  Input Power VA To be filled in
 Voltmeter for input voltage Yes
with Selector Switch (ON/OFF
)
Regulated voltage range on DC
2.5 V 48 V ±10%
busbar
Means of regulating output voltage Semi-conductor
2.6
on DC busbar dropper
2.7 Di-electric strength (50Hz for 1
minute)
• Between AC phases and earth V 2000
• Between AC and DC circuit V 2000
3 DESIGN DETAIL
Continuous rated output
3.1
current including the derating
• On floatmode A To be filled in
• On boostmode A To be filled in
3.2 Charger rate output voltage
• FloatCharging V To be filled in
• BoostCharging V To be filled in
Manual voltage regulator
3.3
(float/boost charge)
• Voltage settingrange V To be filled in
• Boost charging currentsetting A To be filled in
• Boost charging voltagelimit
V To be filled in
setting range
3.4 Voltageripple % To be filled in
Setting range of DC under-
3.5 To be filled in
voltage relay
3.6 Setting current range for DC earth To be filled in
Air-insulated
3.7 Type of charger Cubicle metal-
enclosed
type
Light-grey
3.8 Color of Cubicle
finish, Semi-
gloss
Technical Particulars and Guarantees of DC48V Battery and Battery Charger
Specification
No. Description Unit
Required Proposed

4 DIMENSION AND WEIGHT


Overall dimensions of Cubicle
4.1 m To be filled in
(L x W x H)
4.2 Total weight of battery charger kg To be filled in
C 48VDC SWITCHBOARD
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type To be filled in
1.4 Model To be filled in
1.5 Location of services Indoor
1.6 Degree of protection IP 41
2 ELECTRICAL DATA
2.1 Rated DC voltage V 48
Rated current of busbars at 55°C
2.2 A To be filled in
ambient temperature
2.3 Busbar cross section mm2 To be filled in
2.4 Busbar insulation material To be filled in
2.5 Number of circuits To be filled in
2.6 Main isolator rating A To be filled in
2.7 Main fuse rating A To be filled in
3 DESIGN DETAIL
A MCCB (Incomings & Bus Coupler)
3.1 Manufacturer Name To be filled in
3.2 Type Molded Case
3.3 Model To be filled in
3.4 Applicable Standards IEC 60947-2
3.5 Site current rating (at 55°C) A To be filled in

16
3.6 Rated short time current (3 s) kA To be filled in
3.7 Maximum operating time
• Opening ms To be filled in
• Closing ms To be filled in
3.8 Voltage / power coil rating V/W To be filled in
3.9 Typical circuit diagram number To be filled in
Thermal or
3.10 Protection
Electrical

B DETAILS OF EARTH FAULT PROTECTION


1.1 Manufacturer Name To be filled in
1.2 Type To be filled in
1.3 Model To be filled in
1.4 Catalogue Provided Yes
C DETAILS OF UNDER VOLTAGE PROTECTION
1.1 Manufacturer Name To be filled in
1.2 Type To be filled in
1.3 Model To be filled in
1.4 Catalogue Provided Yes
D INSTRUMENTS
1.1 Manufacturer Name To be filled in
1.2 Type of meter
• Voltmeter To be filled in
• Ammeter To be filled in
1.3 Catalogue Provided Yes
Single line diagram &
E To be filled in
Arrangement drawing number
4 DIMENSION AND WEIGHT
Overall dimensions of Switchboard
m To be filled in
(L x W x H)
Total weight of Switchboard kg To be filled in
D) Remote Terminal Unit
Technical Particulars and Guarantees of Remote Terminal Unit

Specification
No. Description Unit
Required Proposed

Remote Terminal Unit


1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Model To be filled in
1.4 Applicable Standards To be filled in
2 DESIGN DETAIL
2.1 I/O maximum capacities To be filled in
2.2 Input signals
 Signal pcs To be filled in
 Analog measurement pcs To be filled in
 Digital measurement pcs To be filled in
 Pulse measurement pcs To be filled in
2.3 Output signals
 Command pcs To be filled in
 Analog set pointvalue pcs To be filled in
 Digital set pointvalue pcs To be filled in
Spare for each type of input/output
2.4 % 30
signals (Fully fitted and prewired)
Maximum System Capacity
2.5 % ≥2 x SSC
( Specified System Capacity: RTU)
2.6 Maximum future expansion capacity % ≥ 30
A MASTER CONTROL UNIT
1 GENERAL
1.1 Manufacturer Name To be filled in

18
1.2 Country of Manufacturing To be filled in
1.3 Model To be filled in
1.4 Applicable Standards To be filled in
2 ELECTRICAL DATA
2.1 Rated voltage V DC 48 ±15%
2.2 Maximum power consumption W To be filled in
2.3 Rated frequency Hz 50
3 DESIGN DETAIL
3.1 Main Processor To be filled in
3.2 Processor clock speed GHz To be filled in
3.3 Operating System To be filled in
3.4 Memory size GB To be filled in
3.5 Maximum Memory Capacity GB To be filled in
3.6 Hard Drive TB To be filled in
3.7 Add up to Hard Disk TB To be filled in
3.8 Optical Drive To be filled in
3.9 External Ports To be filled in
3.10 Network
 Communication Protocols to DCC IEC 60870-5 101
& 104
 Communication Protocols in
IEC 61850
Substation LAN
3.11 TCP/IP Internet Yes
3.12 GPS Interface Yes
3.13 RS232 Interface Yes & ≥ 64kbps
3.14 RS485 Interface Yes & ≥ 64kbps
4 DIMENSION AND WEIGHT
4.1 Dimensions (L x W x H) mm To be filled in
4.2 Weight kg To be filled in
Specification
No. Description Unit
Required Proposed

B SUBSTATION LOCAL AREA NETWORK (LAN)


1 DESIGN DETAIL
1.1 Fiber optic transmission medium To be filled in
1.2 ST-type Connectors of Fiber optic Yes
1.3 Communication protocol To be filled in

Technical Particulars and Guarantees of Substation Control System


Specification
No. Description Unit
Required Proposed

1.4 LAN bandwidth kbps To be filled in


LAN is implemented via hub or star
1.5 Yes
Coupler
C BAY CONTROL UNIT
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Model To be filled in
IEC 60225,
1.4 Applicable Standards IEC61000 and
IEC60068
1.5 Flush Mounted housing Yes
1.6 Degree of protection IP51 (Rear IP20)
1.7 Local LCD Display Yes
2 DESIGN DETAIL
2.1 LAN communication port
Ethernet,
 LAN Interface: IEEE802.3,
10 BASE-FL
 Protocol: TCP/IP
 Data transferrate: >10 Mbit/sec
Optical fiber GI
 Physical medium: 62.5/1 25 pm,
ST

20
connector

2.2 Time synchronization network port


 Accuracy: ±1 ms
Optical fiber GI
 Physical medium: 62.5/1 25 pm,
ST
connector
2.3 Event & Archive recording
 Eventmemory: >2,000 events
 Time resolution: 1 ms
 Archive capacity To be filled in
2.4 Functions
2.4.1 The monitoring
 Status and condition
Yes
monitoring (breaker,
disconnector ,etc)
 Indication & alarm LEDs
Yes
status monitoring
 Analogue measurements
Yes
(currents, voltages,etc.)
2.4.2 The control
 Close / open of circuitbreakers Yes
 Transformer tap changecontrol Yes
 Bay interlockingfacilities Yes
 VAR (For capacitor bank) Yes
 Protection relayreset Yes
2.4.3 The protection
 TR differential Yes
 Overcurrent Yes
 Earth fault Yes
 Voltage earthfault Yes
 Under-frequency Yes
 Unbalanced (For capacitor bank) Yes
measurement value

2.4.5 The reporting


 Events record Yes
 Disturbance record Yes
 Fault record Yes
2.4.6 Other
 Time synchronization (by SNTP & Yes
SCADA )
 IEC 61850 Bus Communication Yes
 Communication Protocol License Yes
( IEC-103 ,MODBus-
Serial,MODBusTCP/IP ,SPABus ,
DNP3 ) with Slave device.
SCADA protocol mapping IEC60870-5-
2.4.7 101 & 104 Yes

IEC101 & 104 point of view


 Link address 0….65535
 ASDU address 0….65535
 Information Object 0…16777216
Host point of view
 Priority 1/2
 Transmit with timestamp Y/N
 Filter Y/N
 Spontaneous transmission
Y/N
(AMI/MFI)
0,2,4,8,10,16,30,6
 Background Cycle(AMI/MFI)
0
sec,2,5,10 min
Normalized,
 Transmission format(AMI/ASO)
Scaled
 Maximum value (100%)(AMI/ASO) -32768…32767
 Minimum value (0%)(AMI/ASO) -32768…32767

22
 Decimal factor(AMI/ASO) 0….IE10
 Engineering(AMI/ASO) 32 ASCII
E) Communication equipment
Technical Particulars and Guarantees of communication equipment
(UHF)
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type To be filled in
1.4 Model To be filled in
1.5 Applicable Standards To be filled in
1.6 Configuration Duplicate
1.7 Type Test
 Date of carriedout To be filled in
 Testing laboratory name and
To be filled in
country
 Certificate Provided Yes/No
2 ELECTRICAL DATA
2.1 Auxiliary power supply V DC 12 ±15%
2.2 Power consumption W To be filled in
 Transmit(Maximum) A To be filled in
 Receive(Maximum) A To be filled in
2.3 Rated Frequency Hz 50
2.4 Input Power VA To be filled in
3 DESIGN DETAIL
3.1 Power output W To be filled in
3.2 Frequency setting range: MHz 335.4〜470
Frequency is
 Frequency transmit andreceive MHz
decided after
Contract
Communication method
3.3 F2D/F3E ,Simplex/half duplex/full To be filled in
duplex)
3.4 Antenna Impedance Ω To be filled in
3.5 Transmission Rate kbps To be filled in
Modulation method: MSK To be filled in
3.6
(Minimum shift keying)
3.7 Interface RS-232C
 Transmission Rate Kbps To be filled in
 Communication procedure:
Yes
ASYNCasynchronous
3.8 Telephone call by headset Yes
4 DIMENSION AND WEIGHT
4.1 Overall dimensions (L x W x H) m To be filled in
4.2 Total weight kg To be filled in

Technical Particulars and Guarantees of communication equipment


(WiMAX)
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type To be filled in
1.4 Model To be filled in
1.5 Applicable Standards To be filled in
1.6 Configuration Duplicate
1.7 Type Test
 Date of carried out To be filled in
 Testing laboratory name and
To be filled in
country
 Type test certificate to be issued by Yes/No Yes

24
independent laboratory or independently
witnessed type test will be acceptable to the
Employer
2 ELECTRICAL DATA
2.1 Auxiliary power supply through POE V DC 48 ±15%
2.2 Power consumption W To be filled in
 Transmit(Maximum) A To be filled in
 Receive(Maximum) A To be filled in
2.3 Rated Frequency Hz 50
2.4 VA <17W;Standard;
Power IEEE 802.3at
(PoE);
3 DESIGN DETAIL
3.1 Power output W To be filled in
3.2 RF Band: GHz 3.3 to 3.8 TDD
3.3 up to 120
Mbps UBR,
Data rate up to 100
Mbps
Ethernet rate
3.4 -40 to 75
Operating Temp °C
3.5 120Mbps UBR
with up to
Industry leading 100Mbps Ethernet
throughput using
2 × 2 MIMO
3.6 Lc TDD, ARQ &
adaptive
Per-link dynamic modulation/codin
g
3.7 Yes
All outdoor configurations with IEEE
802.3 at PoE
3.8 >280,000
Processing speed PPS
3.9 Yes
Surge Protection in Built-in: PoE and
RF ports
3.10 <10 ms
Latency
3.11 Yes
Redundancy (1+1 Hot Standby1
(PRP or RSTP compatible)
3.12 IP67 (IEC 60259)
Enclosure
3.13 rh%
Operating relative
humidity range non-
condensing)
3.14 BPSK 1/2 to 64 QAM
Modulation 5/6, 256 QAM
3.15 3 Mbps to 186.6
System Capacity Mbps UBR
3.16 150 km (93 mi)
Max Range
3.17 +30 dBm (Max
combined tx power,
Max Tx Power MIMO
mode/frequency band
specific)
3.18 External MIMO
Antenna Info
3.19 Dynamic Spectrum
Wireless QoS Access &
Management
3.20 512 Kbps to 100
Layer 2 Mbps
3.21 <10 ms
Latency
3.22 To be filled in
Management
3.23 3G and 4G/LTE
To be ideal for next generation networks
3.24
Details of forward error To be filled in
correction
3.25 Details of alarm monitoring facilities
To be filled in
3.26 Details of interfacing with the
Telecommunications Network Management To be filled in
System
3.27 Details of user interfaces
provided To be filled in
3.28 Dimensions (H×W×D)
mm To be filled in
3.29 Mass of complete equipment
kg To be filled in

26
3.30 Vibration
IEC Std To be filled in
3.31 Shock
IEC Std To be filled in
3.32 Mean Time to repair (MTTR)
h To be filled in
3.34 Mean Time between failure (MTBF)
h To be filled in
3.35 Manufacturer quality system in
accordance Y/N Yes
with ISO9000, 9001, 9002, 9003 and 9004
3.36 Used interfaces
Data interfaces
Voice interfaces
Teleprotection interface
Yes
ethernet

3.37 Operating voltage V DC 48 ±15%

Antenna

4 - Manufacturer
- Model reference
- Place of manufacture
- Type and construction material
- Size mm
- Type
- Shape
- Frequency range
- Gain dB
- Half power beam degree
- Input impedance ohm
- Front to back ratio dB To be filled in
- Return loss dB
- Cross polarization discrimination dB
- Power handling W
- VSWR
- Termination
- Azimuth adjustment
4.1 Termination
To be filled in
4.2 Azimuth adjustment
degree To be filled in
4.3 Elevation adjustment
Degree To be filled in
4.4 Method of mounting
To be filled in
4.5 Wind Speed withstand
o Operational m/s To be filled in
o Survival
4.6 Protection rating
IP Std 67
4.7 Manufacturer quality system in
accordance Y/N Yes
with ISO9000, 9001, 9002, 9003 and 9004
4.8  Type test certificate to be issued by
independent laboratory or independently
Y/N Yes
witnessed type test will be acceptable to the
Employer
Antenna Feeder
Cable
5. - Manufacturer
- Type reference
- Place of manufacture
- Type and material of conductor
- Frequency range GHz
- Character impedance Ohm
- Nominal capacitance pF/m
- Attenuation dB/m
- Group delay Ns/m
- Peak power rating
W
- Type of screening
- Type of insulation
- Radial thickness of insulation
- Type of armouring (if any) mm
- Type of sheath
- Nominal overall diameter
- Minimum bending radius mm
- Are cable of flame retardant type? mm
- Cable mass Y/N
Yes
- Operating temperature range. Kg/m

6. Ethernet Rail Switch

6.1 Fast Ethernet 10/100 BASE-TX


Yes
6.2 Interface (RJ45)
Yes
6.3 100Mbit/s
Yes

28
6.4 Temperature
-40 C˚ to 70C˚
6.5 Remotely managed by Network
Management System (NMS).
Yes
7. 2 IP Telephone Yes

8. Cabinet for Communication Equipment.


Yes
- Cabinet IP Std
≥ 54

F) GPS Receiver and Antenna


Technical Particulars and Guarantees of GPS Receiver and Antenna
Specification
No. Description Unit
Required Proposed

A GPS RECEIVER
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type To be filled in
1.4 Model To be filled in
1.5 Applicable Standards To be filled in
1.6 Location of service Indoor
1.7 Type Test
 Date of carriedout To be filled in
 Testing laboratory name and
To be filled in
country
 CertificateProvided Yes
2 ELECTRICAL DATA
2.1 Rated voltage V DC 48 - 220VAC
2.2 Maximum power consumption W To be filled in
2.3 Rated frequency Hz 50
3 DESIGN DETAIL
3.1 Microprocessor based Yes
3.2 Time base Crystal
3.3 Display LED
Calendar:
3.4 Yes
Built-in calendar with leap years
3.5 Battery backup for time keeping Yes
3.6 12 or 24 hour mode Yes
3.7 Inputs GPS
3.8 Temperature Range
 Maximum workingtemperature °C To be filled in
 Minimum workingtemperature °C To be filled in
Non-volatile
3.9 Memory
EEPROM
3.10 Outputs RS485
3.11 Number of clock circuits 2
4 DIMENSION AND WEIGHT
4.1 Dimensions (L x W x H) mm To be filled in
4.2 Mounting (Wall type or Rack type) To be filled in
4.3 Weight kg To be filled in
B ANTENNA of GPS RECEIVER
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Type Active
1.3 Model To be filled in
1.4 Applicable Standards To be filled in
1.5 Location of service Outdoor
2 ELECTRICAL DATA
Operating voltage
2.1 V To be filled in
(Supply by Receiver)
2.2 Maximum power consumption W To be filled in
3 DESIGN DETAIL
3.1 Received Frequency MHz 1575.42±10

30
3.2 Input Impedance Ω 50
3.3 Temperature Range
 Maximum workingtemperature °C To be filled in
 Minimum workingtemperature °C To be filled in
3.4 Peak gain dB 30±3
3.5 Right Polarization Yes
3.6 V. S. W. R. ≤ 1.5:1
3.7 Noise dB ≤ 1.5
3.8 Housing Material PVC
3.9 Max. cable Length m To be filled in
3.10 Connector To be filled in

G ) Coaxial Cable
Technical Particulars and Guarantees of Coaxial Cable
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
With steel wire
1.3 Type
armoured type
1.4 Model To be filled in
IEC60502
1.5 Applicable Standards
&
IEC60228
2 ELECTRICAL DATA
2.1 Impedance 50+/-2 Ohms
2.2 Max. Conductor resistance Ohm/m To be filled in
2.3 Min. Insulation resistance M Ohm To be filled in
2.4 Capacitance pF/M To be filled in
2.5 Velocity of Propagation 66%
15dB (10 to 300
2.6 SRL MHz) 100% Swept
Tested
(dB
2.7 Attenuation at 50MHz To be filled in
/100M)
2.8 AC. Withstand voltage V To be filled in
3 DESIGN DETAIL
3.1 Number of conductor Core one
3.2 Cross sectional area mm² To be filled in
3.3 Material of conductor Bare Copper
3.4 Material of Dielectric PE
3.5 Material of sheath PVC/PE
3.6 Color of Outer Black
Bonded
3.7 Shield
Aluminum Foil
double galvanized
3.8 Armouring
steel wires
3.9 Minimum Bending Radius of cable mm 25
3.10 Overall diameter of cable (Approx.) mm To be filled in
3.11 Net weight (Approx.) (kg/km) To be filled in

H) Optical cable between Equipment


Technical Particulars and Guarantees of Optical Cable between Equipment
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Fiber Multimode
1.4 Model
1.5 Applicable Standards IEC60793-2
1.6 Fiber Type 50/125µm

32
2 OPTICAL DATA
2.1 Minimum Bandwidth 850 nm MHz-km >500
2.2 Maximum Attenuation 850 nm dB-km <3.5
2.3 Group Index of Refraction 850 nm 1.483
2.4 Core Size Microns 50±3
2.5 Cladding Size Microns 125±2
2.6 Coating Size Microns 245±10
2.7 Buffer Size Microns 900±50
2.8 Core Cladding Concentricity Microns ≤3.0
3 PHYSICAL DATA
3.1 Number of fiber count To be filled in
3.2 Overall diameter of cable (Approx.) mm To be filled in
3.3 Material of fiber To be filled in
3.4 Maximum Pulling Tensions
 Installation N To be filled in
 LongTerm N To be filled in
3.5 Material of Outer PVC
3.6 Color of Outer To be filled in
3.7 Net weight (Approx.) kg/km To be filled in
3.8 Minimum Crush Resistance N/mm To be filled in
3.9 Minimum Flex Resistance Cycle To be filled in
3.10 Operating Temperature oC To be filled in
3.11 Minimum Bending Radius
 Installation mm To be filled in
 LongTerm mm To be filled in

I) Metering Devices of Multi function


Technical Particulars and Guarantees of Meters for 33kV Switchgear
Specification
No. Description Unit
Required Proposed
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
Digital type with
1.3 Type
LCD monitor
1.4 Model To be filled in
IEC 60051
1.5 Applicable Standards
and
IEC61554
1) ACCurrent
2) ACVoltage
3) Activepower
1.6 Kind of measurement 4) MWh
(33kV with MDI)
5) MVArh
6) Hz(33kV)
7) cos 33kV)
1.7 Communication Protocol To be fill in

2 ELECTRICAL DATA
2.1 Rated AC input current A 5
2.2 Rated AC input voltage V 110
2.3 Rated Frequency Hz 50
2.4 Insulation resistance at 500V megger MOhm >20
2.5 Dielectric strength (1 minute) ACKV 2
2.6 Mounting Flush mounting
2.7 Protection of housing IP 50
3 DESIGN DETAIL
3.1 Input consumption
 CurrentCircuit VA To be filled in
 VoltageCircuit VA To be filled in
3.2 Accuracy class Class 0.2 or 0.5
3.3 Number of AC input
 Current 3 (R, Y, B)
 Voltage 3 (R, Y, B)

34
Change-over of display of phase :
3.4 Push button
AC Current & Voltage
3.5 Display updating time Sec. To be filled in
3.6 Overload capacity
1.2 times
 CurrentCircuit for
continuous
operation
1.2 times
 VoltageCircuit for
continuous
operation
3.7 Auxiliary power supply V DC 48
3.8 Power consumption VA To be filled in
3.9 Color frame Semi-gloss black

J ) Technical Data of Smart Meter

itm TECHNICAL DESCRIPTION


Service type Three-phase 4-wire(3p4w),CT/VT-connected
Connection 3p4w, 3p3w
Terminal connection Behind-connected
Accuracy class Class 0.2 for kWh, Class 2 for kvarh , Class 1 for kvah
Meter constant To be filled by supplier imp/kW, imp/kvarh (defult)
Real-time clock ≤ 0.5 seconds per day (≤ 5ppm)
Display To be filled by supplier
Operating temperature - 25°c to 70 °c
Limit temperature range of storage -40 °c to 85 °c
Relative humidity Max.95% RH
Ingress protection IP 54 without suction
Insulation protection Class II
Meter life ≥15 years
Data retention ≥20 years
Battery life /type 15 years (internal built-in battery) / Lithium type or
other advance technology
Enclosure material Poly carbonate + Glass fiber
Dimensions ≤ (150 x 170 x 100) mm
Weight To be filled by supplier
INPUT AC VOLTAGE
Nominal voltage (Un) AC 3*63.5/110V
Operating voltage 70% ~ 120% Un
Power consumption ≤ 0.5 VA (per phase)VT
Auxiliary power supply
power supply (48VDC)V DC
power supply (180-250)V AC
INPUT AC CURRENT
Nominal current (In) 1A or 5 A
Max. current (Imax) 10 A
Starting current 2.5 Ma
Overload 10×CT for 1sec.
Burden CT (per phase) ≤ 0.3 VA
MONITRING
Energy Forward &Reverse(MWh, MVARh, MVAh)
Power MW,MVAR,MVA
Voltage VL-L& VL-N
Current IL-L&IN
Frequency 50 Hz ± 5 %

Hint 1: Specifications of C.T & V.T in MoE stations (33) KV are:

• C.T:
Multi ratio programmable, class 0.2 or 1, burden not less than 30 VA.
• V.T:
Multi ratio programmable, class 0.2 or 1, burden 50 VA per phase.

Hint 2: The Meters to be installed inside separate panels in substation

K) Transducers
Technical Particulars and Guarantees of Transducers
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in

36
1.2 Country of Manufacturing To be filled in
1.3 Type To be filled in
1.4 Standards To be filled in
2 ELECTRICAL DATA
2.1 Auxiliary supply voltage V DC 48
2.2 Operating current (CT secondary) A 5

2.3 Operating voltage(VT secondary) V 110


2.4 Frequency Hz 50
2.5 Insulation resistance at 500V megger MOhm >20
2.6 Dielectric strength (1 minute) ACKV 2
2.7 Continuous overvoltage V 1.2 x Rate voltage
2.8 Continuous overcurrent A 1.2 x Rate current
2.9 Response time (0 to 90%) Ms To be filled in
2.10 Burden
 Currentpath VA <5
 Voltagepath VA <2.5
2.11 Accuracy class Class 0.2
2.12 Scale Linear
3 DESIGN DETAIL
A Current Transducer
3.1 Principle (e.g. single phase, 2 wire) To be filled in
Technical Particulars and Guarantees of Transducers
Specification
No. Description Unit
Required Proposed

3.2 Measuring range 30/300/600


3.3 Output range mA DC 4-20
B Voltage transducer
3.1 Principle (e.g. single phase, 2 wire) To be filled in
3.2 Measuring range kV 13, 36
3.3 Output range mA DC 4-20
C Frequency transducer
3.1 Principle (e.g. single phase, 2 wire) To be filled in
3.2 Measuring range Hz 45 -55
3.3 Output range mA DC 4-20
D Power factor transducer
Principle (e.g. 3 phase, 4 wire,
3.1 To be filled in
unbalanced)
3.2 Measuring range Lead 0 -1- Lag 0
3.3 Output range mA DC 4-20
E Active power transducer
Principle (e.g. 3 phase, 4 wire,
3.1 To be filled in
unbalanced)
To be filled in
3.2 Measuring range MW

3.3 Output range mA DC 4-20


F Reactive power transducer
Principle (e.g. 3 phase, 4 wire,
3.1 To be filled in
unbalanced)
To be filled in
3.2 Measuring range MVAr

3.3 Output range mA DC 4-20


G Communication Protocol (for all type
To be filled in
Transducer )

L) LV AC Distribution Panel

Technical Particulars and Guarantees of LV AC Distribution


Panel

38
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
Metal-clad totally
1.3 Type
enclosed
1.4 Model To be filled in
1.5 Applicable Standards IEC 60439
1.6 Location of services Indoor
1.7 Degree of protection IP 41
2 ELECTRICAL DATA
400/230V,±1
2.1 Rated AC voltage V
0%
3pase 4 wires
Power frequency
2.2 KVrms 3
withstand test voltage
2.3 Rated short circuit current , 1sec. KA 30
2.4 Control supply voltage
• Trip and closing coil V DC48
• Spring charging motors V DC48
3 DESIGN DETAIL
A AIR BREAK CIRCUIT BREAKER (INCOMING)
1.1 Manufacturer Name To be filled in
1.2 Type MCCB
1.3 Model To be filled in
1.4 Applicable Standards IEC 60947-2
1.5 Rated current A 150
Thermal &
1.6 Protection
Magnetic
B BUSBAR
Rated current of busbars at 55°C
2.1 A 250
ambient temperature
2.2 Busbar cross section mm2 To be filled in
2.3 Busbar insulation material To be filled in
C DETAILS OF MCBs
1.1 Manufacturer Name To be filled in
1.2 Type Molded
Case
1.3 Model To be filled in
1.4 Applicable Standards IEC 60947-2
1.5 Site current rating (at 55°C) A To be filled
1.6 Rated short time current (3 s) kA To be filled
1.7 Typical circuit diagram number To be filled
Thermal &
1.8 Protection
Magnetic
D DETAILS OF UNDER VOLTAGE PROTECTION
1.1 Manufacturer Name To be filled in
1.2 Type To be filled in
1.3 Model To be filled in
1.4 Catalogue Provided Yes
E INSTRUMENTS
1.1 Manufacturer Name To be filled in
1.2 Type of meter
• Voltmeter To be filled in
• Ammeter To be filled in
1.3 Catalogue Provided Yes
Single line diagram &
F To be filled in
Arrangement drawing number
4 DIMENSION AND WEIGHT
Overall dimensions of
Distribution Panel m To be filled in
(L x W x H)
Total weight of Distribution Panel kg To be filled in

M) Over current / Earth Fault Protection


Technical Particulars and Guarantees of Over current / Earth Fault protection
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in

40
1.2 Country of Manufacturing To be filled in
1.3 Type Numerical
1.4 Model To be filled in
IEC 60255/IEC
1.5 Applicable Standards
60068
2 ELECTRICAL DATA
2.1 Auxiliary power supply V DC 48
2.2 Maximum power consumption W To be filled in
2.3 Rated AC input current A 5
2.4 Maximum burden VA To be filled in
2.5 Rated AC input voltage V N/A
2.6 Maximum burden VA To be filled in
2.7 RatedFrequency Hz 50
2.8 Mounting Flush mounting
2.9 Protection of relay housing IP 50
3 DESIGN DETAILS
3.1 Over current relay
• Current settingrange % To be filled in
• Current settingrange % To be filled in
(Instantaneous)

• Time settingrange sec To be filled in


• Time-currentcharacteristics To be filled in
3.2 Earth fault relay
• Current settingrange % To be filled in
• Current setting range
% To be filled in
(Instantaneous)
• Time settingrange sec To be filled in
• Time-currentcharacteristics To be filled in
3.3 Integral metering functions Yes
3.4 Programmable scheme logic Yes
3.5 Event and Fault recording functions Yes
3.6 Self-monitoring facility Yes
3.7 Trip circuit supervision Yes
User-friendly HMI, Windows
3.8 based software for relay Yes
setting, relay configuration and
event,
disturbance and fault record
Rated voltage of tripping contacts
3.9 V 250 AC/DC
-Continuous5A
4 COMMUNICATIONS
Front panel localPC
4.1 To be filled in
communicationport
Rear panel RTU fiber optic
4.2 communication port (ST Yes
type connector)
4.3 Name of protocols (IEC60870-5-103) Yes
Ether LAN Interface
4.4 Yes
communication port (IEC61850)
4.5 Transmission speed To be filled in
N) Trip Circuit Supervision (TCS)

Technical Particulars and Guarantees of Trip Circuit Supervision


Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type To be filled in
1.4 Model To be filled in
IEC 60255/IEC
1.5 Applicable Standards
60068
2 ELECTRICAL DATA
2.1 Auxiliary power supply V DC 48
3 DESIGN DETAILS
3.1 Voltage of monitored circuit V DC 48
3.2 Measuring current typ. mA To be filled in
3.3 Operate delay time Sec. To be filled in
Supervision of the whole trip
3.4 Yes
circuit with CB open and closed.
3.5 Relay operatedindicator/LED Yes
3.6 Output Relay

42
• 2 x C(1a+1b) Yes
• Rated voltage 250 VAC/DC
• Rated current ofcontacts
A To be filled in
• -Continuous
O) Multi Contact Tripping Relay

Technical Particulars and Guarantees of Multi Contact Tripping Relay


Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type To be filled in
1.4 Model To be filled in
IEC 60255/IEC
1.5 Applicable Standards
60068
2 ELECTRICAL DATA
2.1 Auxiliary power supply V DC48
3 DESIGN DETAILS
3.1 Number of Contacts To be filled in
3.2 Ratedvoltage 250 VAC/DC
Rated current of contacts
3.3 A To be filled in
-Continuous
3.4 Operating time To be filled in
Is relay mechanically latched or
3.5 To be filled in
self resetting
Method used to reset latched relay
3.6 To be filled in
(hand or electrical)
3.7 Burden at rated voltage To be filled in
Minimum voltage at which
3.8 To be filled in
reliable operation occurs
3.9 Relay operated indicator type To be filled in

44
45

P) 33kV Load Shedding Frequency Relay (for incomer)

Technical Particulars and Guarantees of 33 kV Load Shedding Frequency Relay


Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type Numerical
1.4 Model To be filled in
IEC
1.5 Applicable Standards
60255/IE
C 60068
1.6 Type Test
• Date of carriedout To be filled in
• Testing laboratory nameand To be filled in
• Certificate Provided Yes
2 ELECTRICAL DATA
2.1 Auxiliary power supply V DC 48
2.2 Maximum power consumption W To be filled in
2.3 Rated AC input voltage V 110
2.4 Maximum burden VA To be filled in
2.5 Rated Frequency Hz 50
2.6 Mounting Flush mounting
2.7 Protection of relay housing IP 50
3 DESIGN DETAILS
Number of programmable
3.1 To be filled in
output relays
Independent time delay setting
3.2 Yes
for each stage
3.3 Number of frequency stages 4
3.4 Frequency setting range Hz To be filled
in
3.5 Delay times sec To be filled
in
3.6 df/dt testing range To be filled
in

3.7 Number of contacts for each stage To be filled


in
Flush mounting/cubicle
3.8 Yes
mounting, terminals on the rear
3.9 Frequency measurement accuracy Hz To be filled
in
3.10 Voltage supervision/blocking To be filled
in
3.11 Busbar VT changeover facility To be filled
in
3.12 Integral metering functions Yes
3.13 Opto-isolator inputs Yes
3.14 Programmable scheme logic Yes
3.15 Event and Fault recording functions To be filled
in
3.16 Self-monitoring facility Yes
Independent frequency rate of
3.17 Yes
Change for each stage df/dt
3.18 under/over voltage Yes
Remote operation of each
3.19 Yes
under frequency stage
Rated voltage of tripping contacts
3.20 V 250 AC/DC
-Continuous5A
4 COMMUNICATIONS
Front panel localPC
4.1 To be filled
communicationport
in
Rear panel RTU fiber optic
4.2 communication port (ST Yes
type connector)
4.3 Name of protocols (IEC60870-5-103) Yes
Ether LAN Interface
4.4 Yes
communication port (IEC61850)
4.5 Transmission speed To be filled
in

Q) Voltage Earth fault Relay ( for incomer)

Technical Particulars and Guarantees of Voltage Earth fault Relay

46
47

Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type Numerical
1.4 Model To be filled in
IEC 60255/IEC
1.5 Applicable Standards
60068
2 ELECTRICAL DATA
2.1 Auxiliary power supply V DC 48
2.2 Maximum power consumption W To be filled in
2.3 Rated voltage (Un) V 110
2.4 Continuous withstand V 2 x Un
2.5 Maximum burden VA To be filled in
2.6 Rated Frequency Hz 50
2.7 Mounting Flush mounting
2.8 Protection of relay housing IP 50
3 DESIGN DETAIL
3.1 Start Voltage Uo>0 To be filled in
3.2 Start time, typically To be filled in
3.3 Operate time t> To be filled in
3.4 Drop-off/pick-up ratio, typically To be filled in
3.5 Setting range To be filled in
4 COMMUNICATIONS
Front panel localPC
4.1 To be filled in
communicationport
Rear panel RTU fiber
4.2 optic communication Yes
port
4.3 Name of protocols (IEC60870-5-103) Yes
Ether LAN Interface
4.4 Yes
communication port (IEC61850)
4.5 Transmission speed To be filled in

R) Under Voltage Protection (for incomer)


Technical Particulars and Guarantees of Under Voltage Protection
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type Numerical
1.4 Model To be filled in
IEC 60255/IEC
1.5 Applicable Standards
60068
2 ELECTRICAL DATA
2.1 Auxiliary power supply V DC48
2.2 Maximum power consumption W To be filled in
2.3 Rated AC input voltage V 111
2.4 Maximum burden VA To be filled in
2.5 RatedFrequency Hz 50
2.6 Mounting Flush mounting
2.7 Protection of relay housing IP 50
3 DESIGN DETAIL
3.1 Voltage setting range To be filled in
3.2 Voltage/time characteristics To be filled in
3.3 Time delay setting range To be filled in
3.4 Voltage pick up/resetratio To be filled in
4 COMMUNICATIONS
Front panel localPC
4.1 To be filled in
Communicationport
Rear panel RTU fiber
4.2 Yes
optic communication
4.3 Name of protocols (IEC60870-5-103) Yes
Ether LAN Interface
4.4 Yes
communication port (IEC61850)
4.5 Transmission speed To be filled in

S) Over Voltage Protection (for incomer)


48
49

Technical Particulars and Guarantees of Over Voltage Protection


Specification
No. Description Unit
Required Proposed

1 GENERAL
1.6 Manufacturer Name To be filled in
1.7 Country of Manufacturing To be filled in
1.8 Type Numerical
1.9 Model To be filled in
IEC 60255/IEC
1.10 Applicable Standards
60068
2 ELECTRICAL DATA
2.8 Auxiliary power supply V DC48
2.9 Maximum power consumption W To be filled in
2.10 Rated AC input voltage V 110
2.11 Maximum burden VA To be filled in
2.12 RatedFrequency Hz 50
2.13 Mounting Flush mounting
2.14 Protection of relay housing IP 50
3 DESIGN DETAIL
3.12 Voltage setting range To be filled in
3.13 Voltage/time characteristics To be filled in
3.14 Time delay setting range To be filled in
3.15 Voltage pick up/resetratio To be filled in
4 COMMUNICATIONS
Front panel localPC
4.6 To be filled in
communicationport
Rear panel SCS fibre
4.7 Yes
optic communication
4.8 Name of protocols (IEC60870-5-103) Yes
Ether LAN Interface
4.9 Yes
communication port (IEC61850)
4.10 Transmission speed To be filled in

T) Unbalance Protection Relay


Technical Particulars and Guarantees of Unbalance protection relay
Specification
No. Description Unit
Required Proposed
1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type Numerical
1.4 Model To be filled in
IEC 60255/IEC
1.5 Applicable Standards
60068
1.6 Type Test
• Date of carriedout To be filled in
• Testinglaboratoryname
To be filled in
andcountry
• CertificateProvided Yes
2 ELECTRICAL DATA
2.1 Auxiliary power supply V DC 48
2.2 Maximum power consumption VA To be filled in
2.3 Rated AC input current A 5
2.4 Maximum burden VA To be filled in
2.5 RatedFrequency Hz 50
2.6 Mounting Flush mounting
2.7 Protection of relay housing IP 50
3 DESIGN DETAIL
3.1 Measuring rate (Measurement/Sec) /sec To be filled in
3.2 Actualization of indication /sec To be filled in
3.3 Measurementaccuracy % < 1.0
3.4 Relay output
3.5 Maximum switching Voltage V N/A
3.6 Maximum switching Power W N/A
3.7 Maximum switching frequency Hz N/A
3.8 No. of contacts To be filled in

50
51

3.9 Discharge time for the capacitors Min. N/A


3.10 Overload capacity To be filled in
Setting Range Alarm :(0-5A)
3.11 Separately for each yes
measurement channel
Setting Range switch-off :(0-5A)
3.12 Separately for each yes
measurement channel
Setting Range Time Delay Alarm
3.13 To be filled in
(assignable value)
Setting Range Time Delay switch-off
3.14 To be filled in
(assignable value)
4 COMMUNICATIONS
Front panel localPC
4.1 To be filled in
communicationport
Rear panel RTU fiber
4.2 optic communication Yes
Port
4.3 Name of protocols (IEC60870-5-103) Yes
Ether LAN Interface
4.4 Yes
communication port (IEC61850)
4.5 Transmission speed To be filled in
U) 33kV XLPE insulated Single core Power Cables to Aux.TR(unarmored)

Technical Particulars and Guarantees of 33 kV XLPE insulated Single core Power Cables
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
(Accordingto
1.3 Type MoE
specifications
)
1.4 Rated voltage(Uo/U) kV 18/30
1.5 Highest system voltage (Umax) kV 36
IEC60502-2 &
1.6 Applicable Standards
IEC60228
1.7 Type Test
• CertificateProvided Yes
2 ELECTRICAL DATA
2.1 Rated Frequency Hz 50
2.2 AC. Withstand voltage for 5 minutes kV rms 63
2.3 Impulsewithstandvoltage(1.2/50µs) kV peak 170
2.4 Max. DC Conductor resistance at ohm/km 0.387
2.5 Max. Temperature rating of ◦C 90
3 DESIGN DETAIL
3.1 Number of conductor Core 1
3.2 Cross sectional area (Phase) mm² 50
Compacted
3.3 Shape of Conductor
circular
stranded
Annealed
3.4 Material of Conductor
Copper
Wires
3.5 Weight of Conductor (Approx.) kg/km To be filled in
3.6 Material of insulation XLPE
3.7 Insulation thickness (Nominal) mm 8

V) LV PVC insulated Single core Power Cables(Unarmored)

Technical Particulars and Guarantees of LV PVC insulated Single core Power Cables
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
(Accordingto
1.3 Type MoE
specifications
)
1.4 Rated voltage(Uo/U) kV 0.6/1.0
IEC60502-1 &
1.5 Applicable Standards
IEC60228
2 ELECTRICAL DATA
2.1 RatedFrequency Hz 50
2.2 AC. Withstand voltage V 3500
52
53

2.3 Temperature rating of conductor ◦C 70


3 DESIGN DETAIL
3.1 Number of conductor Core 1
3.2 Cross sectional area (Phase) mm² 150
Compacted
3.3 Shape of Conductor
circular
stranded
Annealed
3.4 Material of Conductor
Copper
Wires
3.5 Material of insulation PVC
3.6 Insulation thickness (Nominal) mm To be filled in
Maximum DC resistance of
3.7 ohm/km 0.124
conductor at 200C
Insulation resistance between
3.8 M ohm To be filled in
core/ screen
3.9 Material of sheath PVC
3.10 Color of sheath Black
Max. current rating (touching
3.11 A To be filled in
flat formation) in ground at 35
3.12 Rated short-time current for 1 sec. kA 27
Minimum Bending Radius of Cable
3.13 mm To be filled in
(during installation)
3.14 Overall diameter of cable (Approx.) mm To be filled in
3.15 Net weight (Approx.) kg/km To be filled in
W) LV PVC insulated Multi core Power Cables
Technical Particulars and Guarantees of LV PVC insulated Multi core Power Cables
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type CU/PVC/PVC
1.4 Rated voltage(Uo/U) kV 0.6/1.0
IEC60502-1
1.5 Applicable Standards
&
IEC60228
2 ELECTRICAL DATA
2.1 RatedFrequency Hz 50
2.2 AC. Withstand voltage V 3500
2.3 Max. Temperature rating of ◦C 90
3 DESIGN DETAILS
3.1 Number of conductor Core To be filled in
As per
3.2 Cross sectional area (Phase) mm²
specification
Compacted
3.3 Shape of conductor
circular
stranded
Annealed
3.4 Material of conductor
Copper
Wires
3.5 Material of insulation PVC
3.6 Material of sheath PVC
3.7 Color of sheath Black
Overall diameter of cable
3.8 mm To be filled in
(Approx.) Each of cables
3.9 Net weight (Approx.) kg/km To be filled in

X) LV PVC Control & Signal Cables

Technical Particulars and Guarantees of Control & Signal Cables


Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type CU/PVC/PVC
1.4 Rated voltage(Uo/U) kV 0.6/1.0
IEC60502-1 &
1.5 Applicable Standards
IEC60228
2 ELECTRICAL DATA
2.1 RatedFrequency Hz 50
2.2 AC. Withstand voltage V 3500
2.3 Max. Temperature rating of ◦C 90

54
55

3 DESIGN DETAIL
3.1 Number of conductor Core Multi
3.2 Cross sectional area mm² Min. 1.5
Compacted
3.3 Shape of conductor
circular
stranded
Annealed
3.4 Material of conductor
Copper
Wires
3.5 Material of insulation PVC
3.6 Material of sheath PVC
3.7 Color of sheath Black
Bonded
3.8 Shield
Aluminum
Foil
double
3.9 Armouring
galvanized
steelwires
3.10 Overall diameter of cable (Approx.) mm To be filled in
3.11 Net weight (Approx.) kg/km To be filled in

Y) Grounding System
Technical Particulars and Guarantees of Grounding System
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
Bare stranded
1.3 Type annealed
copper Wires
IEC60502 &
1.4 Applicable Standards
IEC60228,
BS6360
2 DESIGN DETAIL
2.1 Main ground grid conductor Copper
2.2 Standards IEEE 80
2.3 Main ground grid conductor size mm2 ≥ 95
Depth and burial of main
2.4 mm To be filled in
ground conductor
2.5 Length and diam. of ground rod mm 2500/19
2.6 Material of ground rod Copper weld

Z) Ampere Meters

Technical Particulars and Guarantees of Ampere Meters for incmers, Feeder, Bus &
Aux.TR
Specification
No. Description Unit
Required Proposed

1 GENERAL
1.1 Manufacturer Name To be filled in
1.2 Country of Manufacturing To be filled in
1.3 Type Numerical
1.4 Model To be filled in
IEC 60051 and
1.5 Applicable Standards
IEC61554
2 ELECTRICAL DATA
2.1 Rated AC input current A 5
2.2 Maximum burden VA To be filled in
2.3 RatedFrequency Hz 50
2.4 Insulation resistance at 500V megger MOhm >20
2.5 Dielectric strength (1 minute) ACKV 2
2.6 Mounting Flush mounting
2.7 Protection of housing IP 50
3 DESIGN DETAIL
3.1 Scale 30, 300,600
Number of AC input
3.2 3 (R, Y, B)
Current
3.3 Accuracy class Class 0.2
3.4 Maximum demand Yes
3.5 Color frame Semi-gloss black

56