You are on page 1of 2

COMPANY: Contract No.

:
QATARGAS OPERATING COMPANY LIMITED LTC/C/NFE/3998/18
PROJECT:
Doc. No.:
RLTO EXPANSION AND OFFPLOT FACILITIES OF THE
301-83-SH-SPC-00007
NORTH FIELD EXPANSION PROJECT (EPC-3)
CONTRACTOR: Rev. 0
TECNICAS REUNIDAS S.A. PAGE 23 OF 27
Doc. Title: RLTO - TECHNICAL SPECIFICATION FOR FIREPROOFING

APPENDIX B. FIREPROOFING MATERIALS

Product Name Required Thickness Approval Date


Method Added
15 Minute 30 Minute 1 Hour 2 Hour
Rating Rating Rating Rating
3M Interim E5-3A &4A 0.40 in 0.30 in 0.60 in Mobil Test Facility Jul-91
(1 wrap (1 wrap (2 wraps
E-5A-4) E-5A-3) E-5A-3)
Aerex Panels 1.00 in 1.5 in UL 1709 Jul-91
AP Green lnswool 3.00 in Mobil Test Facility Oct-91
(structural steel only,
not cable trays)

Albi Clad-800 0.20 in 0.32 in Mobil Test Facility Jul-91


(epoxy intumescent) (M*) (M*)
Albi Clad-800 0.25 in 0.51 in UL 1709 Jul-91
(epoxy intumescent) (F*)
Carboline Pyrocrete 240 0.50 in 1.00 in Mobil Test Facility Jul-91
(M*) (M*)
Carboline Pyrocrete 240 0.81 in 1.38 in UL 1709 Jul-91
(M*) (M*)
Carboline Pyrocrete 241 0.50 in 1.00 in Mobil Test Facility Jul-91
(M*) (M*)
Carboline Pyrocrete 241 0.69 in 1.13 in UL 1709 Jul-91
(M*) (M*)
Carboline Pyrocrete 0.38 in FM Jul-91
241 (M*)
Carboline Pitt 0.20 in 0.40 in Mobil Test Facility Jul-91
-Char XP (epoxy intumescent) (M*) (M*)
Carboline Pitt 0.28 in 0.52 in UL 1709 Jul-91
-Char XP (epoxy intumescent) (F*) (F*)
Carboline Pitt 0.16 in 0.31 in UL 1709 Feb-2022
-Char NX (epoxy intumescent) (M*) (M*)
Darchem Darmatt Blanket 4 layers Mobil Test Facility Jul-91
for cable trays 4 lb/ft3

Leighs Paints Firetex M90 5.45 mm 8.63 mm 14.99 mm UL 1709 Aug- 2006
Lloyd's Register
Warrington fire
Leighs Paints Firetex M93 6.51 mm 12.88 mm UL 1709 Aug- 2006
Lloyd's Register
Mandoval Mandolite 0.50 in 0.90 in Mobil Test Facility Jul-91
550 (M*) (M*)
Mandoval Fendolite 0.50 in 1.00 in Mobil Test Facility Jul-91
MIi (M*) (M*)
Mandoval Fendolite 1.00 in 1.44 in UL 1709 Jul-91
MIi (M*) (M*)
Pabco Super Firetemo M 0.75 in 1.25 in UL 1709 Jul-91

Pittsburg Corning Foamglas 4.00 in UL 1709 May-95


Super K or T-4 in Europe per other oil
(API 520/1 factor =0.3, SS company specs
jacketing >0.7 mm thickness)

This document is property of Técnicas Reunidas. Its reproduction without a written permission is strictly forbidden.
COMPANY: Contract No.:
QATARGAS OPERATING COMPANY LIMITED LTC/C/NFE/3998/18
PROJECT:
Doc. No.:
RLTO EXPANSION AND OFFPLOT FACILITIES OF THE
301-83-SH-SPC-00007
NORTH FIELD EXPANSION PROJECT (EPC-3)
CONTRACTOR: Rev. 0
TECNICAS REUNIDAS S.A. PAGE 24 OF 27
Doc. Title: RLTO - TECHNICAL SPECIFICATION FOR FIREPROOFING

Product Name Required Thickness Approval Date


Method Added
15 Minute 30 Minute 1 Hour 2 Hour
Rating Rating Rating Rating
Pittsburg Corning Foamglas 3.0 in Jul-91
with lnteram E-5A Mat

Pyrotenax Ml Cables Alloy 82 Alloy 825 Mobil Test Facility Jul-91


Ni Clad Ni Clad
Superior Energies Temp 2.00 in Mobil Test Facility Jul-91
Set Blanket for cable trays (Cable trays
only)
Textron Coroc II Panels 2.00 in UL 1709 Jul-91

Textron Chartek IV 0.27 in 0.55 in UL 1709 Apr-96


(epoxy intumescent) (M*) (M*)
Thermal Ceramics 1.0 in blanket 1.0 in lb/W 1.5 in Mobil Test Facility Jul-91
Firemaster Blanket, w/ SS covered by blanket 8 lb/ft3
Encapsulation 0.5 in SS blanket
encap.
8 lb/ft3
blanket

Thermal Designs, 0.50 in Mobil Test Facility Jul-92


K-Mass molded electrical
boxes and
MOV actuators
Thermal Sciences Thermo- 0.20 in 0.30 in Mobil Test Facility Jul-91
lag 440 (M*) (M*)
Thermal Sciences Thermo- 0.28 in 0.67 in UL 1709 Jul-91
lag 440 (F*) (F*)
Thermal Sciences Thermo- 0.22 in 0.44 in UL 1709 Nov-95
lag 2000 (F*) (F*)
Unipad Blanket for cable UP 15/18/24 UP34 UL1709 Feb-96
trays Conducted by
Omega Point
Labs
M Designates materials that require installation with wire mesh reinforcement
F Designates materials that require installation with fiberglass ribbon reinforcement
UL 1709 Underwriters Laboratory High Rise Fire Test (W10 x 49 Column 9 ft High)
FM Tested and listed by Factory Mutual for LPG vessels Southwest Research Institute
SRI Southwest Research Institute

In case jet fire were considered, materials will comply with certification of product from manufacturers
for the proper jet fire application.

This document is property of Técnicas Reunidas. Its reproduction without a written permission is strictly forbidden.