You are on page 1of 1

GENERAL :

A. MATERIALS AND WORKMANSHIP SHALL CONFORM WITH THE


REQUIREMENTS OF THE FOLLOWING BUILDING CODES.
1. ACI 318 - 14
2. ASEP SEISMIC DESIGN GUIDE
CONSTRUCTION NOTES
3. NSCP - 2015 EDITION
4. UBC 1997 STRUCTURAL STEEL :
BEAM
B. ALL DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION lb1 lb2

PURPOSES UNLESS OTHERWISE INDICATED. 1. ALL STUCTURAL STEEL SHALL CONFORM TO ASTM A-36. SEE NOTE A SEE NOTE A
5-10MMØ BARS 150MM
BAR SPACES DIA.
C. FOR ALL OTHER REQUIREMENTS , REFER TO ARCHITECTURAL , SPACED AT 200 MM O.C.

SANITARY , ELECTRICAL AND MECHANICAL WORKING DRAWINGS.


2. WELDING SHALL CONFORM TO AWS STANDARDS. 1 2
NOT LESS THAN
20MM

3. FABRICATOR SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL BY LAPS SEE

100MM
50MM
FOOTINGS : CALCULATED BOND
LENGTH BUT
NOTE E

30Ø OR 600MM
1. FOOTINGS ARE DESIGNED TO REST ON FIRM SUBGRADE
WITH MINIMUM BEARING CAPACITY OF 3, 000 psf THE ENGINEER AND THE OWNER.
2. NO FOOTING SHALL REST ON FILL. 2h 2h 5-10MMØ BARS
SPACED AT 200 MM O.C.
3. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL NO LAPS ZONE
1
SEE NOTES
D,F&G 2 SEE NOTE D FOR ALL TYPICAL SLAB DEPRESSION DETAIL
BE 70 MM CLEAR FOR CONCRETE DEPOSITED AGAINST THE SEE NOTE D MINIMUM STEEL LAPS CALCULATED
SEE NOTE B LAP LENGTH
FORMWORK. BUT 300MM
40MM CLEAR
DISTANCE (MINIMUM)
END SPAN INTERNAL
CONCRETE MIXES & PLACINGS : DETAIL - 3 SUPPORT SUPPORT
1. UNLESS OTHERWISE SPECIFIED , THE MINIMUM 28-DAY CYLINDER h 500MM
40MM CLEAR DIST.

10
40MM CLEAR

00
COMPRESSIVE STRENGTH ARE AS FOLLOWS : (MINIMUM) FOR DISTANCE (MINIMUM)

FOOTINGS AND BEAMS ON GRADE 3, 000 psi


BEAMS & GIRDERS
SEE NOTE - A SEE NOTE - A 10 A. CURTAILMENT OF TOP BARS TO BE TENSION BOND LENGTH BEYOND THE POINT OF
TRIMMERS MAY BE 00
COLUMNS 3, 000 psi DETAIL - 1 OMITTED WHERE CONTRAFLEXURE BUT NOT LESS THAN lb/4 FROM SUPPORT , IF SOME BARS ARE 50MM
OPENING IS FRAMED
SLABS , BEAMS AND GIRDERS 3, 000 psi BY BEAMS CURTAILED AT SHORTER DISTANCES AT LEAST A THIRD OF TOTAL STEEL MUST
BEARING AND RETAINING WALLS 3, 000 psi EXTEND THIS DISTANCE.
C h
BEDDED SLABS , CATCH BASINS AND SIDEWALK 2,500 psi

2. ALL CONCRETE MUST BE DEPOSITED , VIBRATED AND CORED IN 2-16MMØ AT MINIMUM 1-16MMØ
B. THE AREA OF BOTTOM OF STEEL PROVIDED AT THE SUPPORTS MUST EQUAL AT
TYPICAL BEAM-COLUMN EACH CORNER
ACCORDANCE WITH ACI STANDARD 318-89. INTERCONNECTION
TOP & BOTTOM FOR LEAST HALF THE AREA OF THE TOP STEEL AT THAT SECTION.
NOTE : SLABS 125MM THK.
AND OVER
50MM

3. STRIPPING FORMS AND SHORES SHALL BE AS FOLLOWS : A. STIRRUP SPACING IN PLASTIC HINGE ZONE OF LENGTH 2h OPENING C. A MIN. OF 1/4 OF THE LARGER AMOUNT OF TOP STEEL REQUIRED AT EITHER END 500MM 10MMØ TIES AT 150MM O.C.
FOUNDATION 1 DAY SHALL BE THE LEAST OF ; 1. D/4 2. 6Ø 3. 150MM. HOOK SLAB MUST CONTINUE FOR THE WHOLE LENGTH OF THE SPAN.
EXTENDED TRIMMER BAR
COLUMNS & WALLS 3 DAYS B. Ø = DIAMETER OF MAIN LONGITUDINAL BAR FOR DISTANCE REINFORCEMENT 1000MM BEYOND SIDES
OVER TRIMMER BAR OF OPENING OR AS FAR
BEAMS & GIRDERS 21 DAYS D. NO LAPS IN TOP & BOTTOM TO OCCUR WITHIN A DISTANCE OF 2h FROM FACE OF
UNDER CONSIDERATION IN TOP OR BOTTOM WHICHEVER IS AS POSSIBLE & HOOK.
SLABS 17 DAYS SUPPORT .
SMALLER.
4. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT
SEGREGATION RE-HANDLING OR FLOWING. PLACING SHALL BE
C. THIS STIRRUP SPACING CONTINUES WITHIN THE INTERMEDIATE E. LAPS ARE TO BE KEPT TO A MINIMUM AND CRANKS IF REQUIRED TO BE AS FOR TYP. BEAM DEPRESSION DETAIL
DONE PREFERABLY WITH BUGGIES , BUCKET OR WHEELBARROWS. ZONE. COLUMNS.
NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE SCHEDULE - 1 PROVIDE EXTRA BAR
(NOT SHOWN) PARALLEL 1000
FROM HOPPERS TO BUGGIES , WHEELBARROWS OR BUCKETS IN TO SIDES OF EQUAL AREA F. IF h > 750MM PROVIDE EXTRA LONGITUDINAL BARS FOR 2/3 OF THE BEAM DEPTH
OF INTERRUPTED SLAB
WHICH CASE THEY SHALL NOT EXCEED SIX (6.0) IN METER IN CONCRETE HOLLOW BLOCK REINFORCEMENT REINFORCEMENT LESS FROM THE TENSION FACE WITH SPACING > 250MM.
AGGREGATE LENGHT. NO DEPOSITING OF CONCRETE SHALL BE BLOCK REINFORCEMENT NOTES AREA TRIMMER BARS.

ALLOWED WITHOUT THE USE OF VIBRATORS. UNLESS AUTHORIZED THICK HORIZONTAL VERTICAL A. MINIMUM SPLICE AT LAP = 300MM
G. LAPS IN FRAMING BARS TO BE STAGGERED RELATIVE TO LAPS IN MAIN TOP AND
B. PROVIDE RIGHT ANGLE REINF. t
75 MM 10MM AT 600MM O.C. 10MM AT 600MM O.C. DETAIL - 4
IN WRITING BY THE DESIGNERS AND ONLY FOR USUAL CONDITIONS 100MM 10MM AT 600MM O.C. 10MM AT 600MM O.C.
AT CORNERS 1000MM LONG.
C. WHERE CHB WALLS ADJOINING COLS.
BOTTOM BARS.
WHERE VIBRATORS IS EXTREMELY DIFFICULT TO ACCOMPLISH. R.C. BEAMS. WALL DOWELS W/ SAME b b ANCHORAGE OUTSIDE
150MM 12MM AT 600MM O.C. 12MM AT 600MM O.C. PANEL ZONE PQRS
SIZE AS VERT. REINF. SHALL BE
200MM
BEAMS AND GIRDERS : 12MM AT 600MM O.C. 12MM AT 600MM O.C. PROVIDED.
P Q TYP. SLAB CONSTRUCTION JOINT
1. CAMBER ALL BEAMS AND GIRDERS AT LEAST 6.50 MM FOR EVERY
3.0 M. OF SPAN. SCHEDULE - 2
h
2. FOR TWO OR MORE LAYERS OF REINFORCING BARS USE SEPARATORS
WALL REINFORCEMENT VERTICAL
SPACED AT 1.0 M. O.C. AND IN NO CASE SHALL BE LESS THAN REMARKS
THK. HORIZONTAL VERTICAL SECTION S R
TWO (2) SEPARATORS. 10MM AT 250MM O.C. 10MM AT 300MM O.C.
HORIZONTAL & CENTER VERTICAL 1-1 2-2
100MM BARS STAGGERED OUTSIDE.
125MM 10MM AT 250MM O.C. 10MM AT 250MM O.C. - DO -
3. NO SPLICE SHALL BE PERMITTED ON BEAMS AND GIRDERS WHERE BOTH FACES HORIZONTAL BEAMS FORMING PART OF A ALTERNATIVE PREFERRED b
150MM 12MM AT 250MM O.C. 12MM AT 300MM O.C
CRITICAL BENDING STRESSES IS OCCUR. TENSION SPLICE SO PERMI-
SHALL BE INSIDE.
DUCTILE MOMENT RESISTING END SUPPORT DETAIL
175MM 12MM AT 200MM O.C. 12MM AT 250MM O.C. - DO -

TTED SHALL BE 60 DIAMETER FOR PLAIN BARS AND 40 DIAMETER 200MM 12MM AT 300MM O.C. E.F. 12MM AT 300MM O.C. BOTH FACES HORIZONTAL FRAMEWORK
SHALL BE OUTSIDE.
12Ø
FOR DEFORMED BARS. 225MM 12MM AT 200MM O.C. E.F. 12MM AT 250MM O.C. E.F. - DO -

COMPRESSION SPLICE SHALL BE 40 DIAMETERS FOR PLAIN BARS


AND 30 DIAMETERS FOR DEFORMED BARS. LAP SPLICES SHALL BE
250MM
275MM
300MM
12MM AT 300MM O.C. E.F.
12MM AT 250MM O.C. E.F.

12MM AT 200MM O.C. E.F.


12MM AT 300MM O.C. E.F.
12MM AT 300MM O.C. E.F.
12MM AT 275MM O.C. E.F.
- DO -

- DO -

- DO -
CONCRETE COLUMNS : PLAN

CONF'T
WIRED TOGETHER UNLESS OTHERWISE SPECIFIED. TOP BARS AT MID-

ZONE

L1
325MM 12MM AT 200MM O.C. E.F. 12MM AT 250MM O.C. E.F. - DO -
SPAN , BOTTOM BARS AT SUPPORT , BEND BARS AT BED POINTS IN
SUPERSTRUCTURE. WELDED SPLICES SHALL DEVELOP IN TENSION AT
350MM 16MM AT 250MM O.C. E.F. 12MM AT 300MM O.C. E.F. - DO -
A. Li = LARGEST OF :
LEAST 125% OF THE SPECIFIED YIELD STRENGTH OF THE BAR. NOT 1. h (h>b)

INTERMEDIATE ZONE
MORE THAN 50% OF THE BARS AT ANY ONE SECTION SHALL BE
PERMITTED TO BE SPLICED.
200
1
200 2. Lo/6 1000MM

Lo
LINTEL BEAM STIFFENER

4. IF BEAM REINFORCING BARS END IN A WALL THE CLEAR DISTANCE


COLUMN
1 1
3. 450 MM
FROM THE BAR TO THE FARTHER FACE OF THE WALL SHALL NOT B. FOR COLUMNS REQUIRING SPECIAL CONFINEMENT STEEL.
BE LESS THAN 50 MM EMBEDMENT LENGTH SHALL BE 40 DIAMETER Shi = SPACING OF ALL CONFINEMENT ZONE USING A

CONF'T
FOR TENSION AND 20 DIAMETER FOR COMPRESSION BARS.

ZONE

L1
MAXIMUM SPACING OS 0.20 b , 6Ø OR 200MM. h

5. MINIMUM CONCRETE PROTECTION OF REINFORCING BARS OR SHAPES

CONNECTION
THE AREA OF CONFINEMENT LINKS SHOULD BE DE-

SEE NOTE
BEAM-COL
SHALL BE AS SHOWN ON DETAIL-1.

D&E
6. UNLESS OTHERWISE NOTED IN PLANS OR SPECIFICATIONS , CAMBER
TERMINED.

Sh1/2
1 - 16MMØ

SEE NOTE
C. Sh : = SPACING FOR ALL LINKS & TIES IN INTERMEDIATE 10MMØ TIES 2-12MMØ ON

CONF'T
ALL BEAMS AND GIRDERS AT LEAST 6.5 MM FOR EVERY 3.0 M OF

ZONE
VERTICAL BAR

L1
B&C
AT 150MM O.C. BOTH SIDES
(TYPICAL)
SPAN EXCEPT CANTILEVERS FOR WHICH THE CAMBERS SHALL BE AS
NOTED IN PLANS OR AS ORDERED BY THE DESIGNER , BUT IN CASE
ZONE. SPACING TO BE THE LEAST OF :
SECTION

INTERMEDIATE ZONE
LESS THAN 7.5 MM FOR EVERY 3.0 M OF FREE SPAN. 1. 12Ø

SEE NOTE C
Lo
2. 400MM

Sh2 LAP SEE


NOTE F
CONCRETE SLABS : TYPICAL BEAM CONSTRUCTION JOINT
3. 0.40b
1. ALL REINFORCEMENT SHALL BE 20 MM CLEAR MINIMUM FROM TOP AND

0.2 Sh1
Ø = DIAMETER OF SMALLEST LONGITUDINAL BAR

CONF'T
ZONE
BOTTOM OF SLAB.

L1
2. FOR TWO-WAY SLAB BARS ALONG SHORTER SPAN SHALL BE PLACED IN COLUMN.

Sh
100-150MMØ PIPE
BELOW THOSE ALONG THE LONGER SPAN AT CENTER AND OVER THE D. SPACING AND TOTAL CROSS-SECTIONAL AREA OF HOOPS
LONGER SPAN BARS NEAR THE SUPPORT. UNLESS OTHERWISE INDICA- ELEVATION ELEVATION
b
TED OR SHOWN IN DETAILS THE SPACING OF THE BARS AT THE a
& TIES THROUGH THE BEAM COLUMN CONNECTION
COLUMN STRIPS CAN BE APPROXIMATELY 1-1/3 TIMES OF THE MIDDLE CHB WALL

STRIP BUT IN NO CASE GREATER THAN 2-1/3 TIMES THE SLAB THICK-
(OR ANY OTHER CONNECTING MEMBER). h
SUPPLEMENTARY
NESS. 300MM DOWEL(SAME DIAMETER
CROSS TIES (SEE
NOTE H)
E. ALL HOOP ARRANGEMENTS MUST ALSO BE CAPABLE
AS CHB VERTICAL REINF.)
3. UNLESS OTHERWISE DETAILED IN CONTINOUS SLABS HAVING SAME REIN- 300MM h
OF RESISTING THE APPLIED SHEARS THROUGHOUT
b

HOOPS 12MMØ ON
FORCEMENT RUNNING IN ONE DIRECTION REINFORCING SHALL BE BENDED
2-12MMØ TOP BAR b/a > 10 THE WHOLE COLUMN LENGTH INCLUDING THE BEAM BOTH SIDES
150MM

EXTENDED OR CUT AS SHOWN ON THE SCHEDULE OF SLABS 1000MM


100MM

b > 300MM
20MM

4. TEMPERATURE BARS SHALL BE GENERALLY PLACED NEAR THE TENSION


10MMØ, 1 AT 50
REST AT 250MM O.C.
1-1 COLUMN CONNECTION ZONE.
FACE AND SHALL NOT BE LESS THAN 0.0025 BT. BARS : 6-12MMØ BARS : 3-12MMØ
2-12MMØ BOTTOM BAR CRANK DETAIL F. IN MEDIUM AND HIGH RISK EARTHQUAKE ZONES NOTE :
TIES : 10Ø, 1 AT 50 TIES : 10Ø, 1 AT 50
5. UNLESS OTHERWISE NOTED ALL BEDDED SLABS SHALL REINFORCED WITH 3 AT 100, 3 AT 150
REST AT 250MM
3 AT 100, 3 AT 150
REST AT 250MM
135° (Ø) SPLICES SHOULD BE MADE OUTSIDE OF PLASTIC A. CONDUITS , PIPES & SLEEVES PASSING THROUGH

10MMØ AT 400MMØ O.C. E.W. AT CENTER OF SLAB CONSTRUCTION
JOINTS FOR SAME SHALL NOT BE MORE THAN 3.0 M APART.
SECTION - 1 HINGE ZONES AND ARE TO BE LARGER OF : A SLAB , WALL OR BEAM SHALL NOT IMPAIR
SIGNIFICANTLY THE STRENGTH OF THE CONSTRUC-
STIFFENER COLUMN STIFFENER COLUMN 1. CALCULATED BOND LENGTH
6. PROVIDE EXTRA REINFORCEMENT AT CORNER SLABS (TWO ADJACENT FOR 6" CHB FOR 4" CHB ØM
r = 2ØM (MILD STEEL)
4ØM (HT. STEEL)
TION.
DISCONTINOUS EDGE ) AS SHOWN ON DETAIL-3. 2. 30Ø , FOR Fy = 415 MPa
B. THEY SHALL NOT BE PLACED CLOSER THAN 3 DIA-
7. PROVIDE SUPPLEMENTARY REINFORCEMENT AT SMALL UNFRAMED OPENING TYPICAL DETAIL OF LINTEL BEAM AND STIFFENER COLUMN DETAIL OF HOOP AND 3. 20Ø , FOR Fy = 275 MPa METER OR WIDTHS ON CENTER.
IN FLOOR SLABS AS SHOWN ON DETAIL-4. TIE ANCHORAGE DIMENSIONS
I. DIAMETER OF HOOPS AND CROSS - TIES :
CONCRETE HOLLOW BLOCKS : MILD STEEL REINFORCEMENT : DETAIL - 5
6MM , IF ØM < 20MM
REINFORCEMENT AS TABULATED IN SCHEDULE SHALL BE PROVIDED UNLESS 1. ALL MILD STEEL REINFORCEMENT SHALL CONFORM TO ASTM A-1562 -2T 10MM , IF 20MM <ØM<28MM TYPICAL PIPE SLEEVE DETAIL
OTHERWISE SPECIFIED IN THE PLAN . SEE SCHEDULE -1. AND DEFORMATIONS TO A-305-56 OR LATEST REVISIONS.
2. DEVELOPMENT LENGTH FOR ALL BARS SHALL BE A MINIMUM OF 40 BARS 12MM , IF ØM>28MM
CONCRETE WALLS : DIAMETERS UNLESS OTHERWISE SPECIFIED. ØM = THE DIAMETER OF LONGITUDINAL BAR.
UNLESS OTHERWISE INDICATED IN THE PLANS , WALL REINFORCEMENT SHALL SEE DETAIL - 5.
BE FOLLOWED AS TABULATED IN SCHEDULE -2. SEE SCHEDULE -2.

FOR PERMIT
ARCHITECT: ENGINEER: PROJECT NAME: CLIENT NAME: SHEET CONTENTS: SHEET NO:
CONSTRUCTION NOTES
Proposed 3-Storey Residence w/ Deck & 2-Storey
DEBBIE ANN S. LUA JEFFERSON M. VILLARAZA
Multipurpose Bldg.
Mr. Kirk Chester Dy S-1
ARCHITECT ENGINEER

NOTE: ANY DISCREPANCIES ON ALL DRAWINGS OR


PRC: 0022594 DATE: Feb. 08, 2022 PRC: 118310 DATE: Jan. 07, 2022 Location: Dorotea St, Quezon City RA 545: THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF THE DESIGNER DRAWN BY: CHECKED BY: DATE: SPECIFICATIONS SHALL BE VERIFIED WITH THE
ARCHITECT PRIOR TO IMPLEMENTATION.
AND AS SUCH MUST NOT BE REPRODUCED IN PART OR WHOLE WITHOUT CONSENT.
PTR: 1580136 PLACE: San Juan City, Manila PTR: 9036680 PLACE: Marikina City

You might also like