Purpose:
Purpose of QTB to Familiarized construction team to installation requirements of
Refrigerant Piping Supports
Installation
Refrigerant piping placed underground shall be protected against corrosion.
Supports for refrigeration piping shall be non-combustible.
Refrigerant piping and tubing shall be securely fastened to a permanent support
within 6 feet (1.8 m) following the first bend in such tubing from the compressor and
within 2 feet (610 mm) of each subsequent bend or angle
Refrigerant piping and tubing shall be supported at points not more than 15 feet
(4570 mm) apart.
Refrigerant piping and joints shall be exposed to view for visual inspection and
acceptance by the company representative prior to being covered or enclosed.